To stop the flow of
                   volatile or
               hazardous fluids
             from tanks, in a fire
Feederstop        emergency             Firestop
                  situation, by
                 automatically
              sealing each tank
                inlet and outlet

     IN                              OUT
                            YOUR S A TIS FA C TION FIRS T¡­
Product Background
                  In 1993 we sat down with tank farms owners,
                  at their request, to design and manufacture a
                  device complying with French and European
                  safety regulations concerning industrial sites
                  potentially dangerous for the environment in
                  case of accident (EEC Directive n¡ã
                  82/501/CEE a.k.a. Seveso Directive).
                  Based on
                  ?French tank farms regulations (art 318.21),
                  ?French industrial safety commission
                  requirements (IM art. 17 dated 9/11/89)
                  ? ATEX 94/9/CE (EU directive on equipment
                  and protective systems intended for use in
                  potentially explosive atmospheres)
 It appeared the most reliable solution was a non return
 swing check valve used backward.
                                    YOUR S A TIS FA C TION FIRS T¡­
Regulation requirements
Legal mandatory requirements requested the device :
   ?   To keep the inflammable liquid inside the tank to avoid
       further feeding of the fire in case of piping break down
       and/or leakage,
   ?   To close down automatically without any human
       intervention and without depending on external power
       supply other than the one responsible for the
       accident. In other words the fire alone should activate
       the automatic shut down (positively safe),
   ?   To allow remote closing of the device,
   ?   To be fire safe, in compliance with BS 6755,
   ?   To avoid disturbance of existing process line
   ?   To allow injection of foam through conduit
   ?   To allow quick emptying of the tank once the fire is
       controlled (in case of tank leak for example)
   ?   To be strictly dedicated to safety.
                                        YOUR S A TIS FA C TION FIRS T¡­
I- Our dedicated solution: FIRESTOP




                        YOUR S A TIS FA C TION FIRS T¡­
I- Our dedicated solution: FIRESTOP
? We supply Firestops with nominal diameter ranging from 50
  to 600 mm (2 to 24 inches). Other sizes on request
? Possible material : Cast Iron (A 216 gr WCB) or Stainless
  Steel (A 351 gr CF 3 M) . Other materials on request
? Connections: Flanges (ISO PN 20)
? From DN 450 (18¡¯¡¯) Firestops are equipped with a reduction
  and a hydraulic flow attenuation rotating shock absorber.
  system




                                       YOUR S A TIS FA C TION FIRS T¡­
A ¨C To keep the liquid inside¡­
? Stellite/stellite tightness
  (Stellite 6, plasma deposit
  on seat and disc as per
  NF EN 15614-7)

? Even      though      fluid
  pressure is usually low in
  the tanks, we use our
  successful PN20 (#150)
  swing check valve design
  issued from our almost
  150 years experience
  manufacturing valves.

                                YOUR S A TIS FA C TION FIRS T¡­
B ¨C To close down automatically¡­
                                                      (1)

                                                      (2)



                       ? 3 non ferrous thermo fuses (1) hold the
Top                    disc in a normally open position .
view                   ? These fuses are mounted at the end of
                       the disc holding shaft in an enclosure also
                       including a loaded spring (2).
? When the on site ambient temperature reaches the set up
point of 124¡ã C / 255¡ã F (set up as standard; other temp. on
request) the fuses become liquid thus releasing the spring
which close the disc automatically.
                                         YOUR S A TIS FA C TION FIRS T¡­
B ¨C To close down automatically¡­




                      YOUR S A TIS FA C TION FIRS T¡­
B ¨C To close down automatically¡­
         Thermo fuses showed




    BEFORE          &            AFTER
             the fire test

                             YOUR S A TIS FA C TION FIRS T¡­
C ¨C To allow remote operation¡­
? As an option our Firestop can
be      equipped      with     an
electromagnetic or a pneumatic
drive, allowing closing of the
device from a remote location.

?In case of power failure
(emergency         stop,      onsite
accident/fire too far to be detected
by the fuses,¡­) both drives are
fail safe and will make the disc to
close thus sealing the tank.

                                       YOUR S A TIS FA C TION FIRS T¡­
C ¨C To allow remote operation¡­
?The thermo fuses will override the remote operation to
automatically close the disc in case of fire detection.
? For further security , our automatic
shut off device is fully enclosed and
factory sealed to avoid being
tampered with.

