This document provides specifications for an Industrial Diesel Generator Set - B900 50Hz including:
- Generator set ratings of 900kVA (720kWe) for standby use and 818kVA (654kWe) for prime power use
- Technical specifications for the Baudouin 12M26G900 engine such as bore, stroke, speed, fuel system details
- Alternator details including brand, voltage regulation, and harmonic distortion levels
- Dimensional details for the compact and soundproofed versions
- Standard features included with the generator set such as the control panel, enclosure, base frame, and manuals
- Emission compliance and applicable codes and standards
This document provides specifications for an Industrial Diesel Generator Set - KD800-E that is 50Hz, emission optimized and EPA Tier 2 compliant. It produces 800kVA in standby mode and 727kVA in prime power mode. The generator set uses a KOHLER KD series engine and commercial KOHLER alternator. It also lists dimensions, sound levels, fuel consumption and control panel options. Performance data is given for the engine along with cooling system, alternator and acoustic enclosure details.
This document provides specifications for an industrial diesel generator set. It is a 1000 kVA, 800 kWe unit that meets EPA Tier 2 emission standards. It uses a 12 cylinder KOHLER KD series engine. The generator set is available in different enclosure options with sound levels between 77-86 dB(A) at 1 meter depending on the enclosure. It includes standard and optional control panel options to monitor and operate the unit.
This document provides specifications for a Caterpillar 3508B marine engine, including:
- Dimensions such as bore, stroke, displacement and rotation direction
- Performance data across a range of engine speeds including power, torque, fuel consumption and oil change interval
- Component details for the air inlet system, control system, cooling system, exhaust system, flywheels, fuel system, instrumentation, lube system, and protection system
- Curves showing power, torque, fuel consumption rates over engine speeds
- Maximum power and propeller demand ratings at various engine speeds
This document provides specifications for Isuzu's Tier 4 Final diesel engine product line, including the 3C, 3CH, 4LE2, 4LE2X, 4JJ1T, 4JJ1X, 4HK1X, 6HK1X, 6UZ1X, and 6WG1X models. It lists the key features and dimensions of each engine, along with performance curve diagrams and limited warranty information. The models range from 21 horsepower to over 500 horsepower and are used in industrial generator, power unit, and other off-highway applications.
10 ta data sheet - flypartsguy.com - 8.2018FrankEasel
油
This document provides specifications for a Weichai America Corp WP10GTA engine. It includes basic data on displacement, cylinder configuration, aspiration, power ratings, thermal balance, weight and dimensions, cooling system details, lubrication system specs, and fuel consumption curves. The engine is an inline 4-cycle diesel with a bore and stroke of 126mm x 130mm, producing 284.6 kW at 212.2 HP on natural gas and 216.8 kW at 161.7 HP on liquid propane gas under ISO 3046 test conditions.
Passenger Transport Aircraft Concept Design-FinalAlex Esche
油
The document describes the iterative design process for a new long-range aircraft. Over multiple tests, parameters such as fuel capacity, engine type, fuselage length, and wing design were varied to improve performance. The final proposed design incorporates composite materials, advanced systems, and a biofuel blend. It is estimated to extend major maintenance intervals by 25% compared to existing aircraft.
This document contains a proposal from Dana Noavaran Energy & Industry Co. for an 18MW combined heat and power (CHP) generation plant for Khoramshahr Power Plant. It includes specifications and pricing for 9 generator sets, heat recovery systems, cooling systems, lubricating oil systems, fuel gas systems, and other mechanical, electrical, and civil engineering components. It also provides construction, installation, testing, commissioning, and training costs. The total proposed cost is over 10 million Euros.
High performance axial fans are designed to dissipate heat generated by transformer losses while complying with the market requirements and assure fail-safe operations in all industrial zones.
An overview of diagnostic tools used in RESNET testingBill Spohn
油
Learn about the variety of tools and test instruments that apply in RESNET standards 310 (pending) and 380. We'll cover the proper procedures as well as pros and cons of various devices.
Focus areas in economic operation of DG setsD.Pawan Kumar
油
This document discusses options for economic operation of diesel generator sets for captive power generation. It outlines the typical advantages of captive generation such as ensuring power quality and offsetting transmission and distribution losses. It then describes different captive power options available, highlighting that diesel generator sets are attractive due to their low implementation period, efficiency, and investments compared to other options. The document also discusses measures to improve the economic operation of diesel generator sets such as improving loading, parallel operations, maintenance practices, and harnessing waste heat recovery potential.
Hyster u005 (h80 ft) forklift service repair manualfhjsekkemm
油
This document provides specifications for various lift truck models including:
1) Lifting capacities and weights for the H80FT-H120FT and S80FT-S120FT models ranging from 3,629 to 5,443 kg.
2) Tire sizes, engine specifications, fuel capacities, fluid capacities, electrical components, transmission oil pressures, hydraulic relief pressures, and steering details.
3) The document is a service manual containing technical specifications to aid in repair work for these lift truck models.
