Aşırı Gerilim ve Yıldırımdan Koruma Semineri
YILDIRIMDAN KORUNMA
MERKEZÄ°
Serdar AKSOY
ELEKTRÄ°K MÃœHENDÄ°SÄ°/MBA
serdar.aksoy@yilkomer.com
Yıldırımdan ve Aşırı Darbe Gerilimlerinden
Korunma Sistemleri
Lightning protection system (LPS)
1. Interception systems
2. Earthing systems
3. Equipotential
bonding systems
4. Surge protection
systems
3
AŞIRI GERİLİM VE YILDIRIMDAN KORUNMA YÖNTEMLERİ-4’LÜ
KORUMA
1-İÇ YILDIRIMLIK SİSTEMİ
• Parafudr
2-DIÅž YILDIRIMLIK SÄ°STEMÄ°
 Kafes Sistemi-FARADAY
 Ağ oluşturma Yön.-MESH METOD
 Franklin Çubuğu
 Gergi Teli Metodu
3-TOPRAKLAMA SÄ°STEMÄ°
4-EÅž POTANSÄ°YEL SÄ°STEM
Loop spacing M
Rolling sphereProtection angle
Earthing system
Conductor
R
h1
h2 α1
α2
Interceptor rod
Source: DIN VDE 0185-305-3 5.2
Yakalama uçları temelli yıldırımdan korunma sistemleri
The protective angle method
is for suitable for buildings of a
simple shape, but is limited to
the heights specified in Table 2.
The loop method is suitable for
protecting flat surfaces.
The rolling sphere
method is suitable for all
cases.
Planning Process
5
DÄ°REK YILDIRIM DARBESÄ°
Effects: Fire hazard
Caused by: specific energy, charge
If a lightning strikes a building, electrical energy
is converted into heat. This may cause fires,
especially in combustible roof structures! .
∫
∞
=
0
2
dti
R
W
∫
∞
=
0
idtQ
İÇ YILDIRIMLIK SİSTEMLERİNİN OLMAMASI DURUMUNDA
AÅžIRI GERÄ°LÄ°MÄ°N OLUÅžMA NEDENLERÄ°
1-Şalt hareketleri sonucu (anahtarlama elemanları
sonucu)ortaya çıkan Aşırı Gerilimler.
2-Åžebekeden kaynaklanan harmonik ve darbeler
sonucu oluşan Aşırı Gerilimler.
3-Yıldırım Deşarjı sonucu oluşan Aşırı Gerilimler
4-Elektrostatik deşarj sonucu oluşan Aşırı Gerilimler
Geçici Gerilimler (Transient Voltage)
Geçici Gerilim Dalgalanmaları Nedir?
Geçici Gerilim Dalgalanmaları mikro saniyeler mertebesinde kısa süreli olarak oluşan, ancak nominal
gerilimin birkaç katına ulaşabilen gerilimlerdir !
30
26
22
18
10
6
2
14
K/
Aşırı
Gerilim
Faktörü
1500
(I)
2500
(II)
4000
(III)
6000
(IV)
Ûr
v
Yıldırım Darbeleri
Anahtarlama Darbeleri
Geçici Gerilim Dalgalanmaları
Harmonikler
Yavaş ve hızlı
Gerilim deÄŸiÅŸiklikleri
Gerilim düşmeleri
Kısa kesilmeler
Yıldırım Deşarjı Nasıl Oluşur ?
-40
-20
0
0 200 400 600 800 t (µs)100 300 500 700 900
Deşarjın başladığı an ve
birkac ms sonraki periyot
Yıldırım deşarjının enerji etkisi laboratuvarlarda 10/350 µs test darbesi ile simüle edilmektedir.
Ana DeÅŸarj
Ä°kinci deÅŸarj
Ölçülmüş yıldırım darbesi
Simüle edilmiş yıldırım darbesi, 10/350 µs
Iimp
1100
I (kA)
Simüle Edilmiş Yıldırım ve Gerilim Darbesi
Arasındaki Fark…
-10
0
10
20
30
40
50
60
0 100 200 300 400 500 600 700 800 900 1000
Zaman [µs]
Akım[kA]
Simüle edilmiş yıldırım darbesi, 10/350 µs
Simüle edilmiş gerilim dalgası, 8/20 µs
AÅžIRI GERÄ°LÄ°ME NEDEN OLAN OLAYLAR
İÇERİSİNDE EN TEHLİKELİ OLANI
YILDIRIM
KAYNAKLI DARBELERÄ°DÄ°R.
YILDIRIM DARBE DEÄžERLERÄ° VE SIKLIKLARI
50 % 10 % 5 % ≈ 1 %
30 80 100 200kA
20 90 100 100kA/µs
10 80 100 400C
105 106
5.106 107A2s
Sıklık %
Yıldırım Akımının
Tepe DeÄŸeri
Yıldırım Akımının
Azami Artış hızı
Yıldırımın Yükü
Yıldırım Akımı
Kare Darbe deÄŸeri
YILDIRIM…
 100 Milyon km hız
 1 milyar volt
 28000 celcius sıcaklık
 Her gün 8 milyon kez düşüyor
 Yarım saniyeden çok daha hızlı bir darbe
 Statik bir elektrik
 Adımları saniyenin/50 hizinda
TÃœRKÄ°YE YILDIRIM HARÄ°TASI
Gerilim Darbelerinin Nedenleri ve Etkileri
Harici Yıldırım Tesisatı Olmayan Bir Binaya
Yıldırım Düşmesi (Direct Strike)
Etkiler (direct strike)
Harici Yıldırım Tesisatı Olmayan Bir Binaya
Yıldırım Düşmesi (Direct Strike)
Bir binaya düşen yıldırım, elektrik enerjisini ısıya
dönüştürür.
Bu özellikle kolay yanabilen çatılar için yangın riskini
çok daha fazla arttırmaktadır.
