The Vulnerability of the US Electric Power Grid to EMP and Severe Space Weather Events John G. Kappenman Storm Analysis Consultants 218-727-2666 http://www.linkedin.com/in/johnkappenman  EMP as well a widespread Cyber Attack and a Large Scale Geomagnetic storm are the largest threat to the Nation  Dr. William R. Graham, Chair EMP Commission (Hearing before the US House Armed  Services Committee,  July 10, 2008)
The US Electric Power Grid is a Critical Infrastructure & Vulnerable to both EMP & Space Weather (Geomagnetic Storms) Electricity is largest energy segment of US ~40% of all energy consumed EMP Commission,  FEMA Exec Order 13407 Investigation and National Academy of Sciences Reports Indicate  EMP & Space Weather Risks have potential to create Large Scale Blackouts,  Permanent Damage to Key  Power Grid Assets and Lengthy Restoration Loss of Electric Supply will Impact all other Interdependent Infrastructures  Potable Water distribution, waste treatment impacted within several hours,  Loss of perishable foods  and medications in about 12-24 hours,  Immediate or eventual loss of heating/AC, sewage, phones, transportation, fuel resupply, etc.  Review of Power Grid Vulnerability to Space Weather
Great Geomagnetic Storms  Disturbance Intensity Perspectives Impacts on North American Power Grid on March 13-14, 1989 occurred at disturbance intensities of ~300-500 nT/min Disturbance intensities of >2000 nT/min have been observed at latitudes of concern for US power grid infrastructure on at least 3 occasions since 1972 Disturbance intensity of ~5000 nT/min was estimated for storm on May 14-15, 1921 (estimated to be largest storm of 20 th  Century and comparable to Carrington Event of 1859) Power Grids should expect Storms 4 to 10 Times More Intense than the March 1989 Storm
Historic Storm Impacts A Brief Overview of the Last Geomagnetic Superstorm and  North American Power Grid Impacts March 13-14, 1989 This will provide some perspective on Potential Impacts from even larger Geomagnetic Storms and EMP Threats to this Critical Infrastructure
5 minutes of storm conditions that precipitated the Quebec blackout  A Quick Overview of the March 13-14, 1989  Geomagnetic Storm and  North American Power Grid Impacts
30 minutes of storm conditions later that day and impacts observed across the US A Quick Overview of the March 13-14, 1989  Geomagnetic Storm and  North American Power Grid Impacts
Salem Nuclear Plant  GSU Transformer  Failure, March 89 EMP & Geomagnetic Storms  Can Cause Permanent Transformer Damage  These Key Assets may take a  Year or More to Replace  Few Spares are available  Manufacturing performed offshore Damage due to one storm
Storms have Continent-Wide Footprints Field Disturbances from Electrojet Current Couple to Power Systems Geomagnetic Storms and Large Power Grids
Great Geomagnetic Storms   March 1989 Superstorm & May 1921 Storm Comparisons Boundaries of Eastward Electrojet March 13, 1989 Position of Westward Electrojet
Great Geomagnetic Storms   March 1989 Superstorm & May 1921 Storm Comparisons Estimated Boundaries of Eastward Electrojet for much larger May 14-15, 1921 Storm
EMP Effects Area  Fast Pulse  EMP Threats   to US Electric Grid Source:  EMP Commission including an Executive Report
EMP Fast Pulse Exposure covers a total of 1765 substations exposed or ~83% of 2106 major HV and EHV substations. In addition some 35,000 to 40,000 Distribution Class Substations may also be of concern for Fast Pulse Exposure EMP Threats   to US Electric Grid Major HV and EHV Substations
EMP Fast Pulse exposed power plants (Red) total 10,730 with a generation capacity that is ~74.4% of the U.S. total generation capability. EMP Threats   to US Electric Grid Large Electric Generation Plants
EMP and Great Geomagnetic Storms   US Electric Grid Vulnerability Trends and Preparedness New Awareness has developed on the Extremes of both EMP and Severe Geomagnetic Storms  Potential for blackouts of unprecedented scale for the US Electric Grid Potential for permanent damage to Key Grid Assets with lengthy restoration times  (For Example  Multiple Years to replace EHV Transformers ) Current Design Practices of Electric Grids have unknowingly and greatly escalated the Risks and Potential Impacts Un-Recognized Systemic Risk  No Design Code Yet to minimize this Threat Present Operational Procedures for Geomagnetic Storms are based upon limited experience, do not reduce GIC levels and will be inadequate for Severe Storms and also EMP threats Economic and societal costs could be also of unprecedented levels; August 14, 2003 Northeast Blackout Cost Estimate -  $4 - $10 Billion Hurricane Katrina Cost Estimate -    $81 - $125 Billion Severe Geomagnetic Storm Scenario   ~$1 - $2 Trillion in 1st Year  Depending on Damage, Full Recovery could take 4  10 Years