Yale (j813) gdp45 vx6 lift truck service repair manualfhjskemme
油
This document provides specifications for GLP/GDP40-55VX lift truck models including:
- Lifting capacities ranging from 3,629 to 5,443 kg
- Fuel tank capacities of 79-100.3 liters for various engine and wheelbase configurations
- Transmission, hydraulic, and engine oil specifications and quantities
- Relief valve pressure settings for hydraulic and steering systems
- Dimensions for tires, wheels, and counterweights
- Electrical system details including battery and alternator specifications
Yale (j813) glp40 vx6 lift truck service repair manualfdhjsekdme
油
This document provides specifications for GLP/GDP40-55VX lift truck models including:
- Lifting capacities ranging from 3,629 to 5,443 kg
- Counterweight weights ranging from 2,108 to 3,226 kg
- Tire sizes for drive and steer tires
- Fuel, oil, coolant, and hydraulic tank capacities
- Electrical system specifications including battery, alternator, and ignition
- Transmission and hydraulic system relief pressures
1. Transformers are critical equipment for power generation and distribution, but premature failures can halt production indefinitely since transformers take a long time to manufacture and procure as replacements.
2. Proper maintenance is important to extend the service life of transformers. Factors like age, site conditions, and maintenance history should be considered when developing a cost-effective maintenance strategy.
3. Bushings, oil, and on-load tap changers are some of the parts most prone to failure in transformers. Monitoring techniques like tan delta testing and dissolved gas analysis help detect issues before complete failure occurs.
Furnace Improvements provides low-cost solutions for improving fired heaters and boilers. They have over 15 years of experience and 40 professionals with over 300 years combined experience. Their services include revamping, capacity increase, efficiency improvement, NOx reduction, and heater design. They have successfully completed over 200 projects for clients in refineries and petrochemical plants. Their patented technologies include split flow technology and inclined firing systems to improve heater performance.
Sutherland.Padi Audit Results Hvac.Final.05 Nov 07guest74c3c1
油
The document provides a summary of findings from an HVAC audit conducted at Sutherland's Padi facility in Chennai. Key findings include:
- Actual capacity utilization of chiller plants, AHUs, and other infrastructure is much lower than installed capacity.
- Several issues were observed with AHUs including lack of filters, damaged components, and improper installation.
- Facility observations revealed unwanted materials, unclean areas, and other maintenance issues.
Recommendations focus on optimization of the HVAC system, changes to distribution, implementing suggested repairs and upgrades, and ongoing maintenance.
This document provides specifications for an Industrial Diesel Generator Set - B1000 50Hz including:
- Power ratings of 1000kVA standby and 909kVA prime
- Technical details on the Baudouin engine, Kohler alternator, cooling and fuel systems
- Dimensions and weights for compact and soundproofed versions
- Performance data at different loads and environmental conditions
- Standard features like the APM403 control panel and protections
- Compliance with international standards for quality and safety
This document provides specifications for an industrial diesel generator set model KD1000-F that produces 1000kVA at 50Hz. It includes details on the generator set such as its engine specifications, alternator specifications, fuel consumption, dimensions, noise levels, and optional control panel models. The generator set is designed to have high reliability and performance for applications such as data centers or mission critical systems.
This document provides specifications for an Industrial Diesel Generator Set - D830 operating at 50 Hz. It includes details on:
- Generator ratings of 825 kVA (Standby) and 750 kVA (Prime)
- Engine specifications including the brand, model, power output, cooling system, and emissions level
- Alternator specifications including the brand, insulation class, voltage regulation, and harmonics
- Control panel options including the APM303, APM403, and APM802
- Dimensions and sound levels for both compact and soundproofed versions
- Standard features and scope of supply
This document provides specifications for an Industrial Diesel Generator Set - T16K 50 Hz. It includes details on the generator set such as its ratings, engine specifications, alternator specifications, dimensions, and standard scope of supply. The generator set has a standby rating of 16 kVA and 50 Hz frequency. It is powered by a Mitsubishi engine and has a KOHLER alternator. Standard control panel options include basic terminal block, M80, APM303, and APM403.
This document provides technical specifications for a 750 kVA diesel generator set including:
1) Generator output voltages and frequencies at 50Hz and 60Hz, motor starting capabilities, and alternator performance data.
2) Protections and features of the generator controller.
3) Engine specifications including model, displacement, emissions compliance, and fuel consumption rates.
4) Dimensions and shipping data for the generator enclosure.
5) Cooling system details including radiator specifications and cooling airflow.
This document provides specifications for an FPI 800P generator including:
- KW and KVA ratings at 50Hz and 60Hz frequencies and 0.8 power factor.
- Prime and standby power ratings defined.
- Technical data for the Perkins 4006-23TAG3A engine including displacement, speed, emissions regulations, and fuel consumption.
This document provides specifications for an FPI 750P generator set including:
- KW/KVA ratings at 50Hz and 60Hz frequencies and 0.8 power factor
- Prime and standby power ratings defined
- Engine model, displacement, speed, cooling details
- Alternator model, voltage, frequency, performance data
- Enclosure details, dimensions, weights
- Controller model and protections included
This document provides specifications for an FPI 1000P generator set including:
- Power ratings of 1000kVA at 50Hz and 995.2kVA at 60Hz at 0.8 power factor
- Prime and standby power definitions and usage limitations
- Engine model, speed, cooling and lubrication details
- Alternator model, voltage regulation, and performance data
- Standard enclosure dimensions and optional enhanced enclosure specifications
This document provides specifications for multiple models of 3-phase diesel generators from DAEJINGENERATORSYSTEMS. For each model (DJG-020 through DJG-130), it lists the generator's weight, dimensions, power ratings at 60Hz and 50Hz, engine details including the manufacturer and model, and general specifications. It also provides contact information for the manufacturer's head office and factory.