Yıldırım, metal parçaların ergimesine de sebep
olabilmektedir. Ayrıca mekanik hasarlara da sebep
olabilmektedir
Yüksek Gerilim Hattına Yıldırım Düşmesi
(Direct Strike)
Alçak Gerilim Hattına Yıldırım Düşmesi
(Direct Strike)
Alçak Gerilim Hattına Yıldırım Düşmesi
(Direct Strike)
Alçak Gerilim Hattına Yıldırım Düşmesi
(Direct Strike)
A.G. hattına düşen yıldırımla Y.G. hattına düşen
yıldırım arasındaki fark, kısmi yıldırım akımlarının
iletildiği binaya olan uzaklığıyla ilgilidir.
Etkileri: A.G. Şebekesinde kısmi yıldırım akımları ve
gerilim dalgalanmaları
Nedeni:Yıldırım darbe akımının genişliği
Yıldırımdan Korunma Tesisatına Yıldırım
Düşmesi (Direct Strike)
Yıldırımdan Korunma Tesisatına Yıldırım
Düşmesi (Direct Strike)
Yıldırımdan Korunma Tesisatına Yıldırım
Düşmesi (Direct Strike) ve Eş potansiyel
Topraklama Sisteminin Var Olmaması
Durumu
Yıldırım düşmesi sonucu oluşan yıldırım akımı,
toprağa yönlendiğinde, tesisatın topraklama
noktasında gerilim yükselmesine neden olur.
Bu, ev içindeki eş potansiyel topraklama
sisteminden geçer.
Yıldırımdan korunma için uygun bir eş
potansiyel topraklama elektrik tesisatının zarar
görmesini engeller.
Etkileri: Gerilim Darbeleri
(Aşırı Gerilim) yalıtım bozulması
Nedeni: Maksimum darbe akımı
L1
L2
L3
PEN
Yıldırımdan Korunma Tesisatına Yıldırım
Düşmesi (Direct Strike)
Yıldırımdan Korunma Tesisatına Yıldırım
Düşmesi (Direct Strike) ve Eş potansiyel
Topraklama Sisteminin Var Olmaması
Durumu
Etkileri: Gerilim Darbeleri
(aşırı gerilim) yalıtım bozulması
Nedeni: Maksimum darbe akımı
Yıldırım düşmesi sonucu oluşan yıldırım akımı,
toprağa yönlendiğinde, tesisatın topraklama
noktasında gerilim yükselmesine neden olur.
Bu, ev içindeki eş potansiyel topraklama
sisteminden geçer.
Yıldırımdan korunma için uygun bir eş
potansiyel topraklama elektrik tesisatının zarar
görmesini engeller.
Yıldırımdan Korunma Tesisatına Yıldırım
Düşmesi (Direct Strike)
Yıldırımdan Korunma Tesisatına Yıldırım
Düşmesi (Direct Strike) ve Eş potansiyel
Topraklama Sisteminin Var Olmaması
Durumu
Etkileri: Gerilim Darbeleri
(aşırı gerilim) yalıtım bozulması
Nedeni: Maksimum darbe akımı
Yıldırım düşmesi sonucu oluşan yıldırım akımı,
toprağa yönlendiğinde, tesisatın topraklama
noktasında gerilim yükselmesine neden olur.
Bu, ev içindeki eş potansiyel topraklama
sisteminden geçer.
Yıldırımdan korunma için uygun bir eş
potansiyel topraklama elektrik tesisatının zarar
görmesini engeller.
Yıldırım düşen noktanın yakınında
Gerilim Darbelerinin Coupling Etkisi (Yıldırım
Düşen Noktanın Yakınında)
Etkileri:
Yıldırım akımları, iletkenler (yer altındaki
borular, kablolar vs ) arasından geçtiği
zaman yüksek indüklenmiş gerilim
üreten manyetik bir değişim yaratmaktadır.
Bu durum yine, bina içindeki yangın riskini
arttırmaktadır.
Endüktif coupling yıldırım akımının
manyetik etkisi ile oluÅŸur.
Gerilim Darbelerinin Coupling Etkisi
(Yıldırım Düşen Noktanın Uzağında)
.
max






dt
di
2 km2 km
Gerilim Darbelerinin Coupling Etkisi
(Yıldırım düşen noktanın uzağında)
Far lightning strike
ENDÃœKTÄ°F KUPLAJ
Pik deÄŸeri=
max






dt
di
Parallel guided
cables
Conductor loop
Lightning current
arrestor
Gerilim Darbelerinin Coupling Etkisi
(Yıldırım düşen noktanın uzağında)
Yıldırımın Kuplaj Etkisi Sonucu Zararları
Yıldırımın Kuplaj Etkisi Sonucu Zararları
Source: http://www.photovoltaik.eu
Anahtarlama
Etkileri
Anahtarlama (Switching)
Anahtarlama özellikle yükün endüktif yük olması
durumundda tehlikeli olabilmektedir. Örneğin;
• Motorlar
• Transformatörler
• Şok bobinleri
• Klima kontrol sistemleri
• Kaynak makinaları
• Uzun aydınlatma iletkenleri
Etkileri: Şebeke hatlarında aşırı gerilim (darbeler)
Neden: Anahtarlama esnasındaki yüksek akım
şebekede geçici gerilim dalgalanmalarına (aşırı
gerilim) sebep olmaktadır.
