HVAC FORMULAS
CFM = ______BTU/Hr / ( 1.08 x Temperature Difference)
TON OF REFRIGERATION -
The amount of heat required to melt a ton (2000 lbs.) of ice at 32属F
288,000 BTU/24 hr.
12,000 BTU/hr.
APPROXIMATELY 2 inches in Hg. (mercury) = 1 psi
WORK =
Force (energy exerted) X Distance
Example: A 150 lb. man climbs a flight of stairs 100 ft. high
Work = 150 lb. X 100 ft.
Work = 15,000 ft.-lb.
ONE HORSEPOWER =
33,000 ft.-lb. of work in 1 minute
ONE HORSEPOWER =
746 Watts
CONVERTING KW to BTU:
1 KW = 3413 BTUs
Example: A 20 KW heater (20 KW X 3413 BTU/KW = 68,260 BTUs)
CONVERTING BTU to KW
3413 BTUs = 1 KW
Example: A 100,000 BTU/hr. oil or gas furnace
(100,000 / 3413 = 29.3 KW)
COULOMB =
6.24 X 1018 (1 Coulomb = 1 Amp)
OHM'S LAW =
E = I x R
I = E / R
R = E / I
Where:
E = voltage (emf)
I = Amperage (current)
R = Resistance (load)
WATTS (POWER) =
volts x amps or P = E x I
P(in KW) = (E x I) / 1000
U FACTOR =
Reciprocal of R factor
1 / R = U
Example:
If R = 19:
U = 1 / 19 = .05 (BTUs transferred / 1 Sq.Ft. / 1尊F / 1 Hour)
VA
(how the secondary of a transformer is rated) = volts X amps
Example: 24V x .41A = 10 VA
ONE FARAD CAPACITY =
1 amp. stored under 1 volt of pressure
MFD (microfarad) =
1 MFD = 1 Farad / 1,000,000
LRA (Locked rotor amps) =
LRA = FLA x 5 (NOTE: This is a commonly used rule-of-thumb, not a direct conversion)
TEV (shown in equilibrium)
46.7# (Bulb Pressure) = 9.7# (Spring Pressure) + 37# (Evaporator Pressure)
Where:
Bulb Pressure = opening force
Spring and Evaporator Pressures = closing forces
RPM of motor = (60Hz x 120) / (No. of Poles)
1800 RPM Motor  slippage makes it about 1750
3600 RPM Motor  slippage makes it about 3450
DRY AIR =
78.0% Nitrogen
21.0% Oxygen
1.0% Other Gases
WET AIR =
Same as dry air plus water vapor
SPECIFIC DENSITY = 1 / Specific Volume
SPECIFIC DENSITY OF AIR = 1 / 13.33 = .075 lbs./cu.ft.
STANDARD AIR =
24 Specific Heat (BTUs needed to raise 1 lb. 1 degree)
SENSIBLE HEAT FORMULA (Furnaces):
BTU/hr.  Specific Heat X Specific Density X 60 min./hr. =
X CFM X DT
.24 X .075 X 60 X CFM X DT = 1.08 X CFM X DT
ENTHALPHY = h =
Sensible heat + Latent heat
TOTAL HEAT FORMULA
(for cooling, humidifying or dehumidifying)
BTU/hr. = Specific Density X 60 min./hr. X CFM X Dh
= 0.75 x 60 x CFM x Dh
= 4.5 x CFM x Dh
Where Dh = Change in Enthalpy
RELATIVE HUMIDITY =
Moisture present / Moisture air can hold
SPECIFIC HUMIDITY =
Grains of moisture per dry air
7000 GRAINS in 1 lb. of water
DEW POINT =
When wet bulb equals dry bulb
TOTAL PRESSURE (Ductwork) =
Static Pressure + Velocity Pressure
CFM =
Area (sq. ft.) X Velocity (ft. min.)
