MOTOR CURRENT
SINGLE	
 PHASE	
 MOTORS
110V	
 ac 220V	
 ac 240V	
 ac
0.07	
 kW 1/12 2.4 1.2 1.1
0.1	
 kW 1/8 3.3 1.6 1.5
0.12	
 kW 1/6 3.8 1.9 1.7
0.18	
 kW 1/4 4.5 2.3 2.1
0.25	
 kW 1/3 5.8 2.9 2.6
0.37	
 kW 1/2 7.9 3.9 3.6
0.56	
 kW 3/4 11 5.5 5
0.75	
 kW 1 15 7.3 6.7
1.1	
 kW 1.5 21 10 9
1.5	
 kW 2 26 13 12
2.2	
 kW 3 37 19 17
3	
 kW 4 49 24 22
3.7	
 kW 5 54 27 25
4	
 kW 5.5 60 30 27
5.5	
 kW 7.5 85 41 38
7.5	
 kW 10 110 55 50
THREE	
 PHASE	
 MOTORS
220V	
 ac 240V	
 ac 380V	
 ac 415V	
 ac 550V	
 ac
0.1	
 kW 1/8 0.7 0.6 0.4 0.4 0.3
0.12	
 kW 1/6 1 0.9 0.5 0.5 0.3
0.18	
 kW 1/4 1.3 1.2 0.8 0.7 0.4
0.25	
 kW 1/3 1.6 1.5 0.9 0.9 0.6
0.37	
 kW 1/2 2.5 2.3 1.4 1.3 0.8
0.56	
 kW 3/4 3.1 2.8 1.8 1.6 1.1
0.75	
 kW 1 3.5 3.2 2 1.8 1.4
1.1	
 kW 1.5 5 4.5 2.8 2.6 1.9
1.5	
 kW 2 6.4 5.8 3.7 3.4 2.6
2.2	
 kW 3 9.5 8.7 5.5 5 3.5
3.0	
 kW 4 12 11 7 6.5 4.7
3.7	
 kW 5 15 13 8 8 6
4.0	
 kW 5.5 16 14 9 8 6
5.5	
 kW 7.5 20 19 12 11 8
7.5	
 kW 10 27 25 16 15 11
9.3	
 kW 12.5 34 32 20 18 14
10	
 kW 13.5 37 34 22 20 15
11	
 kW 15 41 37 23 22 16
15	
 kW 20 64 50 31 28 21
18	
 kW 25 67 62 39 36 26
22	
 kW 30 74 70 43 39 30
30	
 kW 40 99 91 57 52 41
37	
 kW 50 130 119 75 69 50
45	
 kW 60 147 136 86 79 59
55	
 kW 75 183 166 105 96 72
75	
 kW 100 239 219 138 125 95
90	
 kW 125 301 269 170 156 117
110	
 kW 150 350 325 205 189 142
130	
 kW 175 410 389 245 224 169
150	
 kW 200 505 440 278 255 192
HPMOTOR	
 RATING
APPROX.	
 F.L.C.	
 AT	
 LINE	
 VOLTAGE
MOTOR	
 RATING HP
APPROX.	
 F.L.C.	
 AT	
 LINE	
 VOLTAGE
AC Motors - full load current tables (1450rpm approx.) (provided as a guide to the selection of suitable MEM control gear).
The tables are based on motors of approximately 1450rpm of average efficiency and power factor. Motors of higher speed usually take a
lower current than that shown in the table; while motors of lower speed usually take higher current. Wide variations from these figures
can arise, especially on single phase motors, and engineers should, whenever possible, determine the actual f.l.c from the motor rating plate
in each case.

More Related Content

Motor current-rm-technical

  • 1. MOTOR CURRENT SINGLE PHASE MOTORS 110V ac 220V ac 240V ac 0.07 kW 1/12 2.4 1.2 1.1 0.1 kW 1/8 3.3 1.6 1.5 0.12 kW 1/6 3.8 1.9 1.7 0.18 kW 1/4 4.5 2.3 2.1 0.25 kW 1/3 5.8 2.9 2.6 0.37 kW 1/2 7.9 3.9 3.6 0.56 kW 3/4 11 5.5 5 0.75 kW 1 15 7.3 6.7 1.1 kW 1.5 21 10 9 1.5 kW 2 26 13 12 2.2 kW 3 37 19 17 3 kW 4 49 24 22 3.7 kW 5 54 27 25 4 kW 5.5 60 30 27 5.5 kW 7.5 85 41 38 7.5 kW 10 110 55 50 THREE PHASE MOTORS 220V ac 240V ac 380V ac 415V ac 550V ac 0.1 kW 1/8 0.7 0.6 0.4 0.4 0.3 0.12 kW 1/6 1 0.9 0.5 0.5 0.3 0.18 kW 1/4 1.3 1.2 0.8 0.7 0.4 0.25 kW 1/3 1.6 1.5 0.9 0.9 0.6 0.37 kW 1/2 2.5 2.3 1.4 1.3 0.8 0.56 kW 3/4 3.1 2.8 1.8 1.6 1.1 0.75 kW 1 3.5 3.2 2 1.8 1.4 1.1 kW 1.5 5 4.5 2.8 2.6 1.9 1.5 kW 2 6.4 5.8 3.7 3.4 2.6 2.2 kW 3 9.5 8.7 5.5 5 3.5 3.0 kW 4 12 11 7 6.5 4.7 3.7 kW 5 15 13 8 8 6 4.0 kW 5.5 16 14 9 8 6 5.5 kW 7.5 20 19 12 11 8 7.5 kW 10 27 25 16 15 11 9.3 kW 12.5 34 32 20 18 14 10 kW 13.5 37 34 22 20 15 11 kW 15 41 37 23 22 16 15 kW 20 64 50 31 28 21 18 kW 25 67 62 39 36 26 22 kW 30 74 70 43 39 30 30 kW 40 99 91 57 52 41 37 kW 50 130 119 75 69 50 45 kW 60 147 136 86 79 59 55 kW 75 183 166 105 96 72 75 kW 100 239 219 138 125 95 90 kW 125 301 269 170 156 117 110 kW 150 350 325 205 189 142 130 kW 175 410 389 245 224 169 150 kW 200 505 440 278 255 192 HPMOTOR RATING APPROX. F.L.C. AT LINE VOLTAGE MOTOR RATING HP APPROX. F.L.C. AT LINE VOLTAGE AC Motors - full load current tables (1450rpm approx.) (provided as a guide to the selection of suitable MEM control gear). The tables are based on motors of approximately 1450rpm of average efficiency and power factor. Motors of higher speed usually take a lower current than that shown in the table; while motors of lower speed usually take higher current. Wide variations from these figures can arise, especially on single phase motors, and engineers should, whenever possible, determine the actual f.l.c from the motor rating plate in each case.