Gerilim Darbelerinin Sonuçları
4. Data ve bilgi kaybı
5. İmalatın aksaması
6. Sistemin çalışmasında görülen ciddi aksaklıklar
7. Bilgi aktarımında oluşan hatalar
1. Personel yaralanmaları
3. Darbelerden kaynaklanan malzeme hasarları
2. Yangın tehlikesi
YILDIRIM DARBESÄ°NÄ°N ETKÄ°LERÄ°
Yıldırım darbesi sonucu yıkılan bir rüzgar
türbini…
Dağıtım Panoları Kılcal çatlamalar
36
SU Boruları
YILDIRIM DARBESÄ°NÄ°N ETKÄ°LERÄ°
Elektronikteki Uygulama ÖrnekleriTarihi
1950 1960 1970 1980 1990
Elektronikteki uygulama
örnekleri
Time
Interferans
bağışıklığı
Vakum
Tüpleri
Tranzistörler
Entegre Devreler
2000
PC
Sigorta ÅŸirketleri istatistikleri
Hasar Bildirimlerinin Dağılımları
Darbe Gerilimleri ve Yıldırım Düşmeleri dahil (direk ve endirek)
Fırtına
1%
DiÄŸerleri
27%
İhmalkarlık
23%
Yıldırım ve Aşırı
Darbe Gerilimleri
31%
Hırsızlık
7%
Su
6%
Yangın
5%
9000 ÅŸikayetin analizi
Amount of lightning – and
surge damages
Paid benefits for lightning-
and surge damages
Year
Amount of lightning – and surge damages and paid benefits for
lightning- and surge damages from residential building insurer
Statistic
Sigortaların ödediği tazminat miktarları
EÅŸpotansiyel Sistem
 Eşpotansiyel sistem
LPZ 0 B
LPZ 0 A
LPZ 1
LPZ 2
LPZ 3
Eş potansiyel Bağ ve Sistem İçindeki Güç ve Data
Hatları
Data Hatları
Güç Hatları
Eş potansiyel bağın amacı metal kısımlar ile hacim içindeki sistemler arasındaki potansiyel farkı yıldırımdan
korunma için en aza indirmektir.
Yıldırımdan Korunma için Eş Potansiyel
Topraklama Sistemi
PEN iletkeninin bina
topraklama sistemine
bağlanması
Aşırı gerilim darbe
koruyucusunun bina topraklama
sistemine bağlanması.
Minimum Kesit: 16 mm2
Cu
Metal komponentlerin
EÅŸ potansiyel topraklama
barasına (EBR) bağlanması
Topraklama barasının bina
topraklama sistemine bağlanması
*EBR: Eş potansiyel topraklama barası
Yıldırımdan Korunma İçin Eş potansiyel Sistem
İçindeki Güç ve Data Hatları
Yıldırımdan Korunma Bölge
Kabulü
LPZ = Lightning Protection Zone
I
LPZ 0 LPZ 1
Binaya Enerji GiriÅŸi
Ana Dağıtım Panosu
I
LPZ 1  LPZ 2
Tali Dağıtım Panosu
II
II
LPZ 2  LPZ 3
Cihaz giriÅŸi
III
III
Aşırı Gerilim Darbe Koruyucu Seçimi
B
C
D
DIN VDE 0675 Bölüm 6 (A1/A2)’ya göre Aşırı Gerilim Darbe Koruyucu Seçimi
Yıldırım Darbe Koruyucuları (Ana koruma) LPZ 0  1
Aşırı Gerilim Darbe Koruyucuları (Orta koruma) LPZ 1  2
Aşırı Gerilim Darbe Koruyucuları (Cihaz/hassas koruma) LPZ 2  3
Class I, IEC 61643-1:1998 Tip1, EN 61643-11 (07/02)
Class II, IEC 61643-1:1998 Tip 2, EN 61643-11 (07/02)
Class III, IEC 61643-1:1998 Tip 3,EN 61643-11 (07/02)
Darbe Koruyucusu Tipleri
Darbe Koruyucusu Teknolojileri
Parafudrlarda Kullanılan
Teknolojiler
Spark Gaps
(Kıvılcım Aralığı)
DeÅŸarj kapasiteleri nedeniyle
yüksek performanslı spark
gap’ler yıldırımdan korunma
elemanları olarak
kullanılmaktadırlar.
Spark gap’ler izleme akımlarını
sönümlendirmektedir.
Varistörler
Varistörler aşırı gerilim
darbe koruyucusu olarak
kullanılmaktadır. Diğer aşırı
gerilim darbe
koruyucularının tersine
yıldırım akımı taşıma
kapasiteleri sınırlıdır.
Diyotlar
Transzorb diyotlar, aynı
zamanda sönümlendirici
diyotlar olarak bilinirler.
Hızlı tepki vermeleri
karakteristik özellikleri
olmakla birlikte, deÅŸarj
kapasiteleri sınırlıdır.
YILKOMER
VG TECHNOLOGY
SPARK GAP TECHNOLOGY
A new feature in low-voltage spark gaps is the use
of carbon for the electrodes.
•Lastingly consistent properties
•High energy density in a small space
•Heat-proof Teflon discs allow extremely
narrow gaps between electrodes
Structural design
30 V
Graphite electrode
High conducted
current capacity
(fire-resistant)
Negative field voltage
means good capacity for
eliminating secondary
mains currents
Teflon discs
9 encapsulated sub
spark gaps
UG
Varistor technology
intermediate phase
Electrodes
Epoxy resin
Sintered zinc oxide grains with other
metal oxides added
Zinc oxide
microvaristor
Ι = 10 µm
Tinned copper electrode
1)
Source: Siemens brochure on "SIOV metal oxide varistor"
t/(ns)Output pulse
U
(V)
Input pulse
U
t/(ns)
(V)
Varistors are voltage-dependent resistors with highly non-linear U/I characteristics.
A number of microvaristors connected in parallel and in series produce special electrical characteristics.
The transitions between the microvaristors can "age" under the influence of electrical surges.
Diode technology
Input pulse
U
t/(ps)
(V)
Output pulse
U
t/(ps)
(V)
Voltage
(V)
Current
(A)
UC UB UR
UCUBUR
Transorb diodes (also called suppressor diodes) are diodes which limit both positive and
negative surges. Their extremely fast connecting response of just a few ps means they are
especially suited to use in fine and data line protection equipment.
