際際滷

際際滷Share a Scribd company logo
Power System Protection
Dr. Ibrahim El-Amin
Protective Device Coordination
Definition
 Overcurrent Coordination
 A systematic study of current responsive devices
in an electrical power system.
Objective
 To determine the ratings and settings of
fuses, breakers, relay, etc.
 To isolate the fault or overloads.
Criteria
 Economics
 Available Measures of Fault
 Operating Practices
 Previous Experience
Design
 Open only PD upstream of the fault or overload
 Provide satisfactory protection for overloads
 Interrupt SC as rapidly (instantaneously) as
possible
 Comply with all applicable standards and codes
 Plot the Time Current Characteristics of
different PDs
Analysis
When:
 New electrical systems
 Plant electrical system expansion/retrofits
 Coordination failure in an existing plant
Protection vs. Coordination
 Coordination is not an exact science
 Compromise between protection and
coordination
 Reliability
 Speed
 Performance
 Economics
 Simplicity
Protection
 Prevent injury to personnel
 Minimize damage to components
 Quickly isolate the affected portion of the system
 Minimize the magnitude of available short-circuit
Spectrum Of Currents
 Load Current
 Up to 100% of full-load
 115-125% (mild overload)
 Overcurrent
 Abnormal loading condition (Locked-Rotor)
 Fault Current
 Fault condition
 Ten times the full-load current and higher
Coordination
 Limit the extend and duration of service
interruption
 Selective fault isolation
 Provide alternate circuits
Coordination
t
I
C B A
C
D
D B
A
Equipment
 Motor
 Transformer
 Generator
 Cable
 Busway
Capability / Damage Curves
t
I
I2
2
t
Gen
I2
t
Motor
Xfmr
I2
t
Cable
I2
t
Transformer Category
ANSI/IEEE C-57.109
Minimum nameplate (kVA)
Category Single-phase Three-phase
I 5-500 15-500
II 501-1667 501-5000
III 1668-10,000 5001-30,000
IV above 1000 above 30,000
Infrequent Fault Incidence Zones for Category II & III Transformers
* Should be selected by reference to the frequent-fault-incidence protection curve or for
transformers serving industrial, commercial and institutional power systems with secondary-side
conductors enclosed in conduit, bus duct, etc., the feeder protective device may be selected by
reference to the infrequent-fault-incidence protection curve.
Source: IEEE C57
Source
Transformer primary-side protective device
(fuses, relayed circuit breakers, etc.) may be
selected by reference to the infrequent-fault-
incidence protection curve
Category II or III Transformer
Fault will be cleared by transformer
primary-side protective device
Optional main secondary side protective device.
May be selected by reference to the infrequent-fault-
incidence protection curve
Feeder protective device
Fault will be cleared by transformer primary-side
protective device or by optional main secondary-
side protection device
Fault will be cleared by
feeder protective device
Infrequent-Fault
Incidence Zone*
Feeders
Frequent-Fault
Incidence Zone*
Transformer
t
(sec)
I (pu)
Thermal
200
2.5
I
2
t = 1250
2
25
Isc
Mechanical
K=(1/Z)
2
t
(D-D LL) 0.87
(D-R LG) 0.58
Frequent Fault
Infrequent Fault
Inrush
FLA
5010566.ppt
Transformer Protection
MAXIMUM RATING OR SETTING FOR OVERCURRENT DEVICE
PRIMARY SECONDARY
Over 600 Volts Over 600 Volts 600 Volts or Below
Transformer
Rated
Impedance
Circuit
Breaker
Setting
Fuse
Rating
Circuit
Breaker
Setting
Fuse
Rating
Circuit Breaker
Setting or Fuse
Rating
Not more than
6%
600 % 300 % 300 % 250% 125%
(250% supervised)
More than 6%
and not more
than 10%
400 % 300 % 250% 225% 125%
(250% supervised)
Table 450-3(a) source: NEC
