ANALIZER MEASUREMENT : ENERGY ANALYZER CIRCUTOR AR5-L - A
WITHOUT SOMAR INTEGRA/POWERBOSS 25.15 A
WITH SOMAR INTEGRA/POWERBOSS 20.00 A
% SAVING 20.47 %
ENERGY ALANYZER CIRCUTOR AR5-L -
AMPERE
WITHOUT SOMAR INTEGRA/
POWERBOSS
128.18 A
WITH SOMAR INTEGRA/
POWERBOSS
56.90 A
% SAVING 55.60%
AMPERE
SAVING
20.47%
CURRENT [ AMPERE ] MEASUREMENT - STARTING
ENERGYSAVINGREPORT
TYPE OF SI / PBI			 	 : PBI 37V220-480
SCHEMATIC CONNECTION		 : DIRECT ON LINE CONNECTION
EQUIPMENT 				 : CONVEYOR 37KW
CUSTOMER					: PT SEMEN BATURAJA
TESTING INSTRUMENT			 : CIRCUTOR AR5-L ENERGY ANALYZERR
pg. 1
SOMARINTEGRA/POWERBOSS INSTALLEDATCONVEYOR37KW
CURRENT [ AMPERE ] MEASUREMENT - RUNNING
55.60%
GRAPHICWITHOUT SOMAR INTEGRA/POWERBOSS ANDWITH SOMAR INTEGRA/POWERBOSS
ANALIZER MEASUREMENT : ENERGY ANALYZER CIRCUTOR AR5-L - KW
WITHOUT SOMAR INTEGRA/POWERBOSS 59.80 KW
WITH SOMAR INTEGRA/POWERBOSS 23.11 KW
% SAVING 61.35%
2   
POWER [ KW ] MEASUREMENT - STARTING
ENERGYSAVINGREPORTSOMARINTEGRA/POWERBOSS INSTALLEDATCONVEYOR37KW
TYPE OF SI / PBI			 	 : PBI 37V220-480
SCHEMATIC CONNECTION		 : DIRECT ON LINE CONNECTION
EQUIPMENT 				 : CONVEYOR 37KW
CUSTOMER					: PT SEMEN BATURAJA
TESTING INSTRUMENT			 : CIRCUTOR AR5-L ENERGY ANALYZERR
PT ENERCON EQUIPMENT COMPANY
Gedung Aldevco II - 4th Floor
Jl. Warung Jati Barat Raya No. 75 Jakarta, Indonesia
T: 62 21 7941182 F: 62 21 7941184 W: www.enercon.co.id E: info@enercon.co.id
KW
SAVING
61.35%
   3
K E S I M P U L A N
ENERGYSAVINGREPORTSOMARINTEGRA/POWERBOSS INSTALLEDATCONVEYOR37KW
TYPE OF SI / PBI			 	 : PBI 37V220-480
SCHEMATIC CONNECTION		 : DIRECT ON LINE CONNECTION
EQUIPMENT 				 : CONVEYOR 37KW
CUSTOMER					: PT SEMEN BATURAJA
TESTING INSTRUMENT			 : CIRCUTOR AR5-L ENERGY ANALYZERR
PT ENERCON EQUIPMENT COMPANY
Gedung Aldevco II - 4th Floor
Jl. Warung Jati Barat Raya No. 75 Jakarta, Indonesia
T: 62 21 7941182 F: 62 21 7941184 W: www.enercon.co.id E: info@enercon.co.id
•KW SAVING	
Efisiensi KW akan mengurangi nilai pemakaian KWH (energy listrik) oleh
motor utama, sehingga mengurangi biaya pengeluaran tagihan listrik untuk
motor tersebut.
•KVAR SAVING
Efisiensi KVAR akan mengurangi panas yang timbul akibat adanya losses/
kehilangan daya motor, sehingga dengan berkurangnya KVAR akan
memperpanjang faktor lifetime dari motor dan perbaikan Power factor.
•KVA SAVING
Motor & Peralatan lainnya yang berhubungan (cables, fuses, contactors dan
overloads) akan dialiri oleh arus current yang lebih kecil sehingga tidak akan
mudah rusak dan akan mengurangi biaya maintenance serta mengurangi
biaya beban pinalti KVA (KVA Dis-insentif).
Bagi konsumen yang menggunakan sumber listrik (Power Plant) sendiri atau
generator dengan bahan bakar solar, maka KVA saving ini akan mengurangi
konsumsi pemakaian solar pada saat offload dan meningkatkan kemampuan
generator tersebut untuk beroperasi.
Keuntungan lain yang didapatkan dengan dipasangnya sSOMAR INTEGRA /
POWERBOSS, antara lain:
•SOFT START & SOFT STOP
Proses Start & Stop motor akan lebih halus bila dibandingkan dengan
instalasi motor yang hanya menggunakan Direct on line dan star-delta.
Efeknya adalah tiadanya hentakan saat starting dan proses stop yang tiba-
tiba sehingga komponen mekanikal motor akan lebih tahan lama.
•3 PHASE PROTECTOR
Bila terjadi hilangnya salah satu phase power listrik, maka Powerboss akan
bekerja secara otomatis untuk memutuskan aliran listrik ke motor agar motor
tidak terbakar akibat overload/over