Chapter 3.2. Conductor technologies and types
Yıldırım ve Aşırı Gerilim Darbe Koruyucuları Seçimi
Tesisat Rehberi / TN-C Åžebekeler (4 Telli)
Nötr iletkeni ve koruma iletkeni (toprak) binanın girişinde bir iletkende birleştirilmiştir (PEN).
PEN iletkeni, Nötr İletkeni (N) ve Koruma İletkeni (toprak - PE) olarak ayrılmıştır.
Uygulama Alanı: Ağırlıklı olarak nüfus yoğunluğu olan bölgeler ve yeni tesisatlar
Sayaçtan önce de
kullanılabilir
Aşırı gerilim darbe koruyucusu
RCD’den önce monte edilmelidir.
Aksi durumda, RCD darbe akımını
kaçak akım olarak algılayıp
devreyi açar.
3 x MC 50 B
V20-C/3+NPE
Åžebeke Tipleri
50%
50%
Tesisat Rehberi / TN-C Åžebekeler (4 Telli)
VDE V 0185 Part 4: 2002’den Örnek: Yıldırım Koruma Sınıfı : Tip 1
200 kA
50%’si toprağa yönelir (akar)
50%’si binaya 4 iletken üzerinden geri döner.Bu da iletken başına 25 kA demektir.
Tesisat Rehberi / TN-S Åžebekeler (5 Telli)
Ağırlıklı olarak endüstriyel tesisatlar…
3 x MC 50-B ve
1 x MC125-B/NPE
V20 C/3+NPE
200 kA
Faz başına
25 kA
Min. 100 kA
Sigorta Kullanımı
B tipi koruma ürünlerinde Ana sigorta değeri 500 A in üzerinde ise B tipi ürünün önüne maksimum 500 A sigorta bağlanır. B tipi
koruma ürünleri 25 kA e kadar kısa devre akımlarına karşıda koruma yapmaktadır. Olası uzun süreli ( saniyeler mertebesinde ) kısa
devre akımlarında ürünün önüne bağlanacak olan 500 A lik sigorta devreyi açarak kısa devre akımının ana şalter üzerine binmesine
neden olacak ve şalterin devreyi kesmesini sağlayacaktır. Kısa devre arızası kalktığında sigortalar tekrar devreye alınarak koruma
ürünleri çalışır duruma getirilmelidir. Aksi taktirde devre korumasız kalacaktır bu sebeple bağlanacak sigortaların kontak çıkışlı olarak
tercih edilmesi önemlidir.
500 A in üzerinde ise
Maksimum 500 A
Maksimum 125 A
Ä°lave Tesisat Rehberi
Minimum Bağlantı Kesitleri
.
Conductor type Conductor cross-section
mm2
Type I (class B) 16 Cu
Type II (class C) 6 Cu
Type III (class D) 1.5 Cu
Source: DIN EN 0185-305, Part 3
Ä°lave Tesisat Rehberi
• Paralel kablaj yapılmamalıdır (korunan ve korunmayan kablolar).
• Kablolar ve yıldırım darbe koruyucu, loop içinde olmamalıdır.
Yanlış Montaj
SAT receivers
DS-F
m/f
DS-F f/f
1
1
FineController FC-
SAT-D
22
2
2
Chapter 6: Surge protection for data lines, telecommunications systems and ICA systems
Switch
Star network Ethernet 100BaseT
External data line
HUB/switch
RJ45S-
E100/4-C
1
1
3
3 3
333
1
RJ45S-
E100/4-B
1
Chapter 6: Surge protection for data lines, telecommunications systems and ICA systems
Net Defender
2
2
2 2
222
2
Priz Tipi Korumalar
Priz tipi koruma
Anten koruma
Telefon koruma
Uydu Anten koruma
Üçlü Priz koruma
Adaptörlü koruma
Application LSA- Plus
Installation and devices
Basic protection (spark gaps)
• high protection level
• high current capacity
• good frequency attributes
Combi protection
• low protection level
• over current fuse
• small nominal currents
LSA-strip
Design of connecting – and separating strip l
Cable side
Incomming cable with color code
Connection contact for cable
Connection contact for switch cable
Name of double wire/pair (DA)
Hole for numbering
Protection of a high speed computer network
PC PC PC PC PC
PC
230 V 230 V 230 V 230 V 230 V
230 V
Kamera ve Anten Korumaları
BNC tip
N tip
High frequency protectors
To use for
 TV and satellite installations
 radio transmission
 video and audio signals
Types of arrester for high frequency applications
λ/4-Protector
- Is working linke a filter
- No DC possible
Not be used for current controlled
antenna systems
Protection with spark gap
- DC transmission possible
- Not very high bandwidth possible
- Many plug systems available
Overvoltage protection for sat antenna
Quelle: EN 60728-11:2005
1) Net connection
2) Equipotential bar
2a) Equipotential bar
3) Equipotential wire
4) Earth line
5) Earth connection
6) Earthing system
7) Protection wire
Protection must be planed for energy side also!
Protection of CCTV (Close Circuit Television)
• Suggestion for koax based systems
• For IP-based systems
Data ve Komünikasyon Teknolojisinde Darbe
Koruma
Geniş band koruma (kırmızı)
Bina giriÅŸindeki hatta monte edilir.
Kombine Koruma (mavi)
Bina giriÅŸindeki hatta monte edilir.
Korunacak cihazla arasındaki mesafe 10m’yi
aşmamalıdır.
Ya da hassas koruma (yeÅŸil)
Korunacak cihaza monte edilir.