Severe Geomagnetic Storm Disturbance Scenario  Areas of Probable Power System Collapse Impacted Regions involve population of  >130 Million Power System Disturbance and Outage Scenario of Unprecedented Scale
365 Transformers At-Risk,  ~300,000 MVA Rating ~Severe Storm Scenario has larger geographic footprint than all other Natural Hazards  33% 24% 55% 34% 17% 27% 18% 19% 47% 9% 21% 35% 30% 7% 7% 40% 1% 82% 97% 11% 7% 37% 39% 8% 17% 23% 24% 38% 12% 75% 55% 72% 6% 15% 32% 6% 26% 19% 36% 47% 30% Estimated that over 300 large EHV Transformers would have sufficient GIC exposure to be At-Risk of permanent damage & loss  replacement could extend into 4-10 years at current world production rates Severe Geomagnetic Storm Scenario  At-Risk 345kV, 500kV & 765kV Transformers
Power Grid Vulnerability - Response Initiatives The EMP Commission notes positive movement within the Department of Defense toward addressing EMP survivability concerns.  Unfortunately, a similar level of effort for the Critical Infrastructures is not evident within the DOE, NERC, and the DHS. Improved Situational Awareness for Power Grid Operators is needed and is readily available Emphasis on disturbance environments/GIC levels instead of ambiguous K/G Indices Recognize and Improve Situational Awareness for Geomagnetic Storms and EMP Attack and Understand How Effects Differ from Other Disruptions Major Emphasis should be focused on Preventing EMP and Geomagnetic Storm-Related Catastrophic Failure  - Remedial Design measures for the Grid (transformer neutral resistors) are readily feasible and cost effective
Power Grid Vulnerability  Recommendations Protect high value assets through hardening:  hardening, special grounding, other schemes to assure functional operation for assets such as transformers, breakers, generators, critical elements of the natural gas supply systems to key power plants Protect the use of emergency power supplies and fuel delivery:  Increase battery and on-site generating capability for key substation and control facilities to extend critical period allowing recovery  Require emergency generator start, operation, and interconnection mechanisms to be EMP hard or manual. Requires ability to isolate these facilities from main electric power system.  Determine and specify those strategically important electrical loads critical to preserve in such an emergency Designate substantially more black start generation units coupled with specific transmission :  Improve, extend, and exercise recovery capabilities:  Assure sufficient numbers of adequately trained recovery personnel. Develop center for purpose of simulating EMP and other major system threatening attacks.

More Related Content

Kappenman Linked In

  • 1. The Vulnerability of the US Electric Power Grid to EMP and Severe Space Weather Events John G. Kappenman Storm Analysis Consultants 218-727-2666 http://www.linkedin.com/in/johnkappenman EMP as well a widespread Cyber Attack and a Large Scale Geomagnetic storm are the largest threat to the Nation Dr. William R. Graham, Chair EMP Commission (Hearing before the US House Armed Services Committee, July 10, 2008)
  • 2. The US Electric Power Grid is a Critical Infrastructure & Vulnerable to both EMP & Space Weather (Geomagnetic Storms) Electricity is largest energy segment of US ~40% of all energy consumed EMP Commission, FEMA Exec Order 13407 Investigation and National Academy of Sciences Reports Indicate EMP & Space Weather Risks have potential to create Large Scale Blackouts, Permanent Damage to Key Power Grid Assets and Lengthy Restoration Loss of Electric Supply will Impact all other Interdependent Infrastructures Potable Water distribution, waste treatment impacted within several hours, Loss of perishable foods and medications in about 12-24 hours, Immediate or eventual loss of heating/AC, sewage, phones, transportation, fuel resupply, etc. Review of Power Grid Vulnerability to Space Weather
  • 3. Great Geomagnetic Storms Disturbance Intensity Perspectives Impacts on North American Power Grid on March 13-14, 1989 occurred at disturbance intensities of ~300-500 nT/min Disturbance intensities of >2000 nT/min have been observed at latitudes of concern for US power grid infrastructure on at least 3 occasions since 1972 Disturbance intensity of ~5000 nT/min was estimated for storm on May 14-15, 1921 (estimated to be largest storm of 20 th Century and comparable to Carrington Event of 1859) Power Grids should expect Storms 4 to 10 Times More Intense than the March 1989 Storm
