際際滷

際際滷Share a Scribd company logo
08/02
05/02/03
1 1
05/02/03
1
Busbar Protection
Protection & Contr担le / Application
Rev. A JM, September 2004
08/02
05/02/03
2 2
Without Busbar Protection
F2
F1
z There are fewer faults on busbars than on other parts of the
power system.
z No risk of dislocation of system due to accidental operation of
busbar protection.
Argues
08/02
05/02/03
3 3
Without Busbar Protection
F2
F1
z Slow fault clearance.
Busbar faults at F1 and F2 are cleared by remote time
delayed protection on circuits feeding the faults:
Time Delayed Overcurrent or
Time Delayed Distance Protection
Drawbacks
08/02
05/02/03
4 4
With Busbar Protection
BUSBAR
ZONE
F1
z Fast clearance by breakers at the busbars
08/02
05/02/03
5 5
With Busbar Protection
BUSBAR
ZONE
F2
F1
z Where busbars are sectionalised,
Protection can limit the amount of system
disruption for a busbar fault
08/02
05/02/03
6 6
With Busbar Protection
21 21
87BB
87BB
1/2
SS
1
SS
2
SS
3
08/02
05/02/03
7 7
With Busbar Protection
21 21
87BB
87BB
2/2
08/02
05/02/03
8 8
With No Busbar Protection
21 21 21
21 21
1/2
08/02
05/02/03
9 9
With No Busbar Protection
21 21
2/2
21
21 21
08/02
05/02/03
10 10
With Burbar protection
21 21 21
21 21
21 21
87BB
87BB
With No Burbar protection
08/02
05/02/03
11 11
Busbar Faults Are Usually Permanent
Causes of Busbar Faults :
z Falling debris
z Insulation failures
z Circuit breaker failures
z Current transformer failures
z Isolators switchs operated on load or outside their ratings
z Safety earths left connected
Therefore :
Circuit breakers should be tripped and locked out by busbar
protection
08/02
05/02/03
12 12
Busbar Protection must be :
z RELIABLE
 Failure to trip could cause widespread damage to the substation
z STABLE
 False tripping can cause widespread interruption of supplies to
customers / possible power system instability
z DISCRIMINATING
 Should trip the minimum number of breakers to clear the fault
z FAST
 To limit damage and possible power system instability
08/02
05/02/03
13 13
Methods of Providing Busbar Protection
z Frame to Earth (Leakage) Protection
z Blocking Scheme Protection
z Differential Protection : High Impedance
Low Impedance
Insulation
>I
>I >I >I >I
>I
08/02
05/02/03
14 14
05/02/03
14
Frame Leakage Protection
Protection & Contr担le / Application
Rev. A JM, September 2004
08/02
05/02/03
15 15
Frame Leakage Busbar Protection
Insulation
>I
08/02
05/02/03
16 16
Frame Leakage Busbar Protection
>I
08/02
05/02/03
17 17
Frame Leakage Busbar Protection
>I
08/02
05/02/03
18 18
Frame Leakage Busbar Protection
>I
>I
08/02
05/02/03
19 19
Frame Leakage Busbar Protection
z Can detect only earth faults
z Switchgear must be insulated from earth (by standing on
concrete plinth)
z Only one single earth conductor allowed on switchgear
z All cable glands must be insulated
z Switchgear sections must be insulated
08/02
05/02/03
20 20
Frame Leakage Busbar Protection
Neutral Check
>I
>I
False Operation
because induced
loop
No operation
prevents from
false trip
08/02
05/02/03
21 21
Frame Leakage Busbar Protection
Neutral Check
>I
>I
08/02
05/02/03
22 22
Neutral Check
Frame Leakage Busbar Protection
>I
>I
08/02
05/02/03
23 23
05/02/03
23
Blocking Scheme Protection
Protection & Contr担le / Application
Rev. A JM, September 2004
08/02
05/02/03
24 24
>I >I >I >I
>I
Blocking Scheme Busbar Protection
08/02
