PRESENTED BY
BHAGYASHREE CHINDALE(7170)
GET
ELECTRICAL SCHEMATICS AT NCP
POWER FLOW FOR THE
PROJECT
RECEIVING
SUBSTATION
(2 NOS)
33kV HT SUPPLY FROM- BEST CONVERSION
FROM 33kV
TO 11kV
DISTRIBUTION
SUBSTATION
(8 NOS)
CONVERSION
FROM 11kV
TO 415V
LT PANEL
ENERGY METER FOR
MEASUREMENT OF
POWER CONSUMPTION
BUS BAR
SYSTEM
FLAT DB
COMMON
AREA PANEL
LT PANEL
METERING PANEL
TYPICAL FOR
RESIDENTIAL
TOWER
FOR
COMMERCIAL
AND
CLUBHOUSE
BLOCK DIAGRAM OF POWER FLOW IN PROJECT
RSS 1
LOC-T6 GR
FLOOR
DSS 4
11/0.415kV
DSS 3
11/0.415kV
DSS 2
11/0.415kV
DSS 1
11/0.415kV
TRANSFORMER YARD
LOC-RG AREA
2*20MVA TRANSFORMERS
33/11KV RATING
LOC-TOWER2 GR FLOOR
Tx-7*1600kVA
(T1-3*1600kVA
+T2-3*1600kVA
+SPARE-1*1600kVA)
LOC-TOWER4 GR FLOOR
Tx-8*1600kVA
(T4-3*1600kVA
+T3-3*1600kVA
+BASEMENT AND
INFRA-2*1600kVA)
LOC-TOWER6 GR FLOOR
Tx-8*1600kVA
(T5-3*1600kVA
+T6-3*1600kVA
+BASEMENT AND
INFRA-2*1600kVA)
LOC-TOWER8 GR FLOOR
Tx-10*1600kVA
(T7-3*1600kVA
+T8-3*1600kVA
+T9-3*1600kVA
+T10-1*1600kVA)
DISTRIBUTION FROM RSS1
RSS 2
LOC-T10 GR
FLOOR
DSS 8
11/0.415kV
DSS 7
11/0.415kV
DSS 6
11/0.415kV
DSS 5
11/0.415kV
TRANSFORMER YARD
LOC-RG AREA
2*20MVA TRANSFORMERS
33/11KV RATING
LOC-TOWER10 GR FLOOR
Tx-2*1600kVA
(T10-2*1600kVA)
LOC-COMMERCIAL
TOWER
Tx-4*2500kVA
LOC-CLUB HOUSE(NORTH)
Tx-4*1600kVA
(T11-3*1600kVA
+BASEMENT/INFRA/CH-
1*1600kVA)
LOC-CLUB HOUSE(SOUTH)
Tx-5*1600kVA
(T12-3*1600kVA
+BASEMENT/INFRA/CH-
1*1600kVA
+SPARE-1*1600kVA)
DISTRIBUTION FROM RSS2
POWER FLOW IN
BUILDING
TOWER 4
TRANSFORMER
1
TRANSFORMER
2
TRANSFORMER 7
TRANSROMER
5
1600 KVA
11/415 V
DRY TYPE TX 1600 KVA
11/415 V
DRY TYPE TX
1600 KVA
11/415 V
DRY TYPE TX
1600 KVA
11/415 V
DRY TYPE TX
2500A BUS RISER 1
FROM 2ND-17TH FLR
C.L-2748.63KW
D.L-879.56KW
FEEDER
PILLAR 1
2000A BUS RISER 2
FRM 18TH -31ST FLR
C.L-2421.70KW
D.L-774.9KW
COMMON AREA
METERING PANEL
T3
SPARE
FEEDER
PILLAR 4
1600A BUS RISER 3
FRM 32ND -46TH FLR
C.L-2354.4KW
D.L-753.41KW
BASEMENT AND RG
LOADS
SPARE
FEEDER
PILLAR 2
1600A BUS RISER 4
FRM 47TH -53RD
FLR
C.L-1598.90KW
D.L-511.65KW
METERING PANEL
(T3 &T4 DUPLEXES)
SPARE
POWER FLOW FROM T4
TOWER 3
TRANSFORMER
8
TRANSFORMER
6
TRANSFORMER 4
TRANSROMER
3