HOW TO CALCULATE AREA
Rectangular Duct
A = L x W
Round Duct
A = (Pi)r族 ...or...(Pi)D族/4
RETURN AIR GRILLES 
Net free area = about 75%
3 PHASE VOLTAGE UNBALANCE =
(100 x maximum deg. from average volts) / Average Volts
NET OIL PRESSURE =
Gross Oil Pressure  Suction Pressure
NOTE: The suction pressure must be measured at the crankcase, not the service valve
COMPRESSION RATIO =
Discharge Pressure Absolute / Suction Pressure Absolute
HEAT PUMP AUXILIARY HEAT 
Sized at 100% of load
ARI HEAT PUMP RATING POINTS =
47属F and 17属F
NON-BLEND REFRIGERANTS:
Constant Pressure = Constant Temperature during
Saturated Condition in an evaporator or condenser
BLENDS
Changing Temperature during Saturated Condition in an evaporator or condenser (See Glide)
28 INCHES OF WC =
1 psi
NATURAL GAS COMBUSTION:
Excess Air = 50%
15 ft.3 of air to burn 1 ft.3 of methane produces:
16 ft.3 of flue gases:
1 ft.3 of oxygen
12 ft.3 of nitrogen
1 ft.3 of carbon dioxide
2 ft.3 of water vapor
Another 15 ft.3 of air is added at the draft hood
GAS PIPING (Sizing  CF/hr.) =
Input BTUs
Heating Value
Example:
80,000 Input BTUs
1000 (Heating Value per CF of Natural Gas)
= 80 CF/hr.
Example:
80,000 Input BTUs
2550 (Heating Value per CF of Propane)
= 31 CF/hr.
FLAMMABILITY LIMITS
Propane Butane Natural Gas
2.4-9.5 1.9-8.5 4-14
COMBUSTION AIR NEEDED
(PC=Perfect Combustion)
(RC=Real Combustion)
Propane
23.5 ft.3 (PC)
36 ft.3 (RC)
Natural Gas
10 ft.3 (PC)
15 ft.3 (RC)
ULTIMATE CO2 13.7% 11.8%
CALCULATING OIL NOZZLE SIZE (GPH):
BTU Input = Nozzle Size (GPH)
140,000 BTUs
OR
BTU Output
140,000 X Efficiency of Furnace
FURNACE EFFICIENCY:
% Efficiency = energy output / energy input
OIL BURNER STACK TEMPERATURE (Net) =
Highest Stack
Temperature minus
Room Temperature
Example: 520属 Stack Temp.  70属 Room Temp. = Net Stack
Temperature of 450属
KELVIN TO CELSIUS:
C = K  273
CELSIUS TO KELVIN:
K = C + 273
ABSOLUTE TEMPERATURE MEASURED IN KELVINS
SINE = side opposite
COSINE = side adjacent
Sin = hypotenuse
Cos = hypotenuse
TANGENT =
side opposite / side adjacent
PERIMETER OF SQUARE:
P = 4s
Where: P = Perimeter and s = side
PERIMETER OF RECTANGLE:
P = 2l + 2w P  Perimeter
l = length
w = width
PERIMETER OF SQUARE
P = a + b + c + d (P = Perimeter)
a = 1st side
b = 2nd side
c = 3rd side
d= 4th
side
PERIMETER OF CIRCLE:
C = (Pi)D = 2(Pi)r
Where:
C = Circumference
(Pi) = 3.1416
D = Diameter
r = radius
AREA OF SQUARE:
a = s族 = s x s
A = Area
s = side
AREA OF RECTANGLE:
A = l x w
Where:
A = Area
l = length
w = width
AREA OF TRIANGLE:
A = 1/2bh
Where:
A = Area
b = base
h = height
AREA OF CIRCLE:
A = (Pi)r族 = (Pi) D族/4
Where:
A = Area
(Pi) = 3.1416
r = radius
D = Diameter
VOLUME OF RECTANGULAR SOLID:
V = l x w x h
Where:
V = Volume
l = length
w = width
h = height
VOLUME OF CYLINDRICAL SOLID:
V = (Pi)r族h = (Pi) D族/4 x h
Where:
V = Volume
p = 3.1416
r = Radius
D = Diameter
h = height
CAPACITANCE IN SERIES:
C = 1 / (C1 + C2)
CAPACITANCE IN PARALLEL:
C = C1 + C2 + . . . . .