Tutarlı cihaz renkleri verilen cihazlar:
Application solution for CCTV (Close Circuit
Television)
Application solution for CCTV (Close Circuit
Television)
RS 232 / RS 485 / Ehernet / Cat 5 / RJ11 / RJ45
korumalar

More Related Content

İç yıldırımlık Parafudr sistemleri

  • 1. Aşırı Gerilim ve Yıldırımdan Koruma Semineri YILDIRIMDAN KORUNMA MERKEZÄ° Serdar AKSOY ELEKTRÄ°K MÃœHENDÄ°SÄ°/MBA serdar.aksoy@yilkomer.com
  • 2. Yıldırımdan ve Aşırı Darbe Gerilimlerinden Korunma Sistemleri
  • 3. Lightning protection system (LPS) 1. Interception systems 2. Earthing systems 3. Equipotential bonding systems 4. Surge protection systems 3
  • 4. AÅžIRI GERÄ°LÄ°M VE YILDIRIMDAN KORUNMA YÖNTEMLERÄ°-4’LÃœ KORUMA 1-İÇ YILDIRIMLIK SÄ°STEMÄ° • Parafudr 2-DIÅž YILDIRIMLIK SÄ°STEMÄ°  Kafes Sistemi-FARADAY  AÄŸ oluÅŸturma Yön.-MESH METOD  Franklin ÇubuÄŸu  Gergi Teli Metodu 3-TOPRAKLAMA SÄ°STEMÄ° 4-EÅž POTANSÄ°YEL SÄ°STEM
  • 5. Loop spacing M Rolling sphereProtection angle Earthing system Conductor R h1 h2 α1 α2 Interceptor rod Source: DIN VDE 0185-305-3 5.2 Yakalama uçları temelli yıldırımdan korunma sistemleri The protective angle method is for suitable for buildings of a simple shape, but is limited to the heights specified in Table 2. The loop method is suitable for protecting flat surfaces. The rolling sphere method is suitable for all cases. Planning Process 5
  • 6. DÄ°REK YILDIRIM DARBESÄ° Effects: Fire hazard Caused by: specific energy, charge If a lightning strikes a building, electrical energy is converted into heat. This may cause fires, especially in combustible roof structures! . ∫ ∞ = 0 2 dti R W ∫ ∞ = 0 idtQ
  • 8. AÅžIRI GERÄ°LÄ°MÄ°N OLUÅžMA NEDENLERÄ° 1-Åžalt hareketleri sonucu (anahtarlama elemanları sonucu)ortaya çıkan Aşırı Gerilimler. 2-Åžebekeden kaynaklanan harmonik ve darbeler sonucu oluÅŸan Aşırı Gerilimler. 3-Yıldırım DeÅŸarjı sonucu oluÅŸan Aşırı Gerilimler 4-Elektrostatik deÅŸarj sonucu oluÅŸan Aşırı Gerilimler
  • 9. Geçici Gerilimler (Transient Voltage) Geçici Gerilim Dalgalanmaları Nedir? Geçici Gerilim Dalgalanmaları mikro saniyeler mertebesinde kısa süreli olarak oluÅŸan, ancak nominal gerilimin birkaç katına ulaÅŸabilen gerilimlerdir ! 30 26 22 18 10 6 2 14 K/ Aşırı Gerilim Faktörü 1500 (I) 2500 (II) 4000 (III) 6000 (IV) Ûr v Yıldırım Darbeleri Anahtarlama Darbeleri Geçici Gerilim Dalgalanmaları Harmonikler YavaÅŸ ve hızlı Gerilim deÄŸiÅŸiklikleri Gerilim düşmeleri Kısa kesilmeler
  • 10. Yıldırım DeÅŸarjı Nasıl OluÅŸur ? -40 -20 0 0 200 400 600 800 t (µs)100 300 500 700 900 DeÅŸarjın baÅŸladığı an ve birkac ms sonraki periyot Yıldırım deÅŸarjının enerji etkisi laboratuvarlarda 10/350 µs test darbesi ile simüle edilmektedir. Ana DeÅŸarj Ä°kinci deÅŸarj Ölçülmüş yıldırım darbesi Simüle edilmiÅŸ yıldırım darbesi, 10/350 µs Iimp 1100 I (kA)
  • 11. Simüle EdilmiÅŸ Yıldırım ve Gerilim Darbesi Arasındaki Fark… -10 0 10 20 30 40 50 60 0 100 200 300 400 500 600 700 800 900 1000 Zaman [µs] Akım[kA] Simüle edilmiÅŸ yıldırım darbesi, 10/350 µs Simüle edilmiÅŸ gerilim dalgası, 8/20 µs
  • 12. AÅžIRI GERÄ°LÄ°ME NEDEN OLAN OLAYLAR İÇERÄ°SÄ°NDE EN TEHLÄ°KELÄ° OLANI YILDIRIM KAYNAKLI DARBELERÄ°DÄ°R.