1600 KVA
11/415 V
DRY TYPE TX 1600 KVA
11/415 V
DRY TYPE TX
1600 KVA
11/415 V
DRY TYPE TX
1600 KVA
11/415 V
DRY TYPE TX
SPARE
2500A BUS RISER 2
FRM 14TH -27TH FLR
C.L-2670.33KW
D.L-854.51KW
2500A BUS RISER 3
FRM 28TH -40TH FLR
C.L-2674.45KW
D.L-855.82KW
FEEDER
PILLAR 3
COMMON AREA
METERING PANEL T4
2500A BUS RISER 4
FRM 41ST -53RD FLR
C.L-2648.33KW
D.L-847.47KW
2500A BUS RISER 1
FRM 2ND -13TH FLR
C.L-2736.26KW
D.L-875.6KW
POWER FLOW FROM T3
BUS BAR SYSTEM
Power from utility meter is brought to each floor by means
of bus duct or bus risers.
•Advantages of bus bar system over normal cabling system
are as follows:
 Saving in space and cost.
Increased flexibility in design
Greater safety
Easy estimation of cost
Ease for accessing power
No overheating and fire protection
Highly efficient and reliable
Easier maintenance
SCHEMATIC FOR T4
POWER FLOW FOR METERING PANEL
SLD FOR L+PDB (10WAY TPN FOR 2.5BHK UNIT) CL-25.59KW
DG PANEL
BOOSTER
PUMP PANEL
@ 55th FLR
1000A
ACB
EDO
1000A
ACB
EDO
630 KVA 630 KVA
4C*300 SQ.MM
BUS
COUPLER
800A
ACB
EDO
800A
ACB
EDO
800A
ACB
EDO
800A
ACB
EDO
MDB
COMMON
AREA
T4
1ST FLR
800A
ATS
NORMAL SUPPLY
FROM
BEST
FIRE PANEL
T4
32ND FLR
800A
ATS
FIRE PANEL
T3
32ND FLR
MDB
COMMON
AREA
T3
1ST FLR
DG PANEL
C.L-721.73KW
D.L-243.34KW
DG 1 DG 2
DG SET POWER DISTRIBUTION SCHEME
C.L-808.67KW
D.L-295.03KW
C.L-457.55KW
D.L-344.3KW
FIRE PANEL
HYDRANT PUMP
SPRINKLER PUMP
JOCKY PUMP
STANDBY PUMP
EXHAUST FAN
BOOSTER PUMP FOR GRND
TO 32ND FLR
NORMAL SUPPLY
FROM
BEST
COMMON
AREA
METER T4
FROM BEST
800A
ACB
EDO
800A
ACB
EDO
E/M
BUS
COUPLER
200A
MCCB
CT
200/5A
WATERBODIES
LIGHTING PANEL
250A
MCCB
CT
250/5A
NORMAL ELEVATOR
PANEL
FOR LIFTS 4-9
@ GRND FLR
63A
MCCB
160A
MCCB
250A
MCCB
CT
63/5A
CT
160/5A
CT
250/5A
HPS
PANEL
@ 54TH FLR
FIRE EMERGENCY
ELEVATOR
PANEL
@GRND FLR
EMERGENCY LIGHTING
&VENTILATION
PANEL @ GRND FLR
FROM DG PANEL
HPS PANEL
• DOMESTIC HYDRO SYSTEM
• FLUSHING HYDRO SYSTEM
• EXHAUST FAN
EMERGENCY LIGHTING
&VENTILATION PANEL
EMERGENCY LIGHTING PANEL
VENTILATION PANELAT 1ST
&55TH FLR
• DG AREA EXHAUST FAN
• LT PANEL EXHAUST AIR FAN
• PRESSURIZATION FAN
MDB COMMON AREA
@ 1ST FLR
THANK YOU

