The M6000-T1-T2-AN is a multi-stage display controller with 6 individually programmable outputs and inputs for 2 temperature sensors. It allows users to customize their HVAC control system by setting parameters for each output like temperature set points, differentials, logic, and delays. The controller can be used for applications with multiple cooling and heating stages controlled by temperature or analog sensors. It provides an easy to program solution for complex HVAC control needs.
1 of 4
Download to read offline
More Related Content
M6000 t1-t2-an-air-conditione-controller
1. meitav-tec
M6000-T1-T2-AN
M6000 (12V) PS104
Multi-stage display controller with
individually programmable outputs,
2 outputs for Fan, 2 temperature
sensors and Fault.
General Features
The M6000-T1-T2-AN controller is the • Main Supply - 230Vac with power supply.
best multi-stage display controller on • Range temperature from 0°C-65°C
the market today. As opposed to many • Range set point for each output 0°C-60°C
complicated units, the M6000-T1-T2-AN • 6 programmable outputs, each output
makes it incredibly easy to pre-set corresponds to a stage- parameters that can be
stages and all other parameters. This, set are:
plus the 6 individually programmed - Set point
outputs, gives users the unique ability - Input to operate by: Analog, T1 or T2 (2
to “custom-build” their entire HVAC different temperature sensors) – inputs may be
control system. combined
- Differential (∆T between stages)
The M6000-T1-T2-AN offers the - Logic for output- COOL or HEAT
following: Ex: Humidifier- If HEAT is selected, output will be
• 6 outputs- fully programmable activated only if set point is HIGHER than actual
• 2 outputs for On Indication (fan) humidity
• Input for 2 temperature sensors to be - Compressor delay – Yes or No
used separately for each output (Meitav- - All outputs have Random start
tec sensors) • Analogue input can be set for different scales
•Analog Inputs (0-10Vdc) to be used (0 to 100 as % or 0 to adjustable)
separately for each output (humidity, • Fault input – Normally Open (all unit OFF)
pressure, water flow, etc)
The M6000-T1-T2-AN is suitable for even
the largest of applications such as
chillers and big air-handling units.
File: M6000-T1-T2.PPT
Pg.1 www.meitavtec.com | Email: info@meitavtec.com | Tel: +972 (3) 962 6462 Rev. 1.1 Date: 16.03.06
2. meitav-tec
M6000-T1-T2-AN
Electrical Diagram – Connection to PS-104
On
Return Air Sensor
Return Air Sensor
Indication
Stages (Fan)
Analog Input
T2 (Option)
T1 (Option)
Main Input
Out 1 (2A)
Out 2 (2A)
Out 3 (2A)
Out 4 (2A)
Out 6 (2A)
Out 5 (2A)
Out 7 (2A)
Out 8 (2A)
(Option)
230Vac
15 14 17 13 12 11 16 17 ~ 0 T1 T1 T2 T2 T3 T3
PS-104
2 3 21 4 5 6 1 22 7 8 9 10 20
13x0.5 12Vdc
10 20 1 2 3 4 5 6 7 8 22 21 9
M6000-T1-T2-AN
Electrical Diagram – Connection to PS-104-DRY
Temperature Sensor
Temperature Sensor
Dry Contact Outputs – Max 220Vac,6A
Outdoor Coil Unit B
Outdoor Coil Unit A
Return Air Sensor
On/Off Command
On/Off Command
Temp. Controller
T1 (Option)
Not Working
Not Working
Main Input
High Temp.
Low Temp.
A/C Unit A
A/C Unit A
A/C Unit B
A/C Unit B
Not in use
230Vac
Failure
Alarm
Alarm
~ 0 T1 T1 T2 T2 T3 T3
A8 B8 A3 B3 A7 B7 A1 B1 A2 B2 A4 B4
ז A5 B5 A6 B6
PS-104-DRY
22 21 1 2 3 4 5 6 7 8 9 10 20
12x0.5 12Vdc
10 20 1 2 3 4 5 6 7 8 22 21 9
M6000-T1-T2-AN
File: M6000-T1-T2.PPT
Pg.2 www.meitavtec.com | Email: info@meitavtec.com | Tel: +972 (3) 962 6462 Rev. 1.1 Date: 16.03.06
3. meitav-tec
M6000-T1-T2-AN
Sample Application
Air Handler with:
• 2 stages of cool (compressors) • Outdoor Temperature Sensor
• 2 stages of heat • Dehumidifier with stage cool 1
• Humidifier • Fresh Air damper based on outdoor temp.
Configuration for Sample Application
Stage/ System Control
Logic Setting Remarks
Output connection By
Tset – 20 First stage of cool and Dehumidifier
Cool 1
1 T1+Analog Cool An On – 55 With Time Delay (Td 1)
(Compressor)
An Off - 70 Differential 2˚C
Second stage of cool to start on 25˚C
Cool 2 With Time delay (Td 1)
2 T1 Cool Tset - 25
(Compressor)
Differential 2˚C
An On – 50 Humidifier set point 50%
3 Humidifier Analog -
An Off - 40 With a dead band of 10% bellow
First stage of Heat and reheat when
Dehumidifier On
4 Heat 1 T1 Heat Tset - 25
No time delay (Td 0)
Differential 2˚C
This is for Freeze protection – based
5 Heat 2 T2 Heat Tset - 3
on outdoor temperature
The fresh air damper will open only
Fresh Air
6 T2 Heat Tset – 21 when the outdoor temperature will be
Damper
less than 21˚C
This output will switch on the fan when
7 Fan for Cool On - -
outputs 1 to 3 are active
This output will switch on the fan when
8 Fan for Heat On - -
outputs 4 to 6 are active
File: M6000-T1-T2.PPT
Pg.3 www.meitavtec.com | Email: info@meitavtec.com | Tel: +972 (3) 962 6462 Rev. 1.1 Date: 16.03.06
4. meitav-tec
M6000-T1-T2-AN
Dimensions
15mm 53mm 15mm
38mm 45mm 43mm 40mm 30mm
Specifications – M6000 Dimensions –PS104
Temperature Range 10°C ÷ 30°C Length 147 mm
Weight 0.25 Kg Width 87 mm
Scale °C Height 40 mm
Color White Weight 0.368 Kg
Accuracy 1°C
Plastic PC/ABS
Flammability UL94V-0
Temperature Input 50K@25°C
Accessories
Part Number Description
PS-104 Power Supply
PS-104-DRY Power Supply with dry contacts
RS01 Temperature Sensor into decorative box
TS01 Temperature Sensor - 80 cm Cable
RS02 Average Temperature Sensor into decorative box
RS03 Room Temperature Sensor ±3°C
DT02 Duct Temperature Sensor
File: M6000-T1-T2.PPT
Pg.4 www.meitavtec.com | Email: info@meitavtec.com | Tel: +972 (3) 962 6462 Rev. 1.1 Date: 16.03.06