Protective Devices
 Fuse
 Relay (50/51 P, N, G, SG, 51V, 67, 46, 79, 21, )
 Thermal Magnetic
 Low Voltage Solid State Trip
 Electro-Mechanical
 MCP
 Overload Heater
Fuse
 Non Adjustable Device
 Continuous and Interrupting Rating
 Voltage Levels
 Characteristic Curves
 Min. Melting
 Total Clearing
 Application
Minimum Melting
Time Curve
Total Clearing
Time Curve
Current Limiting Fuse
(CLF)
 Limits the peak current of short-circuit
 Reduces magnetic stresses (mechanical
damage)
 Reduces thermal energy
5010566.ppt
Symmetrical RMS Amperes
Peak
Let-Through
Amperes
100 A
60 A
15% PF (X/R = 6.6)
12,500
5,200
230,000
300 A
100,000
Let-Through Chart
Fuse
Generally:
 CLF is a better short-circuit protection
 Non-CLF (expulsion fuse) is a better Overload
protection
Selectivity Criteria
Typically:
 Non-CLF: 140% of full load
 CLF: 150% of full load
Molder Case CB
 Thermal-Magnetic
 Magnetic Only
 Integrally Fused
 Current Limiting
 High Interrupting
Capacity
Types
 Frame Size
 Trip Rating
 Interrupting Capability
 Voltage
Thermal Minimum
Thermal Maximum
Magnetic
(instantaneous)
LVPCB
 Voltage and Frequency Ratings
 Continuous Current / Frame Size
 Override (12 times cont. current)
 Interrupting Rating
 Short-Time Rating (30 cycle)
 Fairly Simple to Coordinate
480 kV
CB 2
CB 1
CB 2
CB 1
IT
ST PU
ST Band
LT PU
LT Band
If =30 kA
Motor Protection
 Motor Starting Curve
 Thermal Protection
 Locked Rotor Protection
 Fault Protection
Motor Overload Protection
(NEC Art 430-32)
 Thermal O/L (Device 49)
 Motors with SF not less than 1.15
 125% of FLA
 Motors with temp. rise not over 40
 125% of FLA
 All other motors
 115% of FLA
Locked Rotor Protection
 Thermal Locked Rotor (Device 51)
 Starting Time (TS < TLR)
 LRA
 LRA sym
 LRA asym (1.5-1.6 x LRA sym) + 10% margin
Fault Protection
(NEC Art 430-52)
 Non-Time Delay Fuses
 300% of FLA
 Dual Element (Time-Delay Fuses)
 175% of FLA
 Instantaneous Trip Breaker
 800% of FLA*
 Inverse Time Breakers
 250% of FLA
*MCPs can be set higher
200 HP
MCP
O/L
Starting Curve
I
2
T
(49)
MCP (50)
(51)
ts
tLR
LRAs LRAasym
Overcurrent Relay
 Time-Delay (51  I>)
 Short-Time Instantaneous ( I>>)
 Instantaneous (50  I>>>)
 Electromagnetic (induction Disc)
 Solid State (Multi Function / Multi Level)
 Application
5010566.ppt
Time-Overcurrent Unit
 Ampere Tap Calculation
 Ampere Pickup (P.U.) = CT Ratio x A.T. Setting
 Relay Current (IR) = Actual Line Current (IL) / CT
Ratio
 Multiples of A.T. = IR/A.T. Setting
= IL/(CT Ratio x A.T. Setting)
IL
IR
CT
51
Instantaneous Unit
 Instantaneous Calculation
 Ampere Pickup (P.U.) = CT Ratio x IT Setting
 Relay Current (IR) = Actual Line Current (IL) / CT
Ratio
 Multiples of IT= IR/IT Setting
= IL/(CT Ratio x IT Setting)
IL
IR
CT
50
41
Relay Coordination
 Time margins should be maintained between T/C
curves
 Adjustment should be made for CB opening time
 Shorter time intervals may be used for solid state
relays
 Upstream relay should have the same inverse T/C
characteristic as the downstream relay (CO-8 to CO-8)
or be less inverse (CO-8 upstream to CO-6
downstream)
 Extremely inverse relays coordinates very well with
CLFs
Fixed Points
 Motor starting curves
 Transformer damage curves & inrush
points
 Cable damage curves
 SC maximum fault points
 Cable ampacities
Points or curves which do not change
regardless of protective device settings:
Situation
Calculate Relay Setting (Tap, Inst. Tap & Time Dial)
For This System
4.16 kV
DS 5 MVA
Cable
1-3/C 500 kcmil
CU - EPR
CB
Isc = 30,000 A
6 %
50/51 Relay: IFC 53
CT 800:5
Solution
A
Inrsuh 328
,
8
694
12
I 


A
338
.