More Related Content

ELECTRICAL SCHMATICS AT NCP_FINAL

  • 2. POWER FLOW FOR THE PROJECT
  • 3. RECEIVING SUBSTATION (2 NOS) 33kV HT SUPPLY FROM- BEST CONVERSION FROM 33kV TO 11kV DISTRIBUTION SUBSTATION (8 NOS) CONVERSION FROM 11kV TO 415V LT PANEL ENERGY METER FOR MEASUREMENT OF POWER CONSUMPTION BUS BAR SYSTEM FLAT DB COMMON AREA PANEL LT PANEL METERING PANEL TYPICAL FOR RESIDENTIAL TOWER FOR COMMERCIAL AND CLUBHOUSE
  • 4. BLOCK DIAGRAM OF POWER FLOW IN PROJECT
  • 5. RSS 1 LOC-T6 GR FLOOR DSS 4 11/0.415kV DSS 3 11/0.415kV DSS 2 11/0.415kV DSS 1 11/0.415kV TRANSFORMER YARD LOC-RG AREA 2*20MVA TRANSFORMERS 33/11KV RATING LOC-TOWER2 GR FLOOR Tx-7*1600kVA (T1-3*1600kVA +T2-3*1600kVA +SPARE-1*1600kVA) LOC-TOWER4 GR FLOOR Tx-8*1600kVA (T4-3*1600kVA +T3-3*1600kVA +BASEMENT AND INFRA-2*1600kVA) LOC-TOWER6 GR FLOOR Tx-8*1600kVA (T5-3*1600kVA +T6-3*1600kVA +BASEMENT AND INFRA-2*1600kVA) LOC-TOWER8 GR FLOOR Tx-10*1600kVA (T7-3*1600kVA +T8-3*1600kVA +T9-3*1600kVA +T10-1*1600kVA) DISTRIBUTION FROM RSS1
  • 6. RSS 2 LOC-T10 GR FLOOR DSS 8 11/0.415kV DSS 7 11/0.415kV DSS 6 11/0.415kV DSS 5 11/0.415kV TRANSFORMER YARD LOC-RG AREA 2*20MVA TRANSFORMERS 33/11KV RATING LOC-TOWER10 GR FLOOR Tx-2*1600kVA (T10-2*1600kVA) LOC-COMMERCIAL TOWER Tx-4*2500kVA LOC-CLUB HOUSE(NORTH) Tx-4*1600kVA (T11-3*1600kVA +BASEMENT/INFRA/CH- 1*1600kVA) LOC-CLUB HOUSE(SOUTH) Tx-5*1600kVA (T12-3*1600kVA +BASEMENT/INFRA/CH- 1*1600kVA +SPARE-1*1600kVA) DISTRIBUTION FROM RSS2
  • 8. TOWER 4 TRANSFORMER 1 TRANSFORMER 2 TRANSFORMER 7 TRANSROMER 5 1600 KVA 11/415 V DRY TYPE TX 1600 KVA 11/415 V DRY TYPE TX 1600 KVA 11/415 V DRY TYPE TX 1600 KVA 11/415 V DRY TYPE TX 2500A BUS RISER 1 FROM 2ND-17TH FLR C.L-2748.63KW D.L-879.56KW FEEDER PILLAR 1 2000A BUS RISER 2 FRM 18TH -31ST FLR C.L-2421.70KW D.L-774.9KW COMMON AREA METERING PANEL T3 SPARE FEEDER PILLAR 4 1600A BUS RISER 3 FRM 32ND -46TH FLR C.L-2354.4KW D.L-753.41KW BASEMENT AND RG LOADS SPARE FEEDER PILLAR 2 1600A BUS RISER 4 FRM 47TH -53RD FLR C.L-1598.90KW D.L-511.65KW METERING PANEL (T3 &T4 DUPLEXES) SPARE POWER FLOW FROM T4