This document provides specifications for a 1000REOZM diesel generator set including:
- Ratings for standby and prime power outputs between 1010-1020kW and 920-925kW respectively
- Features a 4-cycle, 12 cylinder turbocharged engine certified to EPA Tier 1 emissions standards
- The brushless alternator is rated for 125属C temperature rise and provides precise voltage regulation
- Standard features include an electronic governor, pilot-excited PMG, and one year limited warranty with extended options
This document provides specifications for an AVP694-6 generator set manufactured by AKSA Power Generation. It includes:
- Technical details on the Volvo engine, Stamford alternator, and DSE control panel components of the generator set.
- Dimensions and weights for the unit in both an enclosed and open skid configuration.
- Performance details like fuel consumption rates, sound levels, and voltage regulation capabilities.
- Standard features like the base fuel tank, battery charger, and residential grade silencer.
- Optional accessories available for custom configurations.
This document provides specifications for a Kohler 150REOZJF diesel generator set. It lists standard features such as one-source responsibility from Kohler, prototype and factory testing, UL2200 listing, load acceptance in one step, and NFPA110 compliance when equipped with accessories. It also details optional extended warranties. Technical specifications are provided for the alternator such as excitation system, insulation class, and temperature rise. Engine specifications include the John Deere model, fuel system, cooling system, lubrication system, and electrical system. Controller options are also summarized. Overall dimensions and wet weight are listed at the end.
This document provides specifications for a 1800REOZM diesel generator set. It includes:
- Ratings for the standby and prime power outputs between 1580-1596kW and 1440-1452kW respectively
- Standard features like a one-year warranty, brushless generator, and electronic governor
- Technical details on the generator, engine, cooling system, fuel system, lubrication system, electrical system, and dimensions
- Optional accessories available for the generator set like exhaust silencers, battery chargers, and paralleling systems
This document provides specifications for a 1600REOZM generator set including:
- Ratings for standby and prime power output between 1380-1630 kW
- It is a 4-cycle, turbocharged diesel generator set with a 60Hz or 50Hz output
- Standard features include a one-year warranty, EPA emissions compliance, and digital voltage regulation
An overview of diagnostic tools used in RESNET testingBill Spohn
油
Learn about the variety of tools and test instruments that apply in RESNET standards 310 (pending) and 380. We'll cover the proper procedures as well as pros and cons of various devices.
Focus areas in economic operation of DG setsD.Pawan Kumar
油
This document discusses options for economic operation of diesel generator sets for captive power generation. It outlines the typical advantages of captive generation such as ensuring power quality and offsetting transmission and distribution losses. It then describes different captive power options available, highlighting that diesel generator sets are attractive due to their low implementation period, efficiency, and investments compared to other options. The document also discusses measures to improve the economic operation of diesel generator sets such as improving loading, parallel operations, maintenance practices, and harnessing waste heat recovery potential.
Hyster u005 (h80 ft) forklift service repair manualfhjsekkemm
油
This document provides specifications for various lift truck models including:
1) Lifting capacities and weights for the H80FT-H120FT and S80FT-S120FT models ranging from 3,629 to 5,443 kg.
2) Tire sizes, engine specifications, fuel capacities, fluid capacities, electrical components, transmission oil pressures, hydraulic relief pressures, and steering details.
3) The document is a service manual containing technical specifications to aid in repair work for these lift truck models.
Yale (j813) gdp45 vx6 lift truck service repair manualfhjskemme
油
This document provides specifications for GLP/GDP40-55VX lift truck models including:
- Lifting capacities ranging from 3,629 to 5,443 kg
- Fuel tank capacities of 79-100.3 liters for various engine and wheelbase configurations
- Transmission, hydraulic, and engine oil specifications and quantities
- Relief valve pressure settings for hydraulic and steering systems
- Dimensions for tires, wheels, and counterweights
- Electrical system details including battery and alternator specifications
Yale (j813) glp40 vx6 lift truck service repair manualfdhjsekdme
油
This document provides specifications for GLP/GDP40-55VX lift truck models including:
- Lifting capacities ranging from 3,629 to 5,443 kg
- Counterweight weights ranging from 2,108 to 3,226 kg
- Tire sizes for drive and steer tires
- Fuel, oil, coolant, and hydraulic tank capacities
- Electrical system specifications including battery, alternator, and ignition
- Transmission and hydraulic system relief pressures
1. Transformers are critical equipment for power generation and distribution, but premature failures can halt production indefinitely since transformers take a long time to manufacture and procure as replacements.
2. Proper maintenance is important to extend the service life of transformers. Factors like age, site conditions, and maintenance history should be considered when developing a cost-effective maintenance strategy.
3. Bushings, oil, and on-load tap changers are some of the parts most prone to failure in transformers. Monitoring techniques like tan delta testing and dissolved gas analysis help detect issues before complete failure occurs.