? All our Firestop can
be equipped with this
option at a later stage




                                         YOUR S A TIS FA C TION FIRS T¡­
C ¨C To allow remote operation¡­
To enhance safety our Firestops are factory equipped with
local disc position indicator to provide local information to
your on site operator




                            Disc

                   Open            Closed

                                       YOUR S A TIS FA C TION FIRS T¡­
C ¨C To allow remote operation¡­


? The Firestop can also be equipped with limit switches (II 2
GD EEX d II CT6) connected to a junction box (enclosure II 2
GD EEX e II T6) so you can get data from our Firestop to your
DCS, to check its disc position or to control other equipments
(for example shut down of a pump when the disc is closed ).




                                       YOUR S A TIS FA C TION FIRS T¡­
C ¨C To allow remote operation¡­




     Firestop complete with lid position indicator, remote
     controlled drive, limit switch and junction box

                                  YOUR S A TIS FA C TION FIRS T¡­
D ¨C To be fire safe¡­

? Firestop complies with BS
6755 fire test (equivalent to
API 607 3rd edition or ISO
10497:2004 ), holding leakage
at least 30 minutes.




                                YOUR S A TIS FA C TION FIRS T¡­
D ¨C To be fire safe¡­
? It also complies with the
even more stringent French
fire department fire tests
requiring 3 hours holding
time to give firemen more
time to fight the blaze.




                              YOUR S A TIS FA C TION FIRS T¡­
D ¨C To be fire safe
Test results BS 6755 part 2 (API 607 3rd edition)

                                      API 607                Data recorded
                                     Requirments     30 min test       3 hours test
  Disc closing time                        -           110 sec           110 sec
  During flame exposure
  Delta P = 1 bar
                    external leaks   < 800 ml/min        0                   0
                    internal leaks   < 3200 ml/min       0                   0

  Correct opening of check                 -         P = 0,8 bar        P= 0,8 bar
  valve with water injection               -         Q= 116 m3/h      Q= 120 m3/h
  After water injection
  Delta P = 1 bar
                    Internal leaks   < 160 ml/min        0                   0
                    External leaks   < 320 ml/min     4 ml/min         130 ml/min

                                                     YOUR S A TIS FA C TION FIRS T¡­
E ¨C To avoid disturbance of
existing process line
? Due to its swing check
valve design (API 6D)
there is no diameter         Tank
                           discharge
reduction in your flow        flow
thus no pressure loss.

? Therefore Firestop can
be installed on your
                           ?Its design (full passage) also
existing tank discharge
                           allows you to use a scrapper,
line without disturbing
                           should you need to clean your
your pumps operation (if
                           process line.
any).
                                       YOUR S A TIS FA C TION FIRS T¡­
F ¨C To allow foam injection through
conduit ¡­            ?Its check valve design
                        also allows you to inject
                        water or foam under 5 bars
                        pressure,     through  the
                        outline line.



                                                  Water / foam
                                                     flow
                       Tank




                              YOUR S A TIS FA C TION FIRS T¡­
G ¨C To allow quick emptying¡­
? We do have a procedure to
manually open our Firestop
with special tools, supplied at
purchase, once the fuses have
blown after a fire.
? But we strongly recommend
to proceed with         extreme
caution and only once the fire
around is totally under control
since    you     ? lost ?    the
automatic shut off advantage
(fuses having melt the first
time).

                                   YOUR S A TIS FA C TION FIRS T¡­
H ¨C To be dedicated to safety¡­
To avoid the safety device to be turned off unintentionally
during tank unloading, the legislator, in France, does not allow
the safety device to be used as process valve .


Therefore depending on your
local legislation we suggest you
installed our Firestop in line with
your process valve.
If needed, we will gladly supply
one as well, from our line of gate
valves.


                                         YOUR S A TIS FA C TION FIRS T¡­
H ¨C To be dedicated to safety¡­




                               In line
                        Firestop for safety
                                and
                       gate valve for process


                       YOUR S A TIS FA C TION FIRS T¡­
III - References
   As of today more than 2500 Firestop have been sold, mainly in France
   and Europe, to tank farm owners such as:




                                           YOUR S A TIS FA C TION FIRS T¡­
IV - Summary
A. Leak free even after 3 hours exposure to fire conditions
B. Totally autonomus shut off once fire heat is detected,
   without any need of an outside source of power
C. Can be closed from remote location
D. Fire safe during 3 hours
E. No disruption of existing process line
F. Possibility to inject foam in the tank trough the process line.
G.Allows quick emptying
H. Dedicated to safety




                                          YOUR S A TIS FA C TION FIRS T¡­
YOUR S A TIS FA C TION FIRS T¡­
YOUR S A TIS FA C TION FIRS T¡­
Thank you

For further information, do not hesitate to contact :
                Francois Guerrero :
                +33 6 84 72 27 83 or
      f-guerrero@oilandgastechnologies.eu




