The document provides requirements for designing a HVAC system for a building consisting of a restaurant, lounge, and kitchen with a maximum capacity of 100 people. It includes building data, schedules for use, infiltration rates, design cooling and heating loads, ventilation rates per ASHRAE standards, duct design and sizing, and component selection including a cooling coil and heating coil from Carrier.
1 of 22
Downloaded 17 times
More Related Content
Mehmet Bariskan -Env. Control 2010_Design for a heating and cooling system of a building
1. City College of New York School of Engineering Mechanical Engineering Department
ME 54700-Environmental Control
Fall-2010
Subject : Design for a heating and cooling system of a building
Instructor : Jorge E. González, Ph.D.NOAA CREST Professor of
Mechanical Engineering
Student : Mehmet Bariskan
2. 2
Requirement
Design for a heating and cooling system of a building consisting of a restaurant, lounge, and a
kitchen for maximum capacity of 100 people. The restaurant is to be located in the New
York/New Jersey area and the HVAC design should consider high energy efficient approaches.
Building data is as follows;
Building size: 80 ft x 60 ft x 12 ft.
Windows are located in the south, north and east sides; with sizes corresponding to wall
area percentages equal to 25%, 10%, and 10%. Windows should be double glazing,
low emissivity. Overhangs can be used to reduce cooling loads.
Walls and roofs should use high R values corresponding to minimums of 20 and 36 hrft2-
ºF/Btu, respectively.
Lighting intensity is equivalent to 10W/m2.
Equipment includes a large gas stove, a large refrigerator, several TV screens spread
across the room, and three computers.
Infiltration should be set to a high value equal to 1.5 changes per hour to maintain good
levels of air quality.
Provide the following in your solution;
Set a schedule for use of the building.
Report infiltration rates, design cooling and heating loads based on daily profile.
Define ventilation rates. Refer to ASHRAE Standards for specific application.
Design air distribution system. Prefer method is exposed round system. Specify duct
diameters, distance, and exhaust systems.
Sizing and recommended HVAC components; V/C system, air handling unit, cooling &
heating coils. Specify vendors of each component and model numbers.
Provide schematic of the design.
Provide cost estimate of the HVAC system.
Report;
Write a concise report that describes the design, and includes the requirements above.
Include a cover page in the report. Reports should not exceed 20 pages total, and are
due Friday December 17, 2010, at 5:00 PM EST.
Reference:
1. 2007 American Society of Heating, Refrigeration and Air Conditioning (ASHRAE),
Applications Handbook.
3. 3
Schedule for use of the building
8 am to 8 pm (12 hours /day- Lights on 12 hours to), 100 people max. capacity (100 people an
hour)
80 ft x 60 ft x 12 ft
Total;
Area East (ft2
) North ( West ( South (
Wall 648 864 688 720
Window 72 96 0 240
Door 0 0 32 0
Length
Window 2x(9+8)=34 ft 2x(12+8)=40 ft 0 2x(4.5+8)+
2x(25.5+8)=92ft
Door 0 0 2x(4+8)=24 ft 0
4. 4
Kitchen;
Area East (ft2
) North ( West ( South (
Wall 336 360 360 360
Window 0 0 0 0
Door 24 0 0 0
Length
Window 0 0 0 0
Door 2*(3+8)=22 ft 0 0 0
Lounge;
Area East (ft2
) North ( West ( South (
Wall 336 360 328 324
Window 0 0 0 36
Door 24 0 32 0
Length
Window 0 0 0 2x(4.5+8)=25ft
Door 2*(3+8)=22 ft 0 2*(4+8)=24 ft 0
Restaurant;
Area East (ft2
) North ( West ( South (
Wall 648 504 672 396
Window 72 96 0 204
Door 0 0 48 0
Length
Window 2x(9+8)=34 ft 2x(12+8)=40 ft 0 2x(25.5+8)=67ft
Door 0 0 4*(3+8)=44 ft 0
ï‚· Infiltration rates
Assuming 20 mph (29.5 ft/s),
Δ P=
(inWg)
South North East West
Cp (Figure 7.4) 0.6 -0.2 -0.6 -0.6
0.114 -0.038 -0.114 -0.114
(Figure 7.6) 0.01 0.01 0.01 0.01
0.12 -0.03 -0.12 -0.12
5. 5
Assuming k= 1 (tight) for windows, k=0.22 (tight) for wall, k=40 crack 1/8’’, one door on south,
South North East West
(inWG) 0.12 -0.03 -0.12 -0.12
Q/L (Fig. 7.8) 0.35 -0.1 -0.35 -0.35
L window (ft) 92 40 34 0
Q window 32.2 4 11.9 0 48.1
(Q/A) wall (Fig. 7.11) 0.05 0.02 -0.05 -0.05
A wall 720 864 648 688
Qc wall 36 17.3 32.4 34.4 120.1
(Q/L) door(Fig. 7.9) 0 0 0 4
L door 0 0 0 24
Q door 0 0 0 96 96
Total CFM 264.2
And infiltration due to door opening as a function of traffic rate 100 people per hour.
From Figure (7.10) C=2900 (Single-bank type) Q traffic= 1000 CFM
Q Total Infiltration = 1264 CFM
ï‚· Design cooling and heating loads based on daily profile.
Design Dry 90 F Summer, Winter 20 F
Windows double glazing with low emissivity ( Table 6.6)
18. 18
Qcooling = 55493 W = 15.78 Tons
Qheating = 40414 W = 11.49 Tons
Ventilation Rates
The volume of building = 80 x 60 x 12 = 57600 ft
3
Infiltration should be set to a high value equal to 1.5 changes per hour
= 57600 x 1.5 = 86400 ft
3
/h = 1440 CFM.
Cooling and Heating Coil capacities
Total volume = 60 x 80 x 12 = 57600 ft2
Flow Rate = = = 1440 CFM
%25 of air supplied from inside 0.25 x 1440 = 360 CFM
%75 of air supplied from outside 0.75 x 1440 = 1080 CFM
Specific volume of air
Mass flow rate going to system, coming from outside, returned from inside
21. 21
Performance Data;
Rows Circuit
Type
Pins / in Total
Capacity
Btuh
Water
Temp
Drop
Leaving
Air DB
Temp
Leaving
Air WB
Temp
Water
Pressure
Drop (ft
WG)
Air
Pressure
Drop (in
WG)
4 Half 12 15275 14.7 59.14 57.37 11.3 0.61
Heating Coil;
Supplier: Carrier (www.commercial.carrier.com)
Model Number: 28BHA214HDB121CR
22. 22
Performance Data;
Rows Circuit
Type
Pins / in Total
Capacity
Btuh
Water
Temp
Drop
Leaving
Air DB
Temp
Water
Pressure
Drop (ft
WG)
Air
Pressure
Drop (in
WG)
2 Half 14 37215 46.19 108.62 9.16 0.52