Furnace Improvements provides low-cost solutions for improving fired heaters and boilers. They have over 15 years of experience and 40 professionals with over 300 years combined experience. Their services include revamping, capacity increase, efficiency improvement, NOx reduction, and heater design. They have successfully completed over 200 projects for clients in refineries and petrochemical plants. Their patented technologies include split flow technology and inclined firing systems to improve heater performance.
Sutherland.Padi Audit Results Hvac.Final.05 Nov 07guest74c3c1
油
The document provides a summary of findings from an HVAC audit conducted at Sutherland's Padi facility in Chennai. Key findings include:
- Actual capacity utilization of chiller plants, AHUs, and other infrastructure is much lower than installed capacity.
- Several issues were observed with AHUs including lack of filters, damaged components, and improper installation.
- Facility observations revealed unwanted materials, unclean areas, and other maintenance issues.
Recommendations focus on optimization of the HVAC system, changes to distribution, implementing suggested repairs and upgrades, and ongoing maintenance.
This document provides specifications for an Industrial Diesel Generator Set - B1000 50Hz including:
- Power ratings of 1000kVA standby and 909kVA prime
- Technical details on the Baudouin engine, Kohler alternator, cooling and fuel systems
- Dimensions and weights for compact and soundproofed versions
- Performance data at different loads and environmental conditions
- Standard features like the APM403 control panel and protections
- Compliance with international standards for quality and safety
This document provides specifications for an industrial diesel generator set model KD1000-F that produces 1000kVA at 50Hz. It includes details on the generator set such as its engine specifications, alternator specifications, fuel consumption, dimensions, noise levels, and optional control panel models. The generator set is designed to have high reliability and performance for applications such as data centers or mission critical systems.
This document provides specifications for an Industrial Diesel Generator Set - D830 operating at 50 Hz. It includes details on:
- Generator ratings of 825 kVA (Standby) and 750 kVA (Prime)
- Engine specifications including the brand, model, power output, cooling system, and emissions level
- Alternator specifications including the brand, insulation class, voltage regulation, and harmonics
- Control panel options including the APM303, APM403, and APM802
- Dimensions and sound levels for both compact and soundproofed versions
- Standard features and scope of supply
This document provides specifications for an Industrial Diesel Generator Set - T16K 50 Hz. It includes details on the generator set such as its ratings, engine specifications, alternator specifications, dimensions, and standard scope of supply. The generator set has a standby rating of 16 kVA and 50 Hz frequency. It is powered by a Mitsubishi engine and has a KOHLER alternator. Standard control panel options include basic terminal block, M80, APM303, and APM403.
This document provides technical specifications for a 750 kVA diesel generator set including:
1) Generator output voltages and frequencies at 50Hz and 60Hz, motor starting capabilities, and alternator performance data.
2) Protections and features of the generator controller.
3) Engine specifications including model, displacement, emissions compliance, and fuel consumption rates.
4) Dimensions and shipping data for the generator enclosure.
5) Cooling system details including radiator specifications and cooling airflow.
This document provides specifications for an FPI 800P generator including:
- KW and KVA ratings at 50Hz and 60Hz frequencies and 0.8 power factor.
- Prime and standby power ratings defined.
- Technical data for the Perkins 4006-23TAG3A engine including displacement, speed, emissions regulations, and fuel consumption.
This document provides specifications for an FPI 750P generator set including:
- KW/KVA ratings at 50Hz and 60Hz frequencies and 0.8 power factor
- Prime and standby power ratings defined
- Engine model, displacement, speed, cooling details
- Alternator model, voltage, frequency, performance data
- Enclosure details, dimensions, weights
- Controller model and protections included
This document provides specifications for an FPI 1000P generator set including:
- Power ratings of 1000kVA at 50Hz and 995.2kVA at 60Hz at 0.8 power factor
- Prime and standby power definitions and usage limitations
- Engine model, speed, cooling and lubrication details
- Alternator model, voltage regulation, and performance data
- Standard enclosure dimensions and optional enhanced enclosure specifications
This document provides specifications for multiple models of 3-phase diesel generators from DAEJINGENERATORSYSTEMS. For each model (DJG-020 through DJG-130), it lists the generator's weight, dimensions, power ratings at 60Hz and 50Hz, engine details including the manufacturer and model, and general specifications. It also provides contact information for the manufacturer's head office and factory.
This document provides specifications for a 1000REOZM diesel generator set including:
- Ratings for standby and prime power outputs between 1010-1020kW and 920-925kW respectively
- Features a 4-cycle, 12 cylinder turbocharged engine certified to EPA Tier 1 emissions standards
- The brushless alternator is rated for 125属C temperature rise and provides precise voltage regulation
- Standard features include an electronic governor, pilot-excited PMG, and one year limited warranty with extended options
This document provides specifications for an AVP694-6 generator set manufactured by AKSA Power Generation. It includes:
- Technical details on the Volvo engine, Stamford alternator, and DSE control panel components of the generator set.
- Dimensions and weights for the unit in both an enclosed and open skid configuration.
- Performance details like fuel consumption rates, sound levels, and voltage regulation capabilities.
- Standard features like the base fuel tank, battery charger, and residential grade silencer.
- Optional accessories available for custom configurations.