                                 YOUR S A TIS FA C TION FIRS T¡­

More Related Content

Automatic positive safety valve - Firestop - for tank farms

  • 1. Don¡¯t let your tank farm turns¡­ YOUR S A TIS FA C TION FIRS T¡­
  • 2. ±õ²Ô³Ù´Ç¡­ HELL¡­ YOUR S A TIS FA C TION FIRS T¡­
  • 3. To stop the flow of volatile or hazardous fluids from tanks, in a fire Feederstop emergency Firestop situation, by automatically sealing each tank inlet and outlet IN OUT YOUR S A TIS FA C TION FIRS T¡­
  • 4. Product Background In 1993 we sat down with tank farms owners, at their request, to design and manufacture a device complying with French and European safety regulations concerning industrial sites potentially dangerous for the environment in case of accident (EEC Directive n¡ã 82/501/CEE a.k.a. Seveso Directive). Based on ?French tank farms regulations (art 318.21), ?French industrial safety commission requirements (IM art. 17 dated 9/11/89) ? ATEX 94/9/CE (EU directive on equipment and protective systems intended for use in potentially explosive atmospheres) It appeared the most reliable solution was a non return swing check valve used backward. YOUR S A TIS FA C TION FIRS T¡­
  • 5. Regulation requirements Legal mandatory requirements requested the device : ? To keep the inflammable liquid inside the tank to avoid further feeding of the fire in case of piping break down and/or leakage, ? To close down automatically without any human intervention and without depending on external power supply other than the one responsible for the accident. In other words the fire alone should activate the automatic shut down (positively safe), ? To allow remote closing of the device, ? To be fire safe, in compliance with BS 6755, ? To avoid disturbance of existing process line ? To allow injection of foam through conduit ? To allow quick emptying of the tank once the fire is controlled (in case of tank leak for example) ? To be strictly dedicated to safety. YOUR S A TIS FA C TION FIRS T¡­
  • 6. I- Our dedicated solution: FIRESTOP YOUR S A TIS FA C TION FIRS T¡­
  • 7. I- Our dedicated solution: FIRESTOP ? We supply Firestops with nominal diameter ranging from 50 to 600 mm (2 to 24 inches). Other sizes on request ? Possible material : Cast Iron (A 216 gr WCB) or Stainless Steel (A 351 gr CF 3 M) . Other materials on request ? Connections: Flanges (ISO PN 20) ? From DN 450 (18¡¯¡¯) Firestops are equipped with a reduction and a hydraulic flow attenuation rotating shock absorber. system YOUR S A TIS FA C TION FIRS T¡­
  • 8. A ¨C To keep the liquid inside¡­ ? Stellite/stellite tightness (Stellite 6, plasma deposit on seat and disc as per NF EN 15614-7) ? Even though fluid pressure is usually low in the tanks, we use our successful PN20 (#150) swing check valve design issued from our almost 150 years experience manufacturing valves. YOUR S A TIS FA C TION FIRS T¡­
  • 9. B ¨C To close down automatically¡­ (1) (2) ? 3 non ferrous thermo fuses (1) hold the Top disc in a normally open position . view ? These fuses are mounted at the end of the disc holding shaft in an enclosure also including a loaded spring (2). ? When the on site ambient temperature reaches the set up point of 124¡ã C / 255¡ã F (set up as standard; other temp. on request) the fuses become liquid thus releasing the spring which close the disc automatically. YOUR S A TIS FA C TION FIRS T¡­
  • 10. B ¨C To close down automatically¡­ YOUR S A TIS FA C TION FIRS T¡­
  • 11. B ¨C To close down automatically¡­ Thermo fuses showed BEFORE & AFTER the fire test YOUR S A TIS FA C TION FIRS T¡­
  • 12. C ¨C To allow remote operation¡­ ? As an option our Firestop can be equipped with an electromagnetic or a pneumatic drive, allowing closing of the device from a remote location. ?In case of power failure (emergency stop, onsite accident/fire too far to be detected by the fuses,¡­) both drives are fail safe and will make the disc to close thus sealing the tank. YOUR S A TIS FA C TION FIRS T¡­
  • 13. C ¨C To allow remote operation¡­ ?The thermo fuses will override the remote operation to automatically close the disc in case of fire detection. ? For further security , our automatic shut off device is fully enclosed and factory sealed to avoid being tampered with. ? All our Firestop can be equipped with this option at a later stage YOUR S A TIS FA C TION FIRS T¡­