GAS LAWS:
Boyles Law: P1 V1 = P2 V2
Where:
P = Pressure (absolute)
V = Volume
Charles Law:
P1 / T1 = P2 / T2
Where:
P = Pressure (absolute)
T = Temperature (absolute)
General Gas Law:
(P1 x V1) / T1 = (P2 x V2) / T2
Where:
P = Pressure (absolute)
V = Volume
T = Temperature (absolute)
PYTHAGOREAN THEOREM:
c2 = a2 + b2
Where:
c = hypotenuse
a & b = sides
Capacity of Schedule 80 steel pipe in foot per length in US gallons:
1 = .0374
1-1/4 = .0666
1-1/2 = .0918
2 = .1535
2-1/2 = .22
3 = .344
4 = .5970
5 = .947
Example 2-1/2" pipe = .22 x 10 feet = 2.2 gallons capacity
Infrared Thermometer Adjustment Values:
Material/Emissivity
Aluminum
Bright/0.09
Anodized/0.55
Oxidized/0.2 to 0.3
Brass
Bright/0.03
Oxidized/0.61
Chromium
Polished/0.08
Copper
Bright/0.05
Oxidized/0.78
Iron and Steel
Polished/0.55
Oxidized/0.85
Nickel
Polished/0.05
Oxidized/0.95
Zinc
Bright/0.23
Oxidized/0.23
Brick
Building/0.45
Paints
White/0.9
Black/0.86
Oil Paints (all)/0.92
Roofing Paper /0.91
Rubber /0.94
Silica /0.42 to 0.62
Water /0.92
Weights and Specific Heats of Substances
Material/Weight (Ib./ft続)/Specific Heat (Btu/lb)
Gases
Air (normal temp)/0.075/0.24
Metals
Aluminum/166.5/0.214
Copper/552/0.094
Iron/480/0.118
Lead/710/0.030
Mercury/847/0.033
Steel/492/0.117
Zinc/446/0.096
Liquids
Alcohol/49.6/0.60
Glycerin/83.6/0.576
Oil/57.5/0.400
Water/62.4/1.000
Others
Concrete/147/0.19
Cork/15/0.48
Glass/164/0.199
Ice/57.5/0.504
Masonry/112/0.200
Paper/58/0.324
Rubber/59/0.48
Sand/100/0.195
Stone/138-200/0.20
Tar/75/0.35
Wood, Oak/48/0.57
Wood, Pine/38/0.47
Linear Measurement Equivalents (U.S. Conventional - SI Metric)
1 inch =
2.54 cm
25.4 mm
25400 袖m
1 foot =
12"
0.304 m
30.48 cm
1 yard =
3'
0.914 m
91.44 cm
1 micron =
0.0000394"
1 millimeter =
1000 袖m
0.0394"
1 centimeter =
10 mm
0.3937"
1 meter =
100 cm
39.37"
1 kilometer =
1000m
0.62137 miles
Area Equivalents ( U.S. to Metric )
1 in族=
0.0065m族
1 ft族=
144 in族
0.093 m族
1 yd族=
1296 in族=
9 ft族=
0.836 m族
Volume Equivalents ( U.S. and Metric )
1 in続=
0.016 L=
16.39 cm続
1 ft続=
1728 in続=
7.481 gal=
28.317 L=
0.0283 m続=
28317 cm続
1 yd続=
27 ft続=
46656 in続
1 gal=
0.1337 ft続=
3.79 L=
231 in続=
3785 cm続
1 cm続=
0.0610237 in続
1 L=
61.03 in続
1000 cm続
0.2642 gal
Velocity Equivalents
1 mi/hr=
1.47 ft/sec
0.87 knot
1.61 km/hr
0.45m/sec
1 ft/sec=
0.68 mi/hr
60 ft/min
0.59 knot
o 1.1 km/hr
0.305 m/sec
1 m/sec=
3.28 ft/sec
2.24 mi/hr
1.94 knot
3.6 km/hr
1 km/hr=
0.91 ft/sec
0.62 mi/hr
0.54 knot
0.28 m/sec
Heat Equivalents
1 Btu=
252 calories
1054.4 J (Joules)
1 kcal (kilocalorie)=
1000 cal
4.1840 kJ
1 Btu/lb=
0.5556 kcal/kg
2.3244 kJ/kg
1kcal/kg=
1.8 Btu/lb
Btu/hr=
0.2931W

More Related Content

Hvac formulas