  • 4. Historic Storm Impacts A Brief Overview of the Last Geomagnetic Superstorm and North American Power Grid Impacts March 13-14, 1989 This will provide some perspective on Potential Impacts from even larger Geomagnetic Storms and EMP Threats to this Critical Infrastructure
  • 5. 5 minutes of storm conditions that precipitated the Quebec blackout A Quick Overview of the March 13-14, 1989 Geomagnetic Storm and North American Power Grid Impacts
  • 6. 30 minutes of storm conditions later that day and impacts observed across the US A Quick Overview of the March 13-14, 1989 Geomagnetic Storm and North American Power Grid Impacts
  • 7. Salem Nuclear Plant GSU Transformer Failure, March 89 EMP & Geomagnetic Storms Can Cause Permanent Transformer Damage These Key Assets may take a Year or More to Replace Few Spares are available Manufacturing performed offshore Damage due to one storm
  • 8. Storms have Continent-Wide Footprints Field Disturbances from Electrojet Current Couple to Power Systems Geomagnetic Storms and Large Power Grids
  • 9. Great Geomagnetic Storms March 1989 Superstorm & May 1921 Storm Comparisons Boundaries of Eastward Electrojet March 13, 1989 Position of Westward Electrojet
  • 10. Great Geomagnetic Storms March 1989 Superstorm & May 1921 Storm Comparisons Estimated Boundaries of Eastward Electrojet for much larger May 14-15, 1921 Storm
  • 11. EMP Effects Area Fast Pulse EMP Threats to US Electric Grid Source: EMP Commission including an Executive Report
  • 12. EMP Fast Pulse Exposure covers a total of 1765 substations exposed or ~83% of 2106 major HV and EHV substations. In addition some 35,000 to 40,000 Distribution Class Substations may also be of concern for Fast Pulse Exposure EMP Threats to US Electric Grid Major HV and EHV Substations
  • 13. EMP Fast Pulse exposed power plants (Red) total 10,730 with a generation capacity that is ~74.4% of the U.S. total generation capability. EMP Threats to US Electric Grid Large Electric Generation Plants
  • 14. EMP and Great Geomagnetic Storms US Electric Grid Vulnerability Trends and Preparedness New Awareness has developed on the Extremes of both EMP and Severe Geomagnetic Storms Potential for blackouts of unprecedented scale for the US Electric Grid Potential for permanent damage to Key Grid Assets with lengthy restoration times (For Example Multiple Years to replace EHV Transformers ) Current Design Practices of Electric Grids have unknowingly and greatly escalated the Risks and Potential Impacts Un-Recognized Systemic Risk No Design Code Yet to minimize this Threat Present Operational Procedures for Geomagnetic Storms are based upon limited experience, do not reduce GIC levels and will be inadequate for Severe Storms and also EMP threats Economic and societal costs could be also of unprecedented levels; August 14, 2003 Northeast Blackout Cost Estimate - $4 - $10 Billion Hurricane Katrina Cost Estimate - $81 - $125 Billion Severe Geomagnetic Storm Scenario ~$1 - $2 Trillion in 1st Year Depending on Damage, Full Recovery could take 4 10 Years
  • 15. Severe Geomagnetic Storm Disturbance Scenario Areas of Probable Power System Collapse Impacted Regions involve population of >130 Million Power System Disturbance and Outage Scenario of Unprecedented Scale
  • 16. 365 Transformers At-Risk, ~300,000 MVA Rating ~Severe Storm Scenario has larger geographic footprint than all other Natural Hazards 33% 24% 55% 34% 17% 27% 18% 19% 47% 9% 21% 35% 30% 7% 7% 40% 1% 82% 97% 11% 7% 37% 39% 8% 17% 23% 24% 38% 12% 75% 55% 72% 6% 15% 32% 6% 26% 19% 36% 47% 30% Estimated that over 300 large EHV Transformers would have sufficient GIC exposure to be At-Risk of permanent damage & loss replacement could extend into 4-10 years at current world production rates Severe Geomagnetic Storm Scenario At-Risk 345kV, 500kV & 765kV Transformers
  • 17. Power Grid Vulnerability - Response Initiatives The EMP Commission notes positive movement within the Department of Defense toward addressing EMP survivability concerns. Unfortunately, a similar level of effort for the Critical Infrastructures is not evident within the DOE, NERC, and the DHS. Improved Situational Awareness for Power Grid Operators is needed and is readily available Emphasis on disturbance environments/GIC levels instead of ambiguous K/G Indices Recognize and Improve Situational Awareness for Geomagnetic Storms and EMP Attack and Understand How Effects Differ from Other Disruptions Major Emphasis should be focused on Preventing EMP and Geomagnetic Storm-Related Catastrophic Failure - Remedial Design measures for the Grid (transformer neutral resistors) are readily feasible and cost effective