  • 9. TOWER 3 TRANSFORMER 8 TRANSFORMER 6 TRANSFORMER 4 TRANSROMER 3 1600 KVA 11/415 V DRY TYPE TX 1600 KVA 11/415 V DRY TYPE TX 1600 KVA 11/415 V DRY TYPE TX 1600 KVA 11/415 V DRY TYPE TX SPARE 2500A BUS RISER 2 FRM 14TH -27TH FLR C.L-2670.33KW D.L-854.51KW 2500A BUS RISER 3 FRM 28TH -40TH FLR C.L-2674.45KW D.L-855.82KW FEEDER PILLAR 3 COMMON AREA METERING PANEL T4 2500A BUS RISER 4 FRM 41ST -53RD FLR C.L-2648.33KW D.L-847.47KW 2500A BUS RISER 1 FRM 2ND -13TH FLR C.L-2736.26KW D.L-875.6KW POWER FLOW FROM T3
  • 10. BUS BAR SYSTEM Power from utility meter is brought to each floor by means of bus duct or bus risers. •Advantages of bus bar system over normal cabling system are as follows:  Saving in space and cost. Increased flexibility in design Greater safety Easy estimation of cost Ease for accessing power No overheating and fire protection Highly efficient and reliable Easier maintenance
  • 12. POWER FLOW FOR METERING PANEL
  • 13. SLD FOR L+PDB (10WAY TPN FOR 2.5BHK UNIT) CL-25.59KW
  • 15. BOOSTER PUMP PANEL @ 55th FLR 1000A ACB EDO 1000A ACB EDO 630 KVA 630 KVA 4C*300 SQ.MM BUS COUPLER 800A ACB EDO 800A ACB EDO 800A ACB EDO 800A ACB EDO MDB COMMON AREA T4 1ST FLR 800A ATS NORMAL SUPPLY FROM BEST FIRE PANEL T4 32ND FLR 800A ATS FIRE PANEL T3 32ND FLR MDB COMMON AREA T3 1ST FLR DG PANEL C.L-721.73KW D.L-243.34KW DG 1 DG 2 DG SET POWER DISTRIBUTION SCHEME C.L-808.67KW D.L-295.03KW C.L-457.55KW D.L-344.3KW FIRE PANEL HYDRANT PUMP SPRINKLER PUMP JOCKY PUMP STANDBY PUMP EXHAUST FAN BOOSTER PUMP FOR GRND TO 32ND FLR NORMAL SUPPLY FROM BEST
  • 16. COMMON AREA METER T4 FROM BEST 800A ACB EDO 800A ACB EDO E/M BUS COUPLER 200A MCCB CT 200/5A WATERBODIES LIGHTING PANEL 250A MCCB CT 250/5A NORMAL ELEVATOR PANEL FOR LIFTS 4-9 @ GRND FLR 63A MCCB 160A MCCB 250A MCCB CT 63/5A CT 160/5A CT 250/5A HPS PANEL @ 54TH FLR FIRE EMERGENCY ELEVATOR PANEL @GRND FLR EMERGENCY LIGHTING &VENTILATION PANEL @ GRND FLR FROM DG PANEL HPS PANEL • DOMESTIC HYDRO SYSTEM • FLUSHING HYDRO SYSTEM • EXHAUST FAN EMERGENCY LIGHTING &VENTILATION PANEL EMERGENCY LIGHTING PANEL VENTILATION PANELAT 1ST &55TH FLR • DG AREA EXHAUST FAN • LT PANEL EXHAUST AIR FAN • PRESSURIZATION FAN MDB COMMON AREA @ 1ST FLR