際際滷

際際滷Share a Scribd company logo
DISTRIBUTION SYSTEMS
ELECTRICAL POWER SYSTEM
 The distribution system is a part of the power system, existing between distribution
sub-stations and the consumers.
DISTRIBUTION SYSTEMS
INTRODUCTION(DISTRIBUTION SYSTEMS)
 Distribution systems
To distribute the electric
power among the consumer.
Below a certain voltage
General distribution scheme
Requirements of good distribution systems
 Continuity in the power supply must be ensured.
 Voltage must not vary more than the prescribed limits.(5%).
 Efficiency of line must be high as possible.
 Safe from consumer point of view.
 Layout should not effect the appearance of locality.
 Line should not be overloaded.
Distribution system is further classified on the basis of
voltage
1.primary distribution systems
2.secondary distribution systems
 Primary Distribution:-The part of the electrical-supply system existing between
the distribution substations and the distribution transformers is called the primary
system.
 Secondary Distribution:-The secondary distribution system receives power from
the secondary side of distribution transformers at low voltage and supplies power to
various connected loads via service lines.
Distribution
system
DC
Distribution
system
D.C Three wire
system
1.General
Distribution
system
AC
Distribution
system
Ring main
Distribution
system
Radial
Distribution
system
DC Distribution system 1.General Distribution system
2. D.C Three wire system
1.General Distribution system
 Feeder are used to feed the electrical power
from the generating station to the
substation.
 Distributors are used to distribute the
supply further from the substation.
 Service mains are connected to the
distributors so as to make the supply
available at the consumers.(simplest two
wire distribution system)
2.D.C Three wire system
 Voltage level can not be increased readily like a.c.
 Method:-two generators are connected in series
-each is generating a voltage of V volts
-common point is neutral from where neutral wire is run.
(too expensive , use to double the transmission voltage)
 Demand :-consumers demanding higher voltage are connected to the two lines.
-consumers demanding less voltage are connected between any one line
and neutral.
D.C Three wire system
 Balanced:-One line carries current I1 while
the other current I2.when the load is
balanced(loads connected on either sides of
the neutral wire are equal) .neutral current is
zero.
 Out of balance current:-I1 is greater than
I2 then neutral wire carries current equal to
I1-I2
-I2 is greater than
I1 then neutral wire carries current equal to I2-
I1.
(Direction).neutral potential will not remain
half of that between the 2 lines.
Single generator having twice the line
 Two small d.c machines are connected across
the line in series which are mechanically coupled
to a common shaft . These are called
balancers.
 load is balanced:-machines work as the d.c
motors.
 Out of balance:-machine connected to lightly
loaded side acts as motor , heavily loaded side
acts as generator.
Energy is transferred from lightly loaded side to
heavily loaded side as machine as motor drives the
machine as generator.
AC Distribution system 1.Radial Distribution system
2.Ring main Distribution system
1.Radial Distribution system
 only one/single path is connected between each Distributor and substation is called radial
Distribution system.
 Fault occurs either on feeder or a distributor, all the consumers connected to that distributor
will get affected.
 In India, 99% of
distribution of power
is by radial distribution
system only.
Advantages:
 Its initial cost is minimum.
 Simple in planning, design and operation.
 Useful when the generation is at low voltage..
 Station is located at the center of the load
Disadvantages:
 Distributor nearer to the feeding end is heavily loaded.
 The consumers at the far end of the feeder would be subjected to series voltage
fluctuations with the variations in load.
2.Ring main Distribution system
 Feeder covers the whole area of supply in the ring fashion and finally terminates at
the substation from where it is started.
 Closed loop form and looks like a ring.
Advantages:
 Less conductor material is required as each part of the ring carries less current than
in the radial system.
 Less voltage fluctuations.
Disadvantage:
 It is difficult to design when compared to the designing of a radial system.
Types of D.C Distributors
D.C Distributors
Concentrated
loads
Fed at both the
end
Ends at Unequal
voltages
End at Equal
voltages
Fed at one end
Distributed
loads
Fed at one end
Fed at both the
end
End at Equal
voltages
Ends at Unequal
voltages
 Concentrated loads:-load which are acting at particular points of the distributor are
called concentrated loads.
 Distributed loads:-load which spread over the particular distance of the distributor
are called distributed load.(no load condition practical)
D.C Distributor with Concentrated loads
 Classified 1. Fed at one end
2.Fed at both the ends
1.Fed at one end(Concentrated loads)
 Fed at one end A-A.
 Applying KCL at various points we get,
i1=I1+I2+I3,i2=I2+I3 and i3=I3
 the wire AB is the return wire of the distributor
r=resistance per unit length of conductor in 立
 Voltage drop tabulated as,
section Drop section Drop
Aa i1l1r Aa i1l1r
ab i2(l2-l1)r ab i2(l2-l1)r
bc i3(l3-l2)r bc i3(l3-l2)r
 In practice , the resistance of go and return conductor per unit length is assumed to
be r=2r.
 r1=2r1, r2=2r2, r3=2r3
 The total drop in the distributor is
=r1i1l1+r2i2(l2-l1)+r3i3(l3-l2)
Current loading and voltage drop diagram
2.Fed at both the ends(Concentrated loads)
1.End at Equal voltages
 A and B maintained at equal voltage
 b be the point of minimum potential(the load point where the current are coming
from both the side of distributor is the point of minimum potential.
Let x be supplied by point A
while y be supplied by point B,
y=I2-x
 As both the point A and B are maintained at same voltage, drop in section Aa must
be equal to drop in section Bb.
i1r1+i2r2=i3r3+i4r4
(I1+x)r1+xr2=(I2-x)r3+(I2+I3-x)r4
 All current known ,
x and voltage drop
can be calculated
Current loading and voltage drop diagram
2.Ends at Unequal voltages
 A and B maintained at different voltage
 b be the point of minimum potential.
 Let x be supplied by point A while y be supplied by point B,
y=I2-x
 Voltage drop between A and B = Voltage drop over AB
 If voltage of A is V1 and is greater than voltage of B which is V2 then,
V1-V2=drop in all the section of AB
 The same equation can be written as,
V1-drops over Ab= V2-drops over Bb
V1-i1r1-i2r2=V2-i3r3-i4r4
V1-(I1+x)r1-xr2=V2-(I2-x)r3-(I2+I3-x)r4
Here V1 and V2 are known ,obtain x
Current loading and voltage drop diagram
D.C Distributor with Uniformly Distributed load
 Classified 1. Fed at one end
2.Fed at both the ends
1.Fed at one end (Distributed load )
 Uniformly distributed load on 2 wire distributor , fed at one end
I amperes per meter
Total voltage drop is to be obtained by considering a point C(distance
x),feeding end A
 Current tapped at point C is
=total current  current up to point C=i     =i(l )
 dx near point C , its resistance rdx
dV=i(l-x)rdx
Total voltage drop upto point C
Upto B, x=l
基 =
0