05/02/03
25 25
>I >I >I >I
>I
Blocking Scheme Busbar Protection
08/02
05/02/03
26 26
>I >I >I >I
>I
Blocking Scheme Busbar Protection
08/02
05/02/03
27 27
05/02/03
27
High Impedance Protection
Protection & Contr担le / Application
Rev. A JM, September 2004
08/02
05/02/03
28 28
08/02
05/02/03
28
Single Bus Substation
08/02
05/02/03
29 29
Single Bus Substation
P1
P2
S1
S2
P1
P2
S1
S2
P1
P2
S1
S2
08/02
05/02/03
30 30
Single Bus Substation
08/02
05/02/03
31 31
Single Bus Substation
08/02
05/02/03
32 32
Single Bus Substation
08/02
05/02/03
33 33
08/02
05/02/03
33
Double Bus Substation
08/02
05/02/03
34 34
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
a
b
Current
P1
P2
S1
S2
P1
P2
S1
S2
P1
P2
S1
S2
P1
P2
S1
S2
P1
P2
S1
S2
08/02
05/02/03
35 35
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
a
b
Current
08/02
05/02/03
36 36
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
a
b
Current
08/02
05/02/03
37 37
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
a
b
Current
08/02
05/02/03
38 38
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
a
b
Current
08/02
05/02/03
39 39
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
a
b
Current
08/02
05/02/03
40 40
Isolator Auxiliary Switches
Tripping switching
Bus A
Current
Bus B
a
b
Tripping a
b
08/02
05/02/03
41 41
Interposing CT are not acceptable
z Main CT must be identical
z Current switching via auxilliary relay is not acceptable.
Requirement of number of position contact (Disconnector
switch) is high
08/02
05/02/03
42 42
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
a
b
Current
08/02
05/02/03
43 43
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
a
b
Bus A
Bus B
a
b
Current
Current
08/02
05/02/03
44 44
Isolator Auxiliary Switches
On Load Transfer
Bus A
Bus B
a
b
Current
08/02
05/02/03
45 45
Isolator Auxiliary Switches
On Load Transfer
Bus A
Bus B
a
b
Current
08/02
05/02/03
46 46
Isolator Auxiliary Switches
On Load Transfer
Bus A
a
b
Bus B
Current
08/02
05/02/03
47 47
Isolator Auxiliary Switches
On Load Transfer
Bus A
Bus B
a
b
Current
08/02
05/02/03
48 48
Isolator Auxiliary Switches
On Load Transfer
Bus A
Bus B
a
b
Current
08/02
05/02/03
49 49
Isolator Auxiliary Switches
On Load Transfer
Bus A
Bus B
a
b
Current
08/02
05/02/03
50 50
Isolator Auxiliary Switches
On Load Transfer
Bus A
Bus B
a
b
Current
08/02
05/02/03
51 51
Isolator Auxiliary Switches
Check Zone
Bus A
Bus B
Trip
Bus
A
Trip
Bus
B
Zone A
Zone B
08/02
05/02/03
52 52
Isolator Auxiliary Switches
Check Zone
Bus A
Bus B
Trip
Bus
A
Trip
Bus
B
Zone A
Zone B
Current
switching
failure
False
Tripping
08/02
05/02/03
53 53
Isolator Auxiliary Switches
Check Zone
Bus A
Bus B
Trip
Bus
A
Trip
Bus
B
Check
Zone
Zone A
Zone B
08/02
05/02/03
54 54
Isolator Auxiliary Switches
Check Zone
Bus A
Bus B
Trip
Bus
A
Trip
Bus
B
Zone A
Zone B
08/02
05/02/03
55 55
Isolator Auxiliary Switches
Check Zone
Bus A
Bus B
Trip
Bus
A
Trip
Bus
B
Check
Zone
08/02
05/02/03
56 56
08/02
05/02/03
56
One Breaker and a Half
Substation
08/02
05/02/03
57 57
Bus A Bus
B
P1
P2
S1
S2
P1
S1
P2
S2
P1
P2
S1
S2
08/02
05/02/03
58 58
Bus A Bus
B
08/02
05/02/03
59 59
Bus A Bus
B
08/02
05/02/03
60 60
Bus A Bus
B
08/02
05/02/03
61 61
Bus A Bus
B
08/02
05/02/03
62 62
Bus A Bus
B
08/02
05/02/03
63 63
Bus A Bus
B
P1
S1
P2
S2
P1
S1
P2
S2
P1
S1
P2
S2
P1
S1
P2
S2

More Related Content

11-BUSBAR_PROTECTION_BUSBAR_PROTECTION_RF.pdf