4
800
5
I
I L
R 


Transformer: A
kV
kVA
L 694
16
.
4
3
000
,
5
I 


IL
CT
R
IR
Set Relay:
A
55
1
.
52
800
5
328
,
8
)
50
(
1
)
38
.
1
(6/4.338
0
.
6
4
.
5
338
.
4
%
125
緒








A
Inst
TD
A
TAP
A
Question
What is ANSI Shift Curve?
Answer
 For delta-delta connected transformers, with
line-to-line faults on the secondary side, the
curve must be reduced to 87% (shift to the left
by a factor of 0.87)
 For delta-wye connection, with single line-to-
ground faults on the secondary side, the curve
values must be reduced to 58% (shift to the left
by a factor of 0.58)
Question
What is meant by Frequent and
Infrequent for transformers?
Answer
Infrequent Fault Incidence Zones for Category II & III Transformers
Source
Transformer primary-side protective device
(fuses, relayed circuit breakers, etc.) May be
selected by reference to the infrequent-fault-
incidence protection curve
Category II or III Transformer
Fault will be cleared by transformer
primary-side protective device
Optional main secondary side protective device.
May be selected by reference to the infrequent-fault-
incidence protection curve
Feeder protective device
Fault will be cleared by transformer primary-side
protective device or by optional main secondary-
side protection device
Fault will be cleared by
feeder protective device
Infrequent-Fault
Incidence Zone*
Feeders
Frequent-Fault
Incidence Zone*
Question
What T/C Coordination interval should be
maintained between relays?
Answer
A
t
I
B
CB Opening Time
+
Induction Disc Overtravel (0.1 sec)
+
Safety margin (0.2 sec w/o Inst. & 0.1 sec w/ Inst.)
Question
What is Class 10 and Class 20
Thermal OLR curves?
Answer
 Class 10 for fast trip, 10 seconds or less
 Class 20 for, 20 seconds or less
 There is also a Class 30 for long trip time
Answer

More Related Content

5010566.ppt

  • 1. Power System Protection Dr. Ibrahim El-Amin
  • 3. Definition Overcurrent Coordination A systematic study of current responsive devices in an electrical power system.
  • 4. Objective To determine the ratings and settings of fuses, breakers, relay, etc. To isolate the fault or overloads.
  • 5. Criteria Economics Available Measures of Fault Operating Practices Previous Experience
  • 6. Design Open only PD upstream of the fault or overload Provide satisfactory protection for overloads Interrupt SC as rapidly (instantaneously) as possible Comply with all applicable standards and codes Plot the Time Current Characteristics of different PDs
  • 7. Analysis When: New electrical systems Plant electrical system expansion/retrofits Coordination failure in an existing plant
  • 8. Protection vs. Coordination Coordination is not an exact science Compromise between protection and coordination Reliability Speed Performance Economics Simplicity
  • 9. Protection Prevent injury to personnel Minimize damage to components Quickly isolate the affected portion of the system Minimize the magnitude of available short-circuit
  • 10. Spectrum Of Currents Load Current Up to 100% of full-load 115-125% (mild overload) Overcurrent Abnormal loading condition (Locked-Rotor) Fault Current Fault condition Ten times the full-load current and higher
  • 11. Coordination Limit the extend and duration of service interruption Selective fault isolation Provide alternate circuits
  • 13. Equipment Motor Transformer Generator Cable Busway
  • 14. Capability / Damage Curves t I I2 2 t Gen I2 t Motor Xfmr I2 t Cable I2 t
  • 15. Transformer Category ANSI/IEEE C-57.109 Minimum nameplate (kVA) Category Single-phase Three-phase I 5-500 15-500 II 501-1667 501-5000 III 1668-10,000 5001-30,000 IV above 1000 above 30,000