  • 18. Power Grid Vulnerability Recommendations Protect high value assets through hardening: hardening, special grounding, other schemes to assure functional operation for assets such as transformers, breakers, generators, critical elements of the natural gas supply systems to key power plants Protect the use of emergency power supplies and fuel delivery: Increase battery and on-site generating capability for key substation and control facilities to extend critical period allowing recovery Require emergency generator start, operation, and interconnection mechanisms to be EMP hard or manual. Requires ability to isolate these facilities from main electric power system. Determine and specify those strategically important electrical loads critical to preserve in such an emergency Designate substantially more black start generation units coupled with specific transmission : Improve, extend, and exercise recovery capabilities: Assure sufficient numbers of adequately trained recovery personnel. Develop center for purpose of simulating EMP and other major system threatening attacks.

Editor's Notes

  • #6: This animation provides a recreation of just 20 minutes of the geomagnetic storm events from 2:39-2:58 EST on March 13, 1989. It was during this time interval that the geomagnetic storm caused the Blackout to the entire Province of Quebec. As illustrated by this animation, storm activity was confined to very high latitudes (no population or infrastructures) and then it had a sudden onset and large geographic footprint of intense disturbances that developed along the US-Canada border. The speed and size of this onset is unlike traditional terrestrial weather threats that power grids are more commonly exposed to and better engineered to withstand. This animation shows the sequence of significant power grid impacts reported to NERC that developed due to the intense geomagnetic disturbances shown in the prior animation. As shown power system impacts were in the interconnected power grid along the US-Canada border. The most significant of these impacts was the complete Blackout to the Hydro Quebec grid and the entire Quebec province. They went from normal operating conditions to complete province-wide blackout in just 92 seconds. There was not even sufficient time available for system operators to even assess what was happening to the grid, let alone take any meaningful human intervention actions. For comparison purposes, it is important to note that the intensity of the disturbance over the Quebec region only reached ~500 nT/min, while data from historically larger storms indicate that intensities up to ~5000 nT/min are possible (10 times larger than this storm).
  • #7: This animation shows further intense geomagnetic storm conditions that happened later that day on March 13, 1989. The storm reached higher intensity levels and as a result it expanded to lower latitudes and as shown during this 50 minute time interval, the most intense storm activity is centered on mid-latitude portions of the US and at times has a continent-wide footprint. Also shown is even more intense activity that extends around the globe into northern Europe during this same time interval, clearly making this type of storm an event that can have a planetary reach. This animation shows the sequence of significant power grid events that again were reported to NERC. The NERC assessment of this storm concluded that major portions of the US Power grid came uncomfortably close to also experiencing a blackout of unprecedented scale. The area of blackout could have extended from the Wash DC area and surrounding mid-Atlantic states through the upper mid-west and even into the Pacific Northwest regions of the US. Again, these impacts were observed for intensities that generally were in the ~300 nT/min range, while very large storms could reach ~5000 nT/min in intensity.
  • #8: This is a picture of the Salem New Jersey Nuclear Plant GSU Transformer and permanent damage caused by the March 13, 1989 Geomagnetic Storm. The internal heating was so intense it melted portions of the low voltage windings of this transformer, windings and leads rated for ~3000 amps.