  • 13. YILDIRIM DARBE DEÄžERLERÄ° VE SIKLIKLARI 50 % 10 % 5 % ≈ 1 % 30 80 100 200kA 20 90 100 100kA/µs 10 80 100 400C 105 106 5.106 107A2s Sıklık % Yıldırım Akımının Tepe DeÄŸeri Yıldırım Akımının Azami Artış hızı Yıldırımın Yükü Yıldırım Akımı Kare Darbe deÄŸeri
  • 14. YILDIRIM…  100 Milyon km hız  1 milyar volt  28000 celcius sıcaklık  Her gün 8 milyon kez düşüyor  Yarım saniyeden çok daha hızlı bir darbe  Statik bir elektrik  Adımları saniyenin/50 hizinda
  • 17. Harici Yıldırım Tesisatı Olmayan Bir Binaya Yıldırım Düşmesi (Direct Strike)
  • 18. Etkiler (direct strike) Harici Yıldırım Tesisatı Olmayan Bir Binaya Yıldırım Düşmesi (Direct Strike) Bir binaya düşen yıldırım, elektrik enerjisini ısıya dönüştürür. Bu özellikle kolay yanabilen çatılar için yangın riskini çok daha fazla arttırmaktadır. Yıldırım, metal parçaların ergimesine de sebep olabilmektedir. Ayrıca mekanik hasarlara da sebep olabilmektedir
  • 19. Yüksek Gerilim Hattına Yıldırım Düşmesi (Direct Strike)
  • 20. Alçak Gerilim Hattına Yıldırım Düşmesi (Direct Strike)
  • 21. Alçak Gerilim Hattına Yıldırım Düşmesi (Direct Strike) Alçak Gerilim Hattına Yıldırım Düşmesi (Direct Strike) A.G. hattına düşen yıldırımla Y.G. hattına düşen yıldırım arasındaki fark, kısmi yıldırım akımlarının iletildiÄŸi binaya olan uzaklığıyla ilgilidir. Etkileri: A.G. Åžebekesinde kısmi yıldırım akımları ve gerilim dalgalanmaları Nedeni:Yıldırım darbe akımının geniÅŸliÄŸi
  • 22. Yıldırımdan Korunma Tesisatına Yıldırım Düşmesi (Direct Strike)
  • 23. Yıldırımdan Korunma Tesisatına Yıldırım Düşmesi (Direct Strike) Yıldırımdan Korunma Tesisatına Yıldırım Düşmesi (Direct Strike) ve EÅŸ potansiyel Topraklama Sisteminin Var Olmaması Durumu Yıldırım düşmesi sonucu oluÅŸan yıldırım akımı, topraÄŸa yönlendiÄŸinde, tesisatın topraklama noktasında gerilim yükselmesine neden olur. Bu, ev içindeki eÅŸ potansiyel topraklama sisteminden geçer. Yıldırımdan korunma için uygun bir eÅŸ potansiyel topraklama elektrik tesisatının zarar görmesini engeller. Etkileri: Gerilim Darbeleri (Aşırı Gerilim) yalıtım bozulması Nedeni: Maksimum darbe akımı L1 L2 L3 PEN
  • 24. Yıldırımdan Korunma Tesisatına Yıldırım Düşmesi (Direct Strike) Yıldırımdan Korunma Tesisatına Yıldırım Düşmesi (Direct Strike) ve EÅŸ potansiyel Topraklama Sisteminin Var Olmaması Durumu Etkileri: Gerilim Darbeleri (aşırı gerilim) yalıtım bozulması Nedeni: Maksimum darbe akımı Yıldırım düşmesi sonucu oluÅŸan yıldırım akımı, topraÄŸa yönlendiÄŸinde, tesisatın topraklama noktasında gerilim yükselmesine neden olur. Bu, ev içindeki eÅŸ potansiyel topraklama sisteminden geçer. Yıldırımdan korunma için uygun bir eÅŸ potansiyel topraklama elektrik tesisatının zarar görmesini engeller.
  • 25. Yıldırımdan Korunma Tesisatına Yıldırım Düşmesi (Direct Strike) Yıldırımdan Korunma Tesisatına Yıldırım Düşmesi (Direct Strike) ve EÅŸ potansiyel Topraklama Sisteminin Var Olmaması Durumu Etkileri: Gerilim Darbeleri (aşırı gerilim) yalıtım bozulması Nedeni: Maksimum darbe akımı Yıldırım düşmesi sonucu oluÅŸan yıldırım akımı, topraÄŸa yönlendiÄŸinde, tesisatın topraklama noktasında gerilim yükselmesine neden olur. Bu, ev içindeki eÅŸ potansiyel topraklama sisteminden geçer. Yıldırımdan korunma için uygun bir eÅŸ potansiyel topraklama elektrik tesisatının zarar görmesini engeller.
  • 26. Yıldırım düşen noktanın yakınında Gerilim Darbelerinin Coupling Etkisi (Yıldırım Düşen Noktanın Yakınında) Etkileri: Yıldırım akımları, iletkenler (yer altındaki borular, kablolar vs ) arasından geçtiÄŸi zaman yüksek indüklenmiÅŸ gerilim üreten manyetik bir deÄŸiÅŸim yaratmaktadır. Bu durum yine, bina içindeki yangın riskini arttırmaktadır. Endüktif coupling yıldırım akımının manyetik etkisi ile oluÅŸur.
  • 27. Gerilim Darbelerinin Coupling Etkisi (Yıldırım Düşen Noktanın Uzağında)
  • 28. . max       dt di 2 km2 km Gerilim Darbelerinin Coupling Etkisi (Yıldırım düşen noktanın uzağında)
  • 29. Far lightning strike ENDÃœKTÄ°F KUPLAJ Pik deÄŸeri= max       dt di Parallel guided cables Conductor loop Lightning current arrestor Gerilim Darbelerinin Coupling Etkisi (Yıldırım düşen noktanın uzağında)
  • 31. Yıldırımın Kuplaj Etkisi Sonucu Zararları Source: http://www.photovoltaik.eu
  • 33. Etkileri Anahtarlama (Switching) Anahtarlama özellikle yükün endüktif yük olması durumundda tehlikeli olabilmektedir. ÖrneÄŸin; • Motorlar • Transformatörler • Åžok bobinleri • Klima kontrol sistemleri • Kaynak makinaları • Uzun aydınlatma iletkenleri Etkileri: Åžebeke hatlarında aşırı gerilim (darbeler) Neden: Anahtarlama esnasındaki yüksek akım ÅŸebekede geçici gerilim dalgalanmalarına (aşırı gerilim) sebep olmaktadır.