  • 16. Infrequent Fault Incidence Zones for Category II & III Transformers * Should be selected by reference to the frequent-fault-incidence protection curve or for transformers serving industrial, commercial and institutional power systems with secondary-side conductors enclosed in conduit, bus duct, etc., the feeder protective device may be selected by reference to the infrequent-fault-incidence protection curve. Source: IEEE C57 Source Transformer primary-side protective device (fuses, relayed circuit breakers, etc.) may be selected by reference to the infrequent-fault- incidence protection curve Category II or III Transformer Fault will be cleared by transformer primary-side protective device Optional main secondary side protective device. May be selected by reference to the infrequent-fault- incidence protection curve Feeder protective device Fault will be cleared by transformer primary-side protective device or by optional main secondary- side protection device Fault will be cleared by feeder protective device Infrequent-Fault Incidence Zone* Feeders Frequent-Fault Incidence Zone*
  • 17. Transformer t (sec) I (pu) Thermal 200 2.5 I 2 t = 1250 2 25 Isc Mechanical K=(1/Z) 2 t (D-D LL) 0.87 (D-R LG) 0.58 Frequent Fault Infrequent Fault Inrush FLA
  • 19. Transformer Protection MAXIMUM RATING OR SETTING FOR OVERCURRENT DEVICE PRIMARY SECONDARY Over 600 Volts Over 600 Volts 600 Volts or Below Transformer Rated Impedance Circuit Breaker Setting Fuse Rating Circuit Breaker Setting Fuse Rating Circuit Breaker Setting or Fuse Rating Not more than 6% 600 % 300 % 300 % 250% 125% (250% supervised) More than 6% and not more than 10% 400 % 300 % 250% 225% 125% (250% supervised) Table 450-3(a) source: NEC
  • 20. Protective Devices Fuse Relay (50/51 P, N, G, SG, 51V, 67, 46, 79, 21, ) Thermal Magnetic Low Voltage Solid State Trip Electro-Mechanical MCP Overload Heater
  • 21. Fuse Non Adjustable Device Continuous and Interrupting Rating Voltage Levels Characteristic Curves Min. Melting Total Clearing Application
  • 22. Minimum Melting Time Curve Total Clearing Time Curve
  • 23. Current Limiting Fuse (CLF) Limits the peak current of short-circuit Reduces magnetic stresses (mechanical damage) Reduces thermal energy
  • 25. Symmetrical RMS Amperes Peak Let-Through Amperes 100 A 60 A 15% PF (X/R = 6.6) 12,500 5,200 230,000 300 A 100,000 Let-Through Chart
  • 26. Fuse Generally: CLF is a better short-circuit protection Non-CLF (expulsion fuse) is a better Overload protection
  • 27. Selectivity Criteria Typically: Non-CLF: 140% of full load CLF: 150% of full load
  • 28. Molder Case CB Thermal-Magnetic Magnetic Only Integrally Fused Current Limiting High Interrupting Capacity Types Frame Size Trip Rating Interrupting Capability Voltage
  • 30. LVPCB Voltage and Frequency Ratings Continuous Current / Frame Size Override (12 times cont. current) Interrupting Rating Short-Time Rating (30 cycle) Fairly Simple to Coordinate
  • 31. 480 kV CB 2 CB 1 CB 2 CB 1 IT ST PU ST Band LT PU LT Band If =30 kA
  • 32. Motor Protection Motor Starting Curve Thermal Protection Locked Rotor Protection Fault Protection
  • 33. Motor Overload Protection (NEC Art 430-32) Thermal O/L (Device 49) Motors with SF not less than 1.15 125% of FLA Motors with temp. rise not over 40 125% of FLA All other motors 115% of FLA
  • 34. Locked Rotor Protection Thermal Locked Rotor (Device 51) Starting Time (TS < TLR) LRA LRA sym LRA asym (1.5-1.6 x LRA sym) + 10% margin