This document provides specifications for a Kohler 150REOZJF diesel generator set. It lists standard features such as one-source responsibility from Kohler, prototype and factory testing, UL2200 listing, load acceptance in one step, and NFPA110 compliance when equipped with accessories. It also details optional extended warranties. Technical specifications are provided for the alternator such as excitation system, insulation class, and temperature rise. Engine specifications include the John Deere model, fuel system, cooling system, lubrication system, and electrical system. Controller options are also summarized. Overall dimensions and wet weight are listed at the end.
This document provides specifications for a 1800REOZM diesel generator set. It includes:
- Ratings for the standby and prime power outputs between 1580-1596kW and 1440-1452kW respectively
- Standard features like a one-year warranty, brushless generator, and electronic governor
- Technical details on the generator, engine, cooling system, fuel system, lubrication system, electrical system, and dimensions
- Optional accessories available for the generator set like exhaust silencers, battery chargers, and paralleling systems
This document provides specifications for a 1600REOZM generator set including:
- Ratings for standby and prime power output between 1380-1630 kW
- It is a 4-cycle, turbocharged diesel generator set with a 60Hz or 50Hz output
- Standard features include a one-year warranty, EPA emissions compliance, and digital voltage regulation
This document provides specifications for an FPI 660P generator set including:
- KW and KVA ratings at 50Hz and 60Hz frequencies and 0.8 power factor.
- Definitions of prime power and standby power ratings.
- Engine speed, fuel consumption, cooling airflow, and other engine data.
- Alternator model number, voltage, KVA rating, and performance data.
- Enclosure dimensions and weights for open and enclosed options.
- Generator protection features including over/under voltage, frequency, and current.
- Controller model with features like event logging, analog/digital inputs/outputs.
This document provides technical specifications and performance data for a BITZER 4DES-7Y semi-hermetic reciprocating compressor, including:
- Cooling capacity, power input, current draw, and COP/EER performance metrics at various operating conditions
- Dimensional drawings and connection port locations
- Motor specifications, enclosure rating, vibration dampers, and protection devices included
It also includes recommendations for an F302H horizontal liquid receiver to pair with the compressor, with dimensional drawings and specifications for the receiver. An IQ MODULE control system is summarized with its standard sensors, communication interfaces, and enclosure rating to provide monitoring and protection functions for the compressor.
This document provides specifications for the Honny Googol 2000kW/2500kVA diesel generator. Key details include:
- The generator is powered by a Guangdong Honny Power tech Co. QTA5400G1 water cooled diesel engine.
- It has a prime power rating of 2000kW/2500kVA and can provide up to 2280kW in standby mode.
- Additional specifications cover the engine, alternator, cooling and electrical systems, dimensions, and optional accessories.
This document provides specifications for a 2000REOZM generator set model. It includes details on:
- Standard features like one-source responsibility, prototype testing, EPA emissions compliance, and warranty options
- Electrical specifications of the alternator and generator
- Engine details including the model, fuel system, cooling system, and emissions compliance
- Operation requirements around air flow, fuel consumption, and environmental conditions
- Controller features and available accessories
This document provides specifications for a 1500REOZM diesel generator set. It includes details on:
- Ratings for standby and prime power output in kW and kVA at 60Hz and 50Hz frequencies
- Alternator specifications including voltage, phase, and cooling rise ratings
- Engine specifications including model, type, displacement, ratings, and cooling/fuel systems
- Standard features such as one-source responsibility, prototype testing, transient performance compliance
- Optional accessories for the open unit, cooling, fuel, electrical, and control systems
How to Configure Restaurants in Odoo 17 Point of SaleCeline George
油
Odoo, a versatile and integrated business management software, excels with its robust Point of Sale (POS) module. This guide delves into the intricacies of configuring restaurants in Odoo 17 POS, unlocking numerous possibilities for streamlined operations and enhanced customer experiences.
QuickBooks Desktop to QuickBooks Online How to Make the MoveTechSoup
油
If you use QuickBooks Desktop and are stressing about moving to QuickBooks Online, in this webinar, get your questions answered and learn tips and tricks to make the process easier for you.
Key Questions:
* When is the best time to make the shift to QuickBooks Online?
* Will my current version of QuickBooks Desktop stop working?
* I have a really old version of QuickBooks. What should I do?
* I run my payroll in QuickBooks Desktop now. How is that affected?
*Does it bring over all my historical data? Are there things that don't come over?
* What are the main differences between QuickBooks Desktop and QuickBooks Online?
* And more
Computer Application in Business (commerce)Sudar Sudar
油
The main objectives
1. To introduce the concept of computer and its various parts. 2. To explain the concept of data base management system and Management information system.
3. To provide insight about networking and basics of internet
Recall various terms of computer and its part
Understand the meaning of software, operating system, programming language and its features
Comparing Data Vs Information and its management system Understanding about various concepts of management information system
Explain about networking and elements based on internet
1. Recall the various concepts relating to computer and its various parts
2 Understand the meaning of softwares, operating system etc
3 Understanding the meaning and utility of database management system
4 Evaluate the various aspects of management information system
5 Generating more ideas regarding the use of internet for business purpose
Digital Tools with AI for e-Content Development.pptxDr. Sarita Anand
油
This ppt is useful for not only for B.Ed., M.Ed., M.A. (Education) or any other PG level students or Ph.D. scholars but also for the school, college and university teachers who are interested to prepare an e-content with AI for their students and others.
