ݺߣ

ݺߣShare a Scribd company logo
Turbine Controls Limited
Temperature Spread
Monitor
TM41-TSM temperature spread monitor
for gas turbines
Low cost monitor of gas turbine exhaust temperatures.
TemperatureSpreadMonitor
A cost effective solution to gas turbine exhaust temperature
spread monitoring. Monitoring the spread of temperature in the
exhaust gases can lead to early detection of combustor and
burner faults and can prevent catastrophic failure of plant.
The TM41-TSM can be configured to monitor up to 24
thermocouple inputs. Standard versions are available for the
following gas turbines:
RR Avon/RB211/Olympus•	
Ruston TD4000/TB5000/Tornado/Typhoon•	
LM2500/5000/6000/1600•	
GE Frame 3/5/6/7/9•	
Solar Mars/Centaur/Saturn•	
Inputs/Outputs
Inputs:
Up to 24 thermocouple inputs.a)	
8 digital inputs, can be configured for:b)	
alarm/trip inhibit--
Remote alarm accept/reset--
Outputs:
8 Digital outputs, can be configured for:
Alarm initiation--
Trip initiation and indication--
Sensor fault--
Hardware fault--
Functionality
The TM41-TSM is programmed to perform temperature
spread monitoring functions in accordance with engine
manufacturer’s specification.
The functionality for a Rolls Royce Avon, Olympus & RB211
is summarised as:
Signal validation – discount faulty inputs and alarm•	
Calculate average of healthy thermocouples•	
Calculate deviation of individual from average•	
Alarm on deviation exceeding alarm setpoint•	
Trip on deviation exceeding trip set point or number of failed•	
thermocouple inputs exceeds set point
Operator interface
The operator panel is a backlit VGA (120x90mm) graphic
monochrome LCD display with keypad.
Visual display of important parameters to enable the
operator to make quick and informed decisions on the
status of the gas turbine:
Logic I/O status•	
Bar graph and digital display of analogue values•	
Alarm and trip alphanumeric message, time and date stamped•	
Trend plot to view temperatures•	
Commissioning modes to ease fault finding and set up.
Allow forcing of outputs•	
Adjustment of control parameters (gains, setpoints, etc.)•	
The TM41-TSM will interface with the retained or sequence and
unit control devices.
Temperature spread monitor
TM41-TSM temperature spread monitor
for gas turbines
TM41-TSM Temperature spread monitor
Temperature deviation display
Turbine Controls Limited
52, Kenilworth Drive	 T +44 (0)116 271 7248
Oadby, Leicester	 F +44 (0)116 271 7250
LE2 5LG UK	 sales@tcluk.net
Or visit us at www.tcluk.net

More Related Content

TCL Temperature Spread Monitor

  • 1. Turbine Controls Limited Temperature Spread Monitor TM41-TSM temperature spread monitor for gas turbines Low cost monitor of gas turbine exhaust temperatures. TemperatureSpreadMonitor
  • 2. A cost effective solution to gas turbine exhaust temperature spread monitoring. Monitoring the spread of temperature in the exhaust gases can lead to early detection of combustor and burner faults and can prevent catastrophic failure of plant. The TM41-TSM can be configured to monitor up to 24 thermocouple inputs. Standard versions are available for the following gas turbines: RR Avon/RB211/Olympus• Ruston TD4000/TB5000/Tornado/Typhoon• LM2500/5000/6000/1600• GE Frame 3/5/6/7/9• Solar Mars/Centaur/Saturn• Inputs/Outputs Inputs: Up to 24 thermocouple inputs.a) 8 digital inputs, can be configured for:b) alarm/trip inhibit-- Remote alarm accept/reset-- Outputs: 8 Digital outputs, can be configured for: Alarm initiation-- Trip initiation and indication-- Sensor fault-- Hardware fault-- Functionality The TM41-TSM is programmed to perform temperature spread monitoring functions in accordance with engine manufacturer’s specification. The functionality for a Rolls Royce Avon, Olympus & RB211 is summarised as: Signal validation – discount faulty inputs and alarm• Calculate average of healthy thermocouples• Calculate deviation of individual from average• Alarm on deviation exceeding alarm setpoint• Trip on deviation exceeding trip set point or number of failed• thermocouple inputs exceeds set point Operator interface The operator panel is a backlit VGA (120x90mm) graphic monochrome LCD display with keypad. Visual display of important parameters to enable the operator to make quick and informed decisions on the status of the gas turbine: Logic I/O status• Bar graph and digital display of analogue values• Alarm and trip alphanumeric message, time and date stamped• Trend plot to view temperatures• Commissioning modes to ease fault finding and set up. Allow forcing of outputs• Adjustment of control parameters (gains, setpoints, etc.)• The TM41-TSM will interface with the retained or sequence and unit control devices. Temperature spread monitor TM41-TSM temperature spread monitor for gas turbines TM41-TSM Temperature spread monitor Temperature deviation display Turbine Controls Limited 52, Kenilworth Drive T +44 (0)116 271 7248 Oadby, Leicester F +44 (0)116 271 7250 LE2 5LG UK sales@tcluk.net Or visit us at www.tcluk.net