This document contains technical specifications for circuit breaker CBL-AHU-S2 and motor overload protection for a 50HP air handling unit motor. It lists the circuit breaker trip settings as 125A with a 5x instantaneous trip of 625A. It also lists the motor overload protection as Class 20 for a 50HP motor served by circuit breaker CB-AHU-S2.
1 of 1
Download to read offline
More Related Content
M#1 50 hp 07-25-13
1. CBL-AHU-S2
0.5 1 10
100
1K
10K
100K
0.01
0.10
1
10
100
1000
CURRENT IN AMPERES
TIMEINSECONDS
CUTLER-HAMMER
HKD
HKD
Trip 125.0 A
Settings Phase
Thermal Curve (Fixed)
INST (5-10 x Trip) 5 (625A)
CB-AHU-S2
MOL
Class 20
Motor O/L
Settings Phase
Class 20
OL-50HP
CBL-AHU-S2
AHU-S2 (M#1 50HP)
CUTLER-HAMMER
HKD
HKD
Trip 125.0 A
Settings Phase
Thermal Curve (Fixed)
INST (5-10 x Trip) 5 (625A)
CB-AHU-S2
MOL
Class 20
Motor O/L
Settings Phase
Class 20
OL-50HP
CBL-AHU-S2
AHU-S2 (M#1 50HP)
CBL-AHU-S2
Isc 3P21219A
Isc SLG 12194 A
AHU-S2 (M#1 50HP)
Isc 3P355A
Isc SLG 135 A
CB-AHU-S2
OL-50HP
VFD-50HP
TCC: M#1 50HP Current Scale x 1 Reference Voltage: 480 July 24, 2013