  • #9: As shown above, geomagnetic storms have a disturbance footprint that can easily span the continental US. These storms can cause multiple correlated failures that far exceed the traditional N-1 design criteria used for the reliability design US Power Grid. The bottom illustration shows that large regional geomagnetic disturbance conditions arise due to a large electrojet current (multi-million amps) in the ionosphere at an altitude of ~100km due to the storm. Both a large eastward and westward electrojet current are created during storms and can span large portions of the planet as the storms increase in intensity. Rapid changes in the geomagnetic field can induce currents (geomagnetically-induced currents or GIC that is low frequency, ~near DC) that can flow into and out of the power grid through the neutral to ground connections of large EHV transformers. It is the flow of this GIC in the transformers that is the root-cause of all power system problems. EMP threat environments can also cause a geographically large geomagnetic field disturbance and lead to similar consequences to the exposed power grid.
  • #10: Illustration showing the large regions of geomagnetic field eastward and westward electrojet currents at time 22UT on March 13, 1989. This provides some perspective as we explore a comparison with even larger storms such as those in 1859, and as shown in the next slide May 1921, before power grids as we know them today existed.
  • #11: Data (in the form of strip charts) exists across North America for what many consider to be the largest geomagnetic storm of the 20 th Century. This historic data can be readily compared with the same data from the March 1989 storm to show not only the increase in intensity but also a dramatic increase in the geographic footprint of this large storm compared to the March 1989 storm. This comparative analysis indicates that not only is the 1921 storm as much as 4 to 10 times more intense than the March 1989 storm, but as shown by the white outlined areas, it would have an even larger geographic footprint that would extend across the entire continental US and its electric power grid.
  • #12: A high altitude nuclear burst can create both a Fast Pulse (E1) and a Slow Pulse (E3). This event can also have an extremely large geographic footprint which can expose a significant portion of the US Power Grid to potential damage from these threat environments. The E1 or Fast Pulse (footprint as shown above) produces an intense EM (electromagnetic field) with a fast rise-time (faster and more intense than lightning transients that power grids can also be exposed to). The E3 or slow pulse is a geomagnetic field disturbance similar to, but more intense than that produced by a severe geomagnetic storm.
  • #13: Both exposure to E1 and E3 pulses can impact EHV Substations. The E1 Pulse has the potential to damage sensitive electronic relay and control systems in each of these substations, while the E3 Pulse can produce large GICs that can trigger blackouts of the grid and damage EHV transformers. In addition, the E1 pulse has the potential to initiate multiple distribution line faults and permanently damage distribution line insulators due to the wide-spread and simultaneous exposure to lightning like pulse across the region.
  • #14: The E1 or fast pulse also has the potential to cause damage to sensitive electronic control systems in electric power plants as well. A well-placed device may have the potential to cause damage to this portion of the power grid infrastructure as well.
  • #15: As noted in this summary, both an EMP or Severe Geomagnetic Storm have the potential to cause electric power grid blackouts of unprecedented scale and with lengthy and unprecedented restoration times, perhaps multiple years. Unfortunately no design code has ever existed in the power industry to take into consideration these threat environments and in retrospect the engineering practices that were undertaken have in many cases unknowingly and greatly escalated the risks and potential impacts of these threat environments on this critical infrastructure. As shown in this economic analysis comparison performed for the FEMA assessment of Severe Geomagnetic Storms, this sort of storm could well be the most serious Natural Disaster that the country could ever face.
  • #16: This illustration shows the analysis results for a 4800 nT/min geomagnetic storm impulsive disturbance located at 50 degrees geomagnetic latitude (some 10 times stronger than the March 1989 storm and similar to that observed in the may 1921 storm). Using NERC disturbance criteria, the outlines of probable blackout regions are shown, progressive collapse could actually make initial blackout regions even larger than shown here. This would be a blackout of unprecedented scale and involve US population of over 130 million people. The red and green dots indicate the polarity and magnitude of GIC flow in each large EHV transformer in the US network. Red means flow of GIC into the transformer from ground, green means flow of GIC out of the transformer into ground. Polarity does not matter in that either polarity causes transformer half-cycle saturation and associated impacts. The size of th dot indicates magnitude, the larger the dot, the larger the GIC and its impacts on the transformer and electric power grid.
  • #17: This scenario also causes a large number of EHV transformers to experience large enough GIC Levels to be considered to be At-Risk of permanent damage due to this exposure. Each red dot indicates the location of an important At-Risk Transformer, also shown is the Percentage of Transformer in each state that is considered At-Risk, there are a number of states with At-Risk transsrformers at levels of ~50% or greater. This level of damage may prevent meaningful re-establishment of an interconnected power grid and raise many problems of transmitting and distributing electricity in these heavily impacted states.