More Related Content

Somar integra industry case semen baturaja conveyor

  • 1. ANALIZER MEASUREMENT : ENERGY ANALYZER CIRCUTOR AR5-L - A WITHOUT SOMAR INTEGRA/POWERBOSS 25.15 A WITH SOMAR INTEGRA/POWERBOSS 20.00 A % SAVING 20.47 % ENERGY ALANYZER CIRCUTOR AR5-L - AMPERE WITHOUT SOMAR INTEGRA/ POWERBOSS 128.18 A WITH SOMAR INTEGRA/ POWERBOSS 56.90 A % SAVING 55.60% AMPERE SAVING 20.47% CURRENT [ AMPERE ] MEASUREMENT - STARTING ENERGYSAVINGREPORT TYPE OF SI / PBI : PBI 37V220-480 SCHEMATIC CONNECTION : DIRECT ON LINE CONNECTION EQUIPMENT : CONVEYOR 37KW CUSTOMER : PT SEMEN BATURAJA TESTING INSTRUMENT : CIRCUTOR AR5-L ENERGY ANALYZERR pg. 1 SOMARINTEGRA/POWERBOSS INSTALLEDATCONVEYOR37KW CURRENT [ AMPERE ] MEASUREMENT - RUNNING 55.60%
  • 2. GRAPHICWITHOUT SOMAR INTEGRA/POWERBOSS ANDWITH SOMAR INTEGRA/POWERBOSS ANALIZER MEASUREMENT : ENERGY ANALYZER CIRCUTOR AR5-L - KW WITHOUT SOMAR INTEGRA/POWERBOSS 59.80 KW WITH SOMAR INTEGRA/POWERBOSS 23.11 KW % SAVING 61.35% 2    POWER [ KW ] MEASUREMENT - STARTING ENERGYSAVINGREPORTSOMARINTEGRA/POWERBOSS INSTALLEDATCONVEYOR37KW TYPE OF SI / PBI : PBI 37V220-480 SCHEMATIC CONNECTION : DIRECT ON LINE CONNECTION EQUIPMENT : CONVEYOR 37KW CUSTOMER : PT SEMEN BATURAJA TESTING INSTRUMENT : CIRCUTOR AR5-L ENERGY ANALYZERR PT ENERCON EQUIPMENT COMPANY Gedung Aldevco II - 4th Floor Jl. Warung Jati Barat Raya No. 75 Jakarta, Indonesia T: 62 21 7941182 F: 62 21 7941184 W: www.enercon.co.id E: info@enercon.co.id KW SAVING 61.35%
  • 3.    3 K E S I M P U L A N ENERGYSAVINGREPORTSOMARINTEGRA/POWERBOSS INSTALLEDATCONVEYOR37KW TYPE OF SI / PBI : PBI 37V220-480 SCHEMATIC CONNECTION : DIRECT ON LINE CONNECTION EQUIPMENT : CONVEYOR 37KW CUSTOMER : PT SEMEN BATURAJA TESTING INSTRUMENT : CIRCUTOR AR5-L ENERGY ANALYZERR PT ENERCON EQUIPMENT COMPANY Gedung Aldevco II - 4th Floor Jl. Warung Jati Barat Raya No. 75 Jakarta, Indonesia T: 62 21 7941182 F: 62 21 7941184 W: www.enercon.co.id E: info@enercon.co.id •KW SAVING Efisiensi KW akan mengurangi nilai pemakaian KWH (energy listrik) oleh motor utama, sehingga mengurangi biaya pengeluaran tagihan listrik untuk motor tersebut. •KVAR SAVING Efisiensi KVAR akan mengurangi panas yang timbul akibat adanya losses/ kehilangan daya motor, sehingga dengan berkurangnya KVAR akan memperpanjang faktor lifetime dari motor dan perbaikan Power factor. •KVA SAVING Motor & Peralatan lainnya yang berhubungan (cables, fuses, contactors dan overloads) akan dialiri oleh arus current yang lebih kecil sehingga tidak akan mudah rusak dan akan mengurangi biaya maintenance serta mengurangi biaya beban pinalti KVA (KVA Dis-insentif). Bagi konsumen yang menggunakan sumber listrik (Power Plant) sendiri atau generator dengan bahan bakar solar, maka KVA saving ini akan mengurangi konsumsi pemakaian solar pada saat offload dan meningkatkan kemampuan generator tersebut untuk beroperasi. Keuntungan lain yang didapatkan dengan dipasangnya sSOMAR INTEGRA / POWERBOSS, antara lain: •SOFT START & SOFT STOP Proses Start & Stop motor akan lebih halus bila dibandingkan dengan instalasi motor yang hanya menggunakan Direct on line dan star-delta. Efeknya adalah tiadanya hentakan saat starting dan proses stop yang tiba- tiba sehingga komponen mekanikal motor akan lebih tahan lama. •3 PHASE PROTECTOR Bila terjadi hilangnya salah satu phase power listrik, maka Powerboss akan bekerja secara otomatis untuk memutuskan aliran listrik ke motor agar motor tidak terbakar akibat overload/over