  • 1. HVAC FORMULAS CFM = ______BTU/Hr / ( 1.08 x Temperature Difference) TON OF REFRIGERATION - The amount of heat required to melt a ton (2000 lbs.) of ice at 32属F 288,000 BTU/24 hr. 12,000 BTU/hr. APPROXIMATELY 2 inches in Hg. (mercury) = 1 psi WORK = Force (energy exerted) X Distance Example: A 150 lb. man climbs a flight of stairs 100 ft. high Work = 150 lb. X 100 ft. Work = 15,000 ft.-lb. ONE HORSEPOWER = 33,000 ft.-lb. of work in 1 minute ONE HORSEPOWER =
  • 2. 746 Watts CONVERTING KW to BTU: 1 KW = 3413 BTUs Example: A 20 KW heater (20 KW X 3413 BTU/KW = 68,260 BTUs) CONVERTING BTU to KW 3413 BTUs = 1 KW Example: A 100,000 BTU/hr. oil or gas furnace (100,000 / 3413 = 29.3 KW) COULOMB = 6.24 X 1018 (1 Coulomb = 1 Amp) OHM'S LAW = E = I x R I = E / R R = E / I Where: E = voltage (emf) I = Amperage (current)
  • 3. R = Resistance (load) WATTS (POWER) = volts x amps or P = E x I P(in KW) = (E x I) / 1000 U FACTOR = Reciprocal of R factor 1 / R = U Example: If R = 19: U = 1 / 19 = .05 (BTUs transferred / 1 Sq.Ft. / 1尊F / 1 Hour) VA (how the secondary of a transformer is rated) = volts X amps Example: 24V x .41A = 10 VA
  • 4. ONE FARAD CAPACITY = 1 amp. stored under 1 volt of pressure MFD (microfarad) = 1 MFD = 1 Farad / 1,000,000 LRA (Locked rotor amps) = LRA = FLA x 5 (NOTE: This is a commonly used rule-of-thumb, not a direct conversion) TEV (shown in equilibrium) 46.7# (Bulb Pressure) = 9.7# (Spring Pressure) + 37# (Evaporator Pressure) Where: Bulb Pressure = opening force Spring and Evaporator Pressures = closing forces RPM of motor = (60Hz x 120) / (No. of Poles) 1800 RPM Motor slippage makes it about 1750 3600 RPM Motor slippage makes it about 3450
  • 5. DRY AIR = 78.0% Nitrogen 21.0% Oxygen 1.0% Other Gases WET AIR = Same as dry air plus water vapor SPECIFIC DENSITY = 1 / Specific Volume SPECIFIC DENSITY OF AIR = 1 / 13.33 = .075 lbs./cu.ft. STANDARD AIR = 24 Specific Heat (BTUs needed to raise 1 lb. 1 degree) SENSIBLE HEAT FORMULA (Furnaces): BTU/hr. Specific Heat X Specific Density X 60 min./hr. = X CFM X DT .24 X .075 X 60 X CFM X DT = 1.08 X CFM X DT
  • 6. ENTHALPHY = h = Sensible heat + Latent heat TOTAL HEAT FORMULA (for cooling, humidifying or dehumidifying) BTU/hr. = Specific Density X 60 min./hr. X CFM X Dh = 0.75 x 60 x CFM x Dh = 4.5 x CFM x Dh Where Dh = Change in Enthalpy RELATIVE HUMIDITY = Moisture present / Moisture air can hold SPECIFIC HUMIDITY = Grains of moisture per dry air 7000 GRAINS in 1 lb. of water
  • 7. DEW POINT = When wet bulb equals dry bulb TOTAL PRESSURE (Ductwork) = Static Pressure + Velocity Pressure CFM = Area (sq. ft.) X Velocity (ft. min.) HOW TO CALCULATE AREA Rectangular Duct A = L x W Round Duct A = (Pi)r族 ...or...(Pi)D族/4 RETURN AIR GRILLES Net free area = about 75% 3 PHASE VOLTAGE UNBALANCE = (100 x maximum deg. from average volts) / Average Volts