  • 14. C ¨C To allow remote operation¡­ To enhance safety our Firestops are factory equipped with local disc position indicator to provide local information to your on site operator Disc Open Closed YOUR S A TIS FA C TION FIRS T¡­
  • 15. C ¨C To allow remote operation¡­ ? The Firestop can also be equipped with limit switches (II 2 GD EEX d II CT6) connected to a junction box (enclosure II 2 GD EEX e II T6) so you can get data from our Firestop to your DCS, to check its disc position or to control other equipments (for example shut down of a pump when the disc is closed ). YOUR S A TIS FA C TION FIRS T¡­
  • 16. C ¨C To allow remote operation¡­ Firestop complete with lid position indicator, remote controlled drive, limit switch and junction box YOUR S A TIS FA C TION FIRS T¡­
  • 17. D ¨C To be fire safe¡­ ? Firestop complies with BS 6755 fire test (equivalent to API 607 3rd edition or ISO 10497:2004 ), holding leakage at least 30 minutes. YOUR S A TIS FA C TION FIRS T¡­
  • 18. D ¨C To be fire safe¡­ ? It also complies with the even more stringent French fire department fire tests requiring 3 hours holding time to give firemen more time to fight the blaze. YOUR S A TIS FA C TION FIRS T¡­
  • 19. D ¨C To be fire safe Test results BS 6755 part 2 (API 607 3rd edition) API 607 Data recorded Requirments 30 min test 3 hours test Disc closing time - 110 sec 110 sec During flame exposure Delta P = 1 bar external leaks < 800 ml/min 0 0 internal leaks < 3200 ml/min 0 0 Correct opening of check - P = 0,8 bar P= 0,8 bar valve with water injection - Q= 116 m3/h Q= 120 m3/h After water injection Delta P = 1 bar Internal leaks < 160 ml/min 0 0 External leaks < 320 ml/min 4 ml/min 130 ml/min YOUR S A TIS FA C TION FIRS T¡­
  • 20. E ¨C To avoid disturbance of existing process line ? Due to its swing check valve design (API 6D) there is no diameter Tank discharge reduction in your flow flow thus no pressure loss. ? Therefore Firestop can be installed on your ?Its design (full passage) also existing tank discharge allows you to use a scrapper, line without disturbing should you need to clean your your pumps operation (if process line. any). YOUR S A TIS FA C TION FIRS T¡­
  • 21. F ¨C To allow foam injection through conduit ¡­ ?Its check valve design also allows you to inject water or foam under 5 bars pressure, through the outline line. Water / foam flow Tank YOUR S A TIS FA C TION FIRS T¡­
  • 22. G ¨C To allow quick emptying¡­ ? We do have a procedure to manually open our Firestop with special tools, supplied at purchase, once the fuses have blown after a fire. ? But we strongly recommend to proceed with extreme caution and only once the fire around is totally under control since you ? lost ? the automatic shut off advantage (fuses having melt the first time). YOUR S A TIS FA C TION FIRS T¡­
  • 23. H ¨C To be dedicated to safety¡­ To avoid the safety device to be turned off unintentionally during tank unloading, the legislator, in France, does not allow the safety device to be used as process valve . Therefore depending on your local legislation we suggest you installed our Firestop in line with your process valve. If needed, we will gladly supply one as well, from our line of gate valves. YOUR S A TIS FA C TION FIRS T¡­
  • 24. H ¨C To be dedicated to safety¡­ In line Firestop for safety and gate valve for process YOUR S A TIS FA C TION FIRS T¡­
  • 25. III - References As of today more than 2500 Firestop have been sold, mainly in France and Europe, to tank farm owners such as: YOUR S A TIS FA C TION FIRS T¡­
  • 26. IV - Summary A. Leak free even after 3 hours exposure to fire conditions B. Totally autonomus shut off once fire heat is detected, without any need of an outside source of power C. Can be closed from remote location D. Fire safe during 3 hours E. No disruption of existing process line F. Possibility to inject foam in the tank trough the process line. G.Allows quick emptying H. Dedicated to safety YOUR S A TIS FA C TION FIRS T¡­
  • 27. YOUR S A TIS FA C TION FIRS T¡­
  • 28. YOUR S A TIS FA C TION FIRS T¡­
  • 29. Thank you For further information, do not hesitate to contact : Francois Guerrero : +33 6 84 72 27 83 or f-guerrero@oilandgastechnologies.eu YOUR S A TIS FA C TION FIRS T¡­