This document provides a product manual for a thermostat. It includes instructions on installation, wiring, settings, functions, and specifications. The thermostat can be used for heating or cooling control, has a temperature range of -50 to 110 degrees, and features settings for mode, hysteresis, calibration, and delay among others. Instructions are provided on how to operate, set parameters, and troubleshoot the thermostat.
2. Installation opening size:
Wiring diagram鐚
Option
switch
5 6 874
NTCPower
321
12V
12V
Load
Terminals 1 and 2: Normally opened contact of relay
Terminals 3 and 4: Connect the power 12V
Terminals 5 and 6: The factory parameter settings of thermostat can be
locked after a short circuit, the user can not modify.
Terminals 7 and 8: Temperature connection sensor
Note: The load refers to the heating or cooling equipment on control.
Electrical performance:
Temperature measurement range: -50 ~ 110
Temperature control range: -50 ~ 110
Temperature measurement error: 賊 0.5
Sensor Type: NTC (10K/3435)
Control accuracy: 1
Working voltage: AC/DC12V
Working current: <2W
Relay contact point current: AC 7A/220V
Data storage : Yes
Working temperature: 0 ~ 50
Storage temperature: -10 ~ 60
3. Key Instructions:
1. RST: Press RST key to switch on and off, press the RST key on the
power-off state once to turn on, on the power-on state, press the RST key
for three seconds and hold on, then it will be off.
2. SET:
A: Press the SET key once to enter the temperature control setting, press
or button to adjust, press or button for three seconds and hold
to enter the fast adjusting mode, press the SET key again to exit setting
mode.
B: Press and hold SET key for three seconds to enter the system menu
settings, press the or key to select the adjustment menu, press SET
key once to enter the appropriate parameter settings, press or to
adjust the parameters needed to be modified, after being adjusted, press
the RST key to exit, or exit as the system delay for 5 seconds.
: Up key
: Down key
Operating Instructions:
LED Status Description:
The WORK lights at the left side of the screen is used as working indicator
lights, flashing is to indicate the delay of cooling or heating, if the LED is
always on ,it indicates it is on the status of cooling or heating .
The SET light at the left side of the screen lights is used as setting indicator
lights, if the LED is always on ,it indicates it is on the status of setting.
.
Function Instructions:
Press RST key to open the thermostat, on the running status, press this key
for 3 seconds, then the thermostat can be turned off.
Cooling, heating function:
Cooling Mode: When the measured temperature is higher than or equal to
the set value + hysteresis, the relay picks up to start the output; When the
measured temperature below the set value, the relay off and close the output.
Heating mode: When the measured temperature is higher than or equal to
the set value, the relay off, turn off the output; When the measured
temperature below the set value - hysteresis, the relay picks up to start the
output.
Example for Setting: If it is set to heating mode, set the temperature to 25
degrees, hysteresis is set to 5, then when the measured temperature is
higher than or equal to 25 degrees, the relay is off, close the output.
When the temperature is below 20 degrees, pick up the relay again, to
start the output.
Example for Setting: If it is set to cooling mode, set the temperature to 25
degrees, hysteresis is set to 5, then when the measured temperature is
below 25 degrees, the relay is off, close the output. When the
temperature is higher than or equal to 30 degrees, pick up the relay again,
to start the output.
Cooling, heating mode setting:
Press "SET" key and hold more than 3 seconds to enter the menu display, the
screen appears "HC" code, press the "SET" key to display the working mode,
press the "" or "" to adjust the display, C means cooling mode; H means
heating mode.
Hysteresis function:
Hysteresis setting limits the maximum interval between the opening and
stopping, this machine minimum interval between the opening and stopping is
4. 1 , the maximum is 15 .
Hysteresis settings:
Press "SET" key and hold more than 3 seconds to enter the menu display,
with "" or "" key adjusted to the screen, appearing "D" code, press the
"SET" key to display the hysteresis set value, press " "Or""key to adjust
the parameters.
Temperature calibration funtion:
When there is deviation between the measuring temperature and standard
temperature, use the temperature calibration function, make the machine
measurements value consistent with the standard temperature, the after
calibration temperature= the before calibration temperature + calibration value
(calibration value can be positive number, negative number, and 0) .
Temperature calibration settings:
Press "SET" key and hold more than 3 seconds to enter the menu display,
with "" or "" key adjusted to the screen, appearing "CA" code, press the
"SET" key to display the temperature calibration settings, press " "Or""key
to adjust the parameters.
For example: When we measure the probe temperature was 25 degrees,it
displays 25 degrees as the CA is 0, it displays 26 degrees as the CA is 1,
it displays 24 degrees as the CA is -1. This function is generally applied
when the probe can not measure directly the measured object. For
example, we place the probe at the outside of a cup to measure its water
temperature, we need to adjust the CA parameters because of the heat
loss of the cup, so that the display temperature can be in accordance
with cup temperature.
Delay Protection Funtion:
In the cooling mode, the first power on, when the measured value above the
set value + hysteresis value, the machine will not immediately start cooling, it
needs to set the delay time, then the machine can run to start cooling; once the
interval between two cooling is larger than the delay time, the machine
immediately starts cooling, once the interval between two cooling is less than
the delay time, the machine must run the remaining delay time to start cooling.
The delay time is started to calculate from stopping the machine. The delay
time of heating mode is as same as the cooling mode.
Note: It is recommended that only the device that use compressor cooling can
use the delay start function, the user who don't need delay start function
please set this parameter to 0.
Delay Protection Setting:
Press "SET" key and hold more than 3 seconds to enter the menu display,
with "" or "" key adjusted to the screen, appearing "PT" code, press the
"SET" key to display the delay setting value, then press the " "or ""key to
adjust the parameters.
Upper and lower limit functions:
The setting of HS and LS limit the set range of control temperature point , for
example: HS is set to +15, LS is set to -10, the control temperature can only be
adjusted between -10 and +15, when the control temperature to -10 then press
"" key, the display will remain on the status of -10 and not decrease; when
the control temperature to +15 then press "" key, the display will on the
status of 15 and not incease. If the set point outside this range, it needs to
firstly change the value of HS and LS, then it can be achieved.
Upper and lower limit settings:
Press "SET" key and hold more than 3 seconds to enter the menu display,
5. with "" or "" key adjusted to the screen, appearing "HS" or "LS" code,
press the "SET" key to display the upper or lower limit set value, Then press
"" or "" key to adjust the parameters. HS means upper limit. LS means
lower limit.
For example: the upper and lower limits are used to limit the range of control
temperature that can be set, such as: LS is 10, HS 20, then press the SET key
to adjust the temperature control, it can only be varied between 10 and 20.
Menu code selection:
Symbol Details Setting range Factory
settings
Units
HC Heating /
cooling
H/C C
D Hysteresis 1鐔15 5
LS The
minimum set
limit
-50鐔110 -50
HS The
maximum set
limit
-50鐔110 110
CA Temperature
calibration
-5鐔+5 0
PT Delay time 0鐔10 1 Minutes
fault tips:
1)When the sensor disconnected, the screen displays --- and close the
heating wire
2)When the sensor detects the temperature is below -50 degrees, the screen
displays LLL
3)When the sensor detects a temperature higher than 110 degrees, the
screen displays HHH
Caution for using:
Cooling, heating load must not exceed the output contact capacity, or it
may result in machine damage and cause a fire.
Various connecting wire must be well connected with the terminal,
otherwise, it would result in reducing the reliability of machine.
When connecting the wire, please separate power supply, relays, sensors,
otherwise it will damage the machine.