  • 8. NET OIL PRESSURE = Gross Oil Pressure Suction Pressure NOTE: The suction pressure must be measured at the crankcase, not the service valve COMPRESSION RATIO = Discharge Pressure Absolute / Suction Pressure Absolute HEAT PUMP AUXILIARY HEAT Sized at 100% of load ARI HEAT PUMP RATING POINTS = 47属F and 17属F NON-BLEND REFRIGERANTS: Constant Pressure = Constant Temperature during Saturated Condition in an evaporator or condenser BLENDS
  • 9. Changing Temperature during Saturated Condition in an evaporator or condenser (See Glide) 28 INCHES OF WC = 1 psi NATURAL GAS COMBUSTION: Excess Air = 50% 15 ft.3 of air to burn 1 ft.3 of methane produces: 16 ft.3 of flue gases: 1 ft.3 of oxygen 12 ft.3 of nitrogen 1 ft.3 of carbon dioxide 2 ft.3 of water vapor Another 15 ft.3 of air is added at the draft hood GAS PIPING (Sizing CF/hr.) = Input BTUs Heating Value Example: 80,000 Input BTUs 1000 (Heating Value per CF of Natural Gas) = 80 CF/hr.
  • 10. Example: 80,000 Input BTUs 2550 (Heating Value per CF of Propane) = 31 CF/hr. FLAMMABILITY LIMITS Propane Butane Natural Gas 2.4-9.5 1.9-8.5 4-14 COMBUSTION AIR NEEDED (PC=Perfect Combustion) (RC=Real Combustion) Propane 23.5 ft.3 (PC) 36 ft.3 (RC) Natural Gas 10 ft.3 (PC) 15 ft.3 (RC)
  • 11. ULTIMATE CO2 13.7% 11.8% CALCULATING OIL NOZZLE SIZE (GPH): BTU Input = Nozzle Size (GPH) 140,000 BTUs OR BTU Output 140,000 X Efficiency of Furnace FURNACE EFFICIENCY: % Efficiency = energy output / energy input OIL BURNER STACK TEMPERATURE (Net) = Highest Stack Temperature minus Room Temperature Example: 520属 Stack Temp. 70属 Room Temp. = Net Stack Temperature of 450属 KELVIN TO CELSIUS: C = K 273
  • 12. CELSIUS TO KELVIN: K = C + 273 ABSOLUTE TEMPERATURE MEASURED IN KELVINS SINE = side opposite COSINE = side adjacent Sin = hypotenuse Cos = hypotenuse TANGENT = side opposite / side adjacent PERIMETER OF SQUARE: P = 4s Where: P = Perimeter and s = side PERIMETER OF RECTANGLE: P = 2l + 2w P Perimeter l = length
  • 13. w = width PERIMETER OF SQUARE P = a + b + c + d (P = Perimeter) a = 1st side b = 2nd side c = 3rd side d= 4th side PERIMETER OF CIRCLE: C = (Pi)D = 2(Pi)r Where: C = Circumference (Pi) = 3.1416 D = Diameter r = radius AREA OF SQUARE: a = s族 = s x s A = Area s = side
  • 14. AREA OF RECTANGLE: A = l x w Where: A = Area l = length w = width AREA OF TRIANGLE: A = 1/2bh Where: A = Area b = base h = height AREA OF CIRCLE: A = (Pi)r族 = (Pi) D族/4 Where: A = Area (Pi) = 3.1416 r = radius D = Diameter