  • 34. Gerilim Darbelerinin Sonuçları 4. Data ve bilgi kaybı 5. Ä°malatın aksaması 6. Sistemin çalışmasında görülen ciddi aksaklıklar 7. Bilgi aktarımında oluÅŸan hatalar 1. Personel yaralanmaları 3. Darbelerden kaynaklanan malzeme hasarları 2. Yangın tehlikesi
  • 35. YILDIRIM DARBESÄ°NÄ°N ETKÄ°LERÄ° Yıldırım darbesi sonucu yıkılan bir rüzgar türbini…
  • 36. Dağıtım Panoları Kılcal çatlamalar 36 SU Boruları YILDIRIM DARBESÄ°NÄ°N ETKÄ°LERÄ°
  • 37. Elektronikteki Uygulama ÖrnekleriTarihi 1950 1960 1970 1980 1990 Elektronikteki uygulama örnekleri Time Interferans bağışıklığı Vakum Tüpleri Tranzistörler Entegre Devreler 2000 PC
  • 38. Sigorta ÅŸirketleri istatistikleri Hasar Bildirimlerinin Dağılımları Darbe Gerilimleri ve Yıldırım Düşmeleri dahil (direk ve endirek) Fırtına 1% DiÄŸerleri 27% Ä°hmalkarlık 23% Yıldırım ve Aşırı Darbe Gerilimleri 31% Hırsızlık 7% Su 6% Yangın 5% 9000 ÅŸikayetin analizi
  • 39. Amount of lightning – and surge damages Paid benefits for lightning- and surge damages Year Amount of lightning – and surge damages and paid benefits for lightning- and surge damages from residential building insurer Statistic Sigortaların ödediÄŸi tazminat miktarları
  • 41. LPZ 0 B LPZ 0 A LPZ 1 LPZ 2 LPZ 3 EÅŸ potansiyel BaÄŸ ve Sistem İçindeki Güç ve Data Hatları Data Hatları Güç Hatları EÅŸ potansiyel bağın amacı metal kısımlar ile hacim içindeki sistemler arasındaki potansiyel farkı yıldırımdan korunma için en aza indirmektir.
  • 42. Yıldırımdan Korunma için EÅŸ Potansiyel Topraklama Sistemi PEN iletkeninin bina topraklama sistemine baÄŸlanması Aşırı gerilim darbe koruyucusunun bina topraklama sistemine baÄŸlanması. Minimum Kesit: 16 mm2 Cu Metal komponentlerin EÅŸ potansiyel topraklama barasına (EBR) baÄŸlanması Topraklama barasının bina topraklama sistemine baÄŸlanması *EBR: EÅŸ potansiyel topraklama barası
  • 43. Yıldırımdan Korunma İçin EÅŸ potansiyel Sistem İçindeki Güç ve Data Hatları Yıldırımdan Korunma Bölge Kabulü LPZ = Lightning Protection Zone I LPZ 0 LPZ 1 Binaya Enerji GiriÅŸi Ana Dağıtım Panosu I LPZ 1  LPZ 2 Tali Dağıtım Panosu II II LPZ 2  LPZ 3 Cihaz giriÅŸi III III
  • 44. Aşırı Gerilim Darbe Koruyucu Seçimi B C D DIN VDE 0675 Bölüm 6 (A1/A2)’ya göre Aşırı Gerilim Darbe Koruyucu Seçimi Yıldırım Darbe Koruyucuları (Ana koruma) LPZ 0  1 Aşırı Gerilim Darbe Koruyucuları (Orta koruma) LPZ 1  2 Aşırı Gerilim Darbe Koruyucuları (Cihaz/hassas koruma) LPZ 2  3 Class I, IEC 61643-1:1998 Tip1, EN 61643-11 (07/02) Class II, IEC 61643-1:1998 Tip 2, EN 61643-11 (07/02) Class III, IEC 61643-1:1998 Tip 3,EN 61643-11 (07/02)
  • 46. Darbe Koruyucusu Teknolojileri Parafudrlarda Kullanılan Teknolojiler Spark Gaps (Kıvılcım Aralığı) DeÅŸarj kapasiteleri nedeniyle yüksek performanslı spark gap’ler yıldırımdan korunma elemanları olarak kullanılmaktadırlar. Spark gap’ler izleme akımlarını sönümlendirmektedir. Varistörler Varistörler aşırı gerilim darbe koruyucusu olarak kullanılmaktadır. DiÄŸer aşırı gerilim darbe koruyucularının tersine yıldırım akımı taşıma kapasiteleri sınırlıdır. Diyotlar Transzorb diyotlar, aynı zamanda sönümlendirici diyotlar olarak bilinirler. Hızlı tepki vermeleri karakteristik özellikleri olmakla birlikte, deÅŸarj kapasiteleri sınırlıdır.
  • 48. SPARK GAP TECHNOLOGY A new feature in low-voltage spark gaps is the use of carbon for the electrodes. •Lastingly consistent properties •High energy density in a small space •Heat-proof Teflon discs allow extremely narrow gaps between electrodes
  • 49. Structural design 30 V Graphite electrode High conducted current capacity (fire-resistant) Negative field voltage means good capacity for eliminating secondary mains currents Teflon discs 9 encapsulated sub spark gaps UG
  • 50. Varistor technology intermediate phase Electrodes Epoxy resin Sintered zinc oxide grains with other metal oxides added Zinc oxide microvaristor Ι = 10 µm Tinned copper electrode 1) Source: Siemens brochure on "SIOV metal oxide varistor" t/(ns)Output pulse U (V) Input pulse U t/(ns) (V) Varistors are voltage-dependent resistors with highly non-linear U/I characteristics. A number of microvaristors connected in parallel and in series produce special electrical characteristics. The transitions between the microvaristors can "age" under the influence of electrical surges.
  • 51. Diode technology Input pulse U t/(ps) (V) Output pulse U t/(ps) (V) Voltage (V) Current (A) UC UB UR UCUBUR Transorb diodes (also called suppressor diodes) are diodes which limit both positive and negative surges. Their extremely fast connecting response of just a few ps means they are especially suited to use in fine and data line protection equipment. Chapter 3.2. Conductor technologies and types
  • 52. Yıldırım ve Aşırı Gerilim Darbe Koruyucuları Seçimi
  • 53. Tesisat Rehberi / TN-C Åžebekeler (4 Telli) Nötr iletkeni ve koruma iletkeni (toprak) binanın giriÅŸinde bir iletkende birleÅŸtirilmiÅŸtir (PEN). PEN iletkeni, Nötr Ä°letkeni (N) ve Koruma Ä°letkeni (toprak - PE) olarak ayrılmıştır. Uygulama Alanı: Ağırlıklı olarak nüfus yoÄŸunluÄŸu olan bölgeler ve yeni tesisatlar Sayaçtan önce de kullanılabilir Aşırı gerilim darbe koruyucusu RCD’den önce monte edilmelidir. Aksi durumda, RCD darbe akımını kaçak akım olarak algılayıp devreyi açar. 3 x MC 50 B V20-C/3+NPE Åžebeke Tipleri
  • 54. 50% 50% Tesisat Rehberi / TN-C Åžebekeler (4 Telli) VDE V 0185 Part 4: 2002’den Örnek: Yıldırım Koruma Sınıfı : Tip 1 200 kA 50%’si topraÄŸa yönelir (akar) 50%’si binaya 4 iletken üzerinden geri döner.Bu da iletken başına 25 kA demektir.