How to Manage Putaway Rule in Odoo 17 InventoryCeline George
油
Inventory management is a critical aspect of any business involved in manufacturing or selling products.
Odoo 17 offers a robust inventory management system that can handle complex operations and optimize warehouse efficiency.
Useful environment methods in Odoo 18 - Odoo 際際滷sCeline George
油
In this slide well discuss on the useful environment methods in Odoo 18. In Odoo 18, environment methods play a crucial role in simplifying model interactions and enhancing data processing within the ORM framework.
Reordering Rules in Odoo 17 Inventory - Odoo 際際滷sCeline George
油
In Odoo 17, the Inventory module allows us to set up reordering rules to ensure that our stock levels are maintained, preventing stockouts. Let's explore how this feature works.
Prelims of Kaun TALHA : a Travel, Architecture, Lifestyle, Heritage and Activism quiz, organized by Conquiztadors, the Quiz society of Sri Venkateswara College under their annual quizzing fest El Dorado 2025.
Prelims of Rass MELAI : a Music, Entertainment, Literature, Arts and Internet Culture Quiz organized by Conquiztadors, the Quiz society of Sri Venkateswara College under their annual quizzing fest El Dorado 2025.
1. Industrial Diesel Generator Set B900
50 Hz
Reference Conditions: 25属C Air Inlet Temperature, 40属C Fuel Inlet Temperature, 100 kPa Barometric Pressure; 10.7 g/kg of dry air Humidity. Intake Restriction
set to maximum allowable limit for clean filter; Exhaust Back pressure set to maximum allowable limit.
Data was taken from a single engine test according to the test methods, fuel specification and reference conditions stated above and is subjected to
instrumentation and engine-to-engine variability. Test conducted with alternate test methods, instrumentation, fuel or reference conditions can yield
different results. Data and specifications subject to change without notice.
RATINGS 400 V - 50 Hz
kVA 900
Standby
kWe 720
kVA 818
Prime
kWe 654
GENERAL SPECIFICATIONS
Engine brand BAUDOUIN
Alternator commercial brand KOHLER
Voltage (V) 400/230
Standard Control Panel APM403
Consumption @ 100% load ESP (L/h) 188
Consumption @ 100% load PRP (L/h) 170
Emission level Fuel consumption optimization
Type of Cooling Mechanical driven fan
Performance class G2
GENERATOR SETS RATINGS
Standby Rating Prime Rating
Voltage PH Hz kWe kVA Amps kWe kVA
415/240 3 50 690 863 1201 628 785
400/230 3 50 720 900 1299 654 818
B900
380/220 3 50 720 900 1367 654 818
Benefits & features
KOHLER SDMO premium quality
KOHLER SDMO provides one source responsibility for
the generating set and accessories
The generator set, its components and a wide range of
options have been fully developed, prototype tested,
factory built, and production tested
The generator sets are designed in accordance to
ISO8528
KOHLER SDMO premium performances
Engines
High reliability enhanced through a simple design for
optimal functional performances
High performances turbochargers providing high engine
performances under all loads
Easy operation and maintenance: accessories requiring
daily maintenance are conveniently located on the same
side of the engine
Alternator
Provide industry leading motor starting capability
Excitation system to permit sustained overcurrent >
300% In, during 10 sec
Built with a class H insulation and IP23
Cooling
A compact and complete solution using a mechanical
driven fan radiator
High temperature and altitude product capacity
available
Control Panel
The KOHLER SDMO wide controller range provides the
reliability and performances you expect from your
equipment. You can program, manage and diagnose it
easily and in an efficient way
KOHLER SDMO worldwide support
A standard two-year or 1000-hours limited warranty for
standby applications.
A standard one-year or 2500 hours limited warranty for
prime power applications.
A worldwide product support
DIMENSIONS COMPACT VERSION
Length (mm) 4417
Width (mm) 1740
Height (mm) 2384
Tank capacity (L) 500
Dry weight (kg) 7470
DIMENSIONS SOUNDPROOFED VERSION M427SI
Type soundproofing M427SI
Length (mm) 6413
Width (mm) 2160
Height (mm) 2753
Tank capacity (L) 1035
Dry weight (kg) 9700
Acoustic pressure level @1m in dB(A) 50Hz
(75% PRP)
86
Acoustic pressure level @7m in dB(A) 50Hz
(75% PRP)
77
2. Industrial Diesel Generator Set B900
50 Hz
Reference Conditions: 25属C Air Inlet Temperature, 40属C Fuel Inlet Temperature, 100 kPa Barometric Pressure; 10.7 g/kg of dry air Humidity. Intake Restriction
set to maximum allowable limit for clean filter; Exhaust Back pressure set to maximum allowable limit.
Data was taken from a single engine test according to the test methods, fuel specification and reference conditions stated above and is subjected to
instrumentation and engine-to-engine variability. Test conducted with alternate test methods, instrumentation, fuel or reference conditions can yield
different results. Data and specifications subject to change without notice.