  • 15. VOLUME OF RECTANGULAR SOLID: V = l x w x h Where: V = Volume l = length w = width h = height VOLUME OF CYLINDRICAL SOLID: V = (Pi)r族h = (Pi) D族/4 x h Where: V = Volume p = 3.1416 r = Radius D = Diameter h = height CAPACITANCE IN SERIES: C = 1 / (C1 + C2)
  • 16. CAPACITANCE IN PARALLEL: C = C1 + C2 + . . . . . GAS LAWS: Boyles Law: P1 V1 = P2 V2 Where: P = Pressure (absolute) V = Volume Charles Law: P1 / T1 = P2 / T2 Where: P = Pressure (absolute) T = Temperature (absolute) General Gas Law: (P1 x V1) / T1 = (P2 x V2) / T2 Where: P = Pressure (absolute) V = Volume
  • 17. T = Temperature (absolute) PYTHAGOREAN THEOREM: c2 = a2 + b2 Where: c = hypotenuse a & b = sides Capacity of Schedule 80 steel pipe in foot per length in US gallons: 1 = .0374 1-1/4 = .0666 1-1/2 = .0918 2 = .1535 2-1/2 = .22 3 = .344 4 = .5970 5 = .947 Example 2-1/2" pipe = .22 x 10 feet = 2.2 gallons capacity Infrared Thermometer Adjustment Values: Material/Emissivity Aluminum Bright/0.09
  • 18. Anodized/0.55 Oxidized/0.2 to 0.3 Brass Bright/0.03 Oxidized/0.61 Chromium Polished/0.08 Copper Bright/0.05 Oxidized/0.78 Iron and Steel Polished/0.55 Oxidized/0.85 Nickel Polished/0.05 Oxidized/0.95 Zinc Bright/0.23 Oxidized/0.23 Brick Building/0.45 Paints White/0.9 Black/0.86 Oil Paints (all)/0.92
  • 19. Roofing Paper /0.91 Rubber /0.94 Silica /0.42 to 0.62 Water /0.92 Weights and Specific Heats of Substances Material/Weight (Ib./ft続)/Specific Heat (Btu/lb) Gases Air (normal temp)/0.075/0.24 Metals Aluminum/166.5/0.214 Copper/552/0.094 Iron/480/0.118 Lead/710/0.030 Mercury/847/0.033 Steel/492/0.117 Zinc/446/0.096 Liquids Alcohol/49.6/0.60 Glycerin/83.6/0.576 Oil/57.5/0.400 Water/62.4/1.000
  • 21. 1 yard = 3' 0.914 m 91.44 cm 1 micron = 0.0000394" 1 millimeter = 1000 袖m 0.0394" 1 centimeter = 10 mm 0.3937" 1 meter = 100 cm 39.37" 1 kilometer = 1000m 0.62137 miles Area Equivalents ( U.S. to Metric )
  • 22. 1 in族= 0.0065m族 1 ft族= 144 in族 0.093 m族 1 yd族= 1296 in族= 9 ft族= 0.836 m族 Volume Equivalents ( U.S. and Metric ) 1 in続= 0.016 L= 16.39 cm続 1 ft続= 1728 in続= 7.481 gal= 28.317 L= 0.0283 m続= 28317 cm続
  • 23. 1 yd続= 27 ft続= 46656 in続 1 gal= 0.1337 ft続= 3.79 L= 231 in続= 3785 cm続 1 cm続= 0.0610237 in続 1 L= 61.03 in続 1000 cm続 0.2642 gal Velocity Equivalents 1 mi/hr= 1.47 ft/sec 0.87 knot 1.61 km/hr
  • 24. 0.45m/sec 1 ft/sec= 0.68 mi/hr 60 ft/min 0.59 knot o 1.1 km/hr 0.305 m/sec 1 m/sec= 3.28 ft/sec 2.24 mi/hr 1.94 knot 3.6 km/hr 1 km/hr= 0.91 ft/sec 0.62 mi/hr 0.54 knot 0.28 m/sec Heat Equivalents 1 Btu=
  • 25. 252 calories 1054.4 J (Joules) 1 kcal (kilocalorie)= 1000 cal 4.1840 kJ 1 Btu/lb= 0.5556 kcal/kg 2.3244 kJ/kg 1kcal/kg= 1.8 Btu/lb Btu/hr= 0.2931W