  • 35. Fault Protection (NEC Art 430-52) Non-Time Delay Fuses 300% of FLA Dual Element (Time-Delay Fuses) 175% of FLA Instantaneous Trip Breaker 800% of FLA* Inverse Time Breakers 250% of FLA *MCPs can be set higher
  • 36. 200 HP MCP O/L Starting Curve I 2 T (49) MCP (50) (51) ts tLR LRAs LRAasym
  • 37. Overcurrent Relay Time-Delay (51 I>) Short-Time Instantaneous ( I>>) Instantaneous (50 I>>>) Electromagnetic (induction Disc) Solid State (Multi Function / Multi Level) Application
  • 39. Time-Overcurrent Unit Ampere Tap Calculation Ampere Pickup (P.U.) = CT Ratio x A.T. Setting Relay Current (IR) = Actual Line Current (IL) / CT Ratio Multiples of A.T. = IR/A.T. Setting = IL/(CT Ratio x A.T. Setting) IL IR CT 51
  • 40. Instantaneous Unit Instantaneous Calculation Ampere Pickup (P.U.) = CT Ratio x IT Setting Relay Current (IR) = Actual Line Current (IL) / CT Ratio Multiples of IT= IR/IT Setting = IL/(CT Ratio x IT Setting) IL IR CT 50
  • 41. 41 Relay Coordination Time margins should be maintained between T/C curves Adjustment should be made for CB opening time Shorter time intervals may be used for solid state relays Upstream relay should have the same inverse T/C characteristic as the downstream relay (CO-8 to CO-8) or be less inverse (CO-8 upstream to CO-6 downstream) Extremely inverse relays coordinates very well with CLFs
  • 42. Fixed Points Motor starting curves Transformer damage curves & inrush points Cable damage curves SC maximum fault points Cable ampacities Points or curves which do not change regardless of protective device settings:
  • 43. Situation Calculate Relay Setting (Tap, Inst. Tap & Time Dial) For This System 4.16 kV DS 5 MVA Cable 1-3/C 500 kcmil CU - EPR CB Isc = 30,000 A 6 % 50/51 Relay: IFC 53 CT 800:5
  • 44. Solution A Inrsuh 328 , 8 694 12 I A 338 . 4 800 5 I I L R Transformer: A kV kVA L 694 16 . 4 3 000 , 5 I IL CT R IR Set Relay: A 55 1 . 52 800 5 328 , 8 ) 50 ( 1 ) 38 . 1 (6/4.338 0 . 6 4 . 5 338 . 4 % 125 緒 A Inst TD A TAP A
  • 45. Question What is ANSI Shift Curve?
  • 46. Answer For delta-delta connected transformers, with line-to-line faults on the secondary side, the curve must be reduced to 87% (shift to the left by a factor of 0.87) For delta-wye connection, with single line-to- ground faults on the secondary side, the curve values must be reduced to 58% (shift to the left by a factor of 0.58)
  • 47. Question What is meant by Frequent and Infrequent for transformers?
  • 48. Answer Infrequent Fault Incidence Zones for Category II & III Transformers Source Transformer primary-side protective device (fuses, relayed circuit breakers, etc.) May be selected by reference to the infrequent-fault- incidence protection curve Category II or III Transformer Fault will be cleared by transformer primary-side protective device Optional main secondary side protective device. May be selected by reference to the infrequent-fault- incidence protection curve Feeder protective device Fault will be cleared by transformer primary-side protective device or by optional main secondary- side protection device Fault will be cleared by feeder protective device Infrequent-Fault Incidence Zone* Feeders Frequent-Fault Incidence Zone*
  • 49. Question What T/C Coordination interval should be maintained between relays?
  • 50. Answer A t I B CB Opening Time + Induction Disc Overtravel (0.1 sec) + Safety margin (0.2 sec w/o Inst. & 0.1 sec w/ Inst.)
  • 51. Question What is Class 10 and Class 20 Thermal OLR curves?
  • 52. Answer Class 10 for fast trip, 10 seconds or less Class 20 for, 20 seconds or less There is also a Class 30 for long trip time