Engine
General
Engine brand BAUDOUIN
Engine ref. 12M26G900_5 *
Air inlet system Turbo
Fuel Diesel Fuel
Emission level
Fuel consumption
optimization
Cylinder configuration V
Number of cylinders 12
Displacement (l) 31,81
Bore (mm) * Stroke (mm) 150 * 150
Compression ratio 15.7 : 1
Speed (RPM) 1500
Maximum stand-by power at rated RPM (kW) 793
Charge Air coolant Air/Air
Injection Type Direct
Governor type Electronic
Air cleaner type, models Dry
Fuel system
Maximum fuel pump flow (l/h) 595
Fuel Inlet Minimum recommended size (mm) 14
Fuel Outlet Minimum recommended size (mm) 14
Max head on fuel return line (m) 5,90
Maximum allowed inlet fuel temperature (属C) 70
Consumption with cooling system
Specific consumption @ ESP Max Power
(g/kW.h)
202,10
Specific consumption @ PRP Max Power
(g/kW.h)
201,30
Specific consumption @ 75% of PRP Power
(g/kW.h)
205,60
Specific consumption @ 50% of PRP Power
(g/kW.h)
210,50
Lubrication System
Oil system capacity including filters (l) 114
Min. oil pressure (bar) 2
Max. oil pressure (bar) 7
Oil sump capacity (l) 109
Oil consumption 100% ESP 50Hz (l/h) 0,5660
Air Intake system
Max. intake restriction (mm H2O) 663
Combustion air flow (l/s) 1000
Exhaust system
PRP ESP
Exhaust gas temperature (属C) 550 550
Exhaust gas flow (L/s) 2298 2245
Max. exhaust back pressure (mm H2O) 765
Cooling system
Radiator & Engine capacity (l) 108
Fan power 50Hz (kW) 30
Fan air flow w/o restriction (m3/s) 24
Available restriction on air flow (mm H2O) 20
Type of coolant Gencool
Coolant capacity HT, engine only (l) 191
Max coolant temperature, Shutdown (属C) 103
Thermostat begin of opening HT (属C) 77
Thermostat end of opening HT (属C) 87
* Engine reference may be partially modified depending on genset
application, options selected by the customer and lead time required.
3. Industrial Diesel Generator Set B900
50 Hz
Reference Conditions: 25属C Air Inlet Temperature, 40属C Fuel Inlet Temperature, 100 kPa Barometric Pressure; 10.7 g/kg of dry air Humidity. Intake Restriction
set to maximum allowable limit for clean filter; Exhaust Back pressure set to maximum allowable limit.
Data was taken from a single engine test according to the test methods, fuel specification and reference conditions stated above and is subjected to
instrumentation and engine-to-engine variability. Test conducted with alternate test methods, instrumentation, fuel or reference conditions can yield
different results. Data and specifications subject to change without notice.
Alternator Specifications
Alternator commercial brand KOHLER
Kohler Alternator description KH02970T
Number of pole 4
Number of bearing Single Bearing
Technology Brushless
Indication of protection IP23
Insulation class H
Number of wires 12
AVR Regulation Yes
Coupling Direct
Capacity for maintaining short circuit
at 3 ln for 10 s
Yes
Application data
Overspeed (rpm) 2250
Power factor (Cos Phi) 0,80
Voltage regulation at established
rating (+/- %)
0,50
Wave form : NEMA=TIF <40
Wave form : CEI=FHT <2
Total Harmonic Distortion in no-load
DHT (%)
3,1
Total Harmonic Distortion, on linear
load DHT (%)
2,8
Recovery time (Delta U = 20%
transcient) (ms)
200
Performance datas
Continuous Nominal Rating 40属C
(kVA)
820
Unbalanced load acceptance ratio
(%)
8
Peak motor starting (kVA) based on x% voltage dip power factor at 0.3
Alternator Standard Features
- All models are brushless, rotating-field alternators
- NEMA MG1, IEEE, and ANSI standards compliance for
temperature rise and motor starting
- The AVR voltage regulator provides superior short
circuit capability
- Self-ventilated and dip proof construction
- Sustained short-circuit current of up to 300% of the
rated current for up to 10 seconds
- Superior voltage waveform
Note: See Alternator Data Sheets for alternator application data
and ratings, efficiency curves, voltage dip with motor starting
curves, and short circuit decrement curves.
4. Industrial Diesel Generator Set B900
50 Hz
Reference Conditions: 25属C Air Inlet Temperature, 40属C Fuel Inlet Temperature, 100 kPa Barometric Pressure; 10.7 g/kg of dry air Humidity. Intake Restriction
set to maximum allowable limit for clean filter; Exhaust Back pressure set to maximum allowable limit.
Data was taken from a single engine test according to the test methods, fuel specification and reference conditions stated above and is subjected to
instrumentation and engine-to-engine variability. Test conducted with alternate test methods, instrumentation, fuel or reference conditions can yield
different results. Data and specifications subject to change without notice.
Dimensions compact version with baseframe fuel tank
Length (mm) * Width (mm) * Height (mm) 4417 * 1740 * 2384
Dry weight (kg) 7470
Tank capacity (L) 500
Dimensions soundproofed version
M427SI
Length (mm) * Width (mm) * Height (mm) 6413 * 2160 * 2753
Dry weight (kg) 9700
Tank capacity (L) 1035
Acoustic pressure level @1m in dB(A) 50Hz (75% PRP) 86
Sound power level guaranteed (Lwa) 50Hz (75% PRP) 107
Acoustic pressure level @7m in dB(A) 50Hz (75% PRP) 77
5. Industrial Diesel Generator Set B900
50 Hz
Reference Conditions: 25属C Air Inlet Temperature, 40属C Fuel Inlet Temperature, 100 kPa Barometric Pressure; 10.7 g/kg of dry air Humidity. Intake Restriction
set to maximum allowable limit for clean filter; Exhaust Back pressure set to maximum allowable limit.