  • 55. Tesisat Rehberi / TN-S Åžebekeler (5 Telli) Ağırlıklı olarak endüstriyel tesisatlar… 3 x MC 50-B ve 1 x MC125-B/NPE V20 C/3+NPE 200 kA Faz başına 25 kA Min. 100 kA
  • 56. Sigorta Kullanımı B tipi koruma ürünlerinde Ana sigorta deÄŸeri 500 A in üzerinde ise B tipi ürünün önüne maksimum 500 A sigorta baÄŸlanır. B tipi koruma ürünleri 25 kA e kadar kısa devre akımlarına karşıda koruma yapmaktadır. Olası uzun süreli ( saniyeler mertebesinde ) kısa devre akımlarında ürünün önüne baÄŸlanacak olan 500 A lik sigorta devreyi açarak kısa devre akımının ana ÅŸalter üzerine binmesine neden olacak ve ÅŸalterin devreyi kesmesini saÄŸlayacaktır. Kısa devre arızası kalktığında sigortalar tekrar devreye alınarak koruma ürünleri çalışır duruma getirilmelidir. Aksi taktirde devre korumasız kalacaktır bu sebeple baÄŸlanacak sigortaların kontak çıkışlı olarak tercih edilmesi önemlidir. 500 A in üzerinde ise Maksimum 500 A Maksimum 125 A
  • 57. Ä°lave Tesisat Rehberi Minimum BaÄŸlantı Kesitleri . Conductor type Conductor cross-section mm2 Type I (class B) 16 Cu Type II (class C) 6 Cu Type III (class D) 1.5 Cu Source: DIN EN 0185-305, Part 3
  • 58. Ä°lave Tesisat Rehberi • Paralel kablaj yapılmamalıdır (korunan ve korunmayan kablolar). • Kablolar ve yıldırım darbe koruyucu, loop içinde olmamalıdır. Yanlış Montaj
  • 59. SAT receivers DS-F m/f DS-F f/f 1 1 FineController FC- SAT-D 22 2 2 Chapter 6: Surge protection for data lines, telecommunications systems and ICA systems Switch
  • 60. Star network Ethernet 100BaseT External data line HUB/switch RJ45S- E100/4-C 1 1 3 3 3 333 1 RJ45S- E100/4-B 1 Chapter 6: Surge protection for data lines, telecommunications systems and ICA systems Net Defender 2 2 2 2 222 2
  • 61. Priz Tipi Korumalar Priz tipi koruma Anten koruma Telefon koruma Uydu Anten koruma Üçlü Priz koruma Adaptörlü koruma
  • 62. Application LSA- Plus Installation and devices Basic protection (spark gaps) • high protection level • high current capacity • good frequency attributes Combi protection • low protection level • over current fuse • small nominal currents
  • 63. LSA-strip Design of connecting – and separating strip l Cable side Incomming cable with color code Connection contact for cable Connection contact for switch cable Name of double wire/pair (DA) Hole for numbering
  • 64. Protection of a high speed computer network PC PC PC PC PC PC 230 V 230 V 230 V 230 V 230 V 230 V
  • 65. Kamera ve Anten Korumaları BNC tip N tip
  • 66. High frequency protectors To use for  TV and satellite installations  radio transmission  video and audio signals
  • 67. Types of arrester for high frequency applications λ/4-Protector - Is working linke a filter - No DC possible Not be used for current controlled antenna systems Protection with spark gap - DC transmission possible - Not very high bandwidth possible - Many plug systems available
  • 68. Overvoltage protection for sat antenna Quelle: EN 60728-11:2005 1) Net connection 2) Equipotential bar 2a) Equipotential bar 3) Equipotential wire 4) Earth line 5) Earth connection 6) Earthing system 7) Protection wire Protection must be planed for energy side also!
  • 69. Protection of CCTV (Close Circuit Television) • Suggestion for koax based systems • For IP-based systems
  • 70. Data ve Komünikasyon Teknolojisinde Darbe Koruma GeniÅŸ band koruma (kırmızı) Bina giriÅŸindeki hatta monte edilir. Kombine Koruma (mavi) Bina giriÅŸindeki hatta monte edilir. Korunacak cihazla arasındaki mesafe 10m’yi aÅŸmamalıdır. Ya da hassas koruma (yeÅŸil) Korunacak cihaza monte edilir. Tutarlı cihaz renkleri verilen cihazlar:
  • 71. Application solution for CCTV (Close Circuit Television)
  • 72. Application solution for CCTV (Close Circuit Television)
  • 73. RS 232 / RS 485 / Ehernet / Cat 5 / RJ11 / RJ45 korumalar

Editor's Notes

  1. Amount of lightning and surge
  2. At work or at home, we are steadily becoming more and more dependent on electrical and electronic appliances. From television sets and PCs in our homes to complex data and telecommunication networks - for most people, life without the help of these devices would be unthinkable. OBO offers you a comprehensive range of surge protection devices for your power and data networks. To make it easier for you to choose the correct OBO data line protection device, we have divided them into three classes. Universal device colours and clear designations identify these devices as broad-based protection (red), combined protection (blue) and precision protection (green).