Data was taken from a single engine test according to the test methods, fuel specification and reference conditions stated above and is subjected to
instrumentation and engine-to-engine variability. Test conducted with alternate test methods, instrumentation, fuel or reference conditions can yield
different results. Data and specifications subject to change without notice.
APM403
BASIC GENERATING SET AND POWER PLANT CONTROL
The APM403 is a versatile control unit which allows operation in manual or
automatic mode
- Measurements : voltage and current
- kW/kWh/kVA power meters
- Standard specifications: Voltmeter, Frequency meter.
- Optional : Battery ammeter.
- J1939 CAN ECU engine control
- Alarms and faults: Oil pressure, Coolant temperature, Overspeed, Start-
up failure, alternator min/max, Emergency stop button.
- Engine parameters: Fuel level, hour counter, battery voltage.
- Optional (standard at 24V): Oil pressure, water temperature.
- Event log/ Management of the last 300 genset events.
- Mains and genset protection
- Clock management
- USB connections, USB Host and PC,
- Communications : RS485 INTERFACE
- ModBUS protocol /SNMP
- Optional : Ethernet, GPRS, remote control, 3G, 4G,
- Websupervisor, SMS, E-mails
6. Industrial Diesel Generator Set B900
50 Hz
Reference Conditions: 25属C Air Inlet Temperature, 40属C Fuel Inlet Temperature, 100 kPa Barometric Pressure; 10.7 g/kg of dry air Humidity. Intake Restriction
set to maximum allowable limit for clean filter; Exhaust Back pressure set to maximum allowable limit.
Data was taken from a single engine test according to the test methods, fuel specification and reference conditions stated above and is subjected to
instrumentation and engine-to-engine variability. Test conducted with alternate test methods, instrumentation, fuel or reference conditions can yield
different results. Data and specifications subject to change without notice.
STANDARD DELIVERY
All our gensets are fitted with:
- Industrial water-cooled DIESEL engine
- Electric starter & charge alternator
- Standard air filter
- Electric circuit breaker, adapted to the short-circuit current of the generating set
- Single bearing alternator IP 23 T属 rise/ insulation to class H/H
- Welded steel base frame with 85% vibration attenuation mounts
- frame height optimized to allow it to be moved safely by forklift
- enclosure made of new high-quality European steel with enhanced corrosion resistance
- enclosures and base frames tested and analyzed by the French Corrosion Institut
- 100% of tanks tested for permeability
- Personal protection ensured by protective grilles on hot and rotating parts
- Separate 9 dB(A) silencer
- Fuel tank welded inside the genset frame
- Retention bund included for gensets up to 250 kVA ESP
- Charged DC starting battery with electrolyte
- Emergency stop button on the outside
- Flexible fuel lines & lub oil drain cock
- Exhaust outlet with flexible and flanges
- Users manual (1 copy)
- Packing under plastic film
- Delivered with oil and antifreeze liquid
CODES AND STANDARDS
Engine-generators set is designed and manufactured in facilities certified to standards ISO9001:2015 & ISO14001:2015. The generator sets and
its components are prototype-tested, factory built and production tested and are in compliance with the relevant standards:
- Machinery Directive 2006/42/EC of May 17th 2006
- EMC Directive2014/30/UE
- Safety objectives set out in the Low Voltage Directive 2014/35/UE
- EN ISO 8528-13, EN 60034-1, EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 55011, EN 1679-1 et EN 60204-1
7. Industrial Diesel Generator Set B900
50 Hz
Reference Conditions: 25属C Air Inlet Temperature, 40属C Fuel Inlet Temperature, 100 kPa Barometric Pressure; 10.7 g/kg of dry air Humidity. Intake Restriction
set to maximum allowable limit for clean filter; Exhaust Back pressure set to maximum allowable limit.
Data was taken from a single engine test according to the test methods, fuel specification and reference conditions stated above and is subjected to
instrumentation and engine-to-engine variability. Test conducted with alternate test methods, instrumentation, fuel or reference conditions can yield
different results. Data and specifications subject to change without notice.
TERMS OF USE
According to the standard, the nominal power assigned by the genset is given for 25属C Air Intlet Temperature, of a barometric pressure of 100
kPA (100 m A.S.L), and 30% relative humidity. For particular conditions in your installation, refer to the derating table.
WARRANTY INFORMATIONS
Standard Warranty Period:
- for Products in "back-up" service
o 30 months from the date the Product leaves the plant
o 24 months from the Products commissioning date
o 1,000 running hours
The warranty expires when one of the above conditions is met.
- for Products in prime or "continuous" service (continuous supply of electricity, either in the absence of any normal electricity grid
or to complement the grid),
o 18 months from the date the Product leaves the plant
o 12 months from the Products commissioning date
o 2,500 running hours
The warranty expires when one of the above conditions is met.
For more details regarding conditions of application and scope of the warranty please refer to our General terms & conditions of sales.