      = 
0

    = ( 
2
2
)0

基=( 
2
2
) volts equation of parabola
基=(   

2
)=ir
2
2
=
1
2
(il)(rl)
基 =
1
2
腫
 Power loss=I2R,elementary length dx
 At point C
X=l
 = [    ]2
 
 =
0

2 2  2 + 2   =  2(2 
22
2
+
3
3
)
 =
23
3
2.Fed at both the ends (Uniformly
Distributed load)
1.End at Equal voltages
fed at point A and B are maintained at equal voltage
The total current to be supplied is il amperes.
As two end voltage are equal ,each end will supply half the required current i.e

2
.
Midpoint distance l/2,point C at a distance x , current feeding is il/2 (A)
Current at C=

2
  = 

2
 
Voltage drop over length dx is,
 = 

2
 Upto point C is,
基 =
0



2
    = 

2

2
2
=

2
[  2]
Maximum voltage drop at midpoint x=l/2
ヰ  = ir
2
4

2
8
=
2
8
=
1
8
  =
腫
8
村 drop of fed at one end
Power loss ,point c
 = [

2
  ]2
 
 = 2

0

2
4
  + 2

 =
2
3
12
 2.Ends at Unequal voltages
 Let point C be the point of minimum potential which at a distance x from feeding point A
 The current supplied by the feeding point A is ix
 The current supplied by the feeding point B is i(l-x)
 V1-drops over AC= V2-drops over BC
 In case of distributed load the drop is given by
2
2
for a length of l
基 =
2
2
p$
巨 =
(  )2
2
p$
1 
2
2
= 2 
(  )2
2
X?
Ring main distributor with interconnection
 Cable is arranged in the Loop fashion,fed at only one point
 Use for large area hence voltage drop across the various section become
larger(excessive voltage drop).
 Solution:-distant point of ring distributor are joined together by a conductor this is
called interconnection.
 Thevenins theorem
 =
乞
 + 倹
AC Distribution
 Advantages of AC
 Cheaper transformation between voltages
 Easy to switch off
 Less equipment needed
 More economical in general
 Rotating field
Methods of solving A.C Distribution problem
 1.power factor referred to receiving end voltage
 Resistance R , reactance X
 Impedance of section PR is given by,  = 1 + 1.
 Impedance of section RQ is given by,  = 2 + 2.
 The load current at point R is 1, 1 = 1(cos 1   sin 1)
 The load current at point Q is 2, 2 = 2(cos 2   sin 2)
 Current in section RQ is nothing but 腫 = 2 = 2(cos 2   sin 2)
 Current in section PR is 腫 = 1 + 2=1(cos 1   sin 1)+2(cos 2   sin 2)
1.power factor referred to receiving end voltage
 Voltage drop in section RQ,  = 腫 
=[2(cos 2   sin 2)].[ 2 + 2]
Voltage drop in section PR ,  = 腫 
=[1(cos 1   sin 1) + 2(cos 2   sin 2)][1 + 1].
Sending end voltage  =  +  + 
Sending end current 腫 = 1 + 2
2. power factor referred to respective load
voltages
 2. power factor referred to respective load voltages
Voltage drop in section RQ is given,  = 2 
=[2(cos 2   sin 2)].[ 2 + 2]
 =  +drop of voltage in section RQ=   留.
1 = 1(cos 1   sin 1) w.r.t voltage 
1 = 1(cos(1留)   sin(1  留)) w.r.t voltage 
腫 = 1 + 2
=1(cos(1留)   sin(1  留)) +2(cos 2   sin 2)
=[1(cos(1留)   sin(1  留)) +2(cos 2   sin 2)].[1 + 1]
Sending end voltage ,  =  +  +
THANK YOU

More Related Content

Distribution System

  • 2. ELECTRICAL POWER SYSTEM The distribution system is a part of the power system, existing between distribution sub-stations and the consumers.
  • 4. INTRODUCTION(DISTRIBUTION SYSTEMS) Distribution systems To distribute the electric power among the consumer. Below a certain voltage General distribution scheme
  • 5. Requirements of good distribution systems Continuity in the power supply must be ensured. Voltage must not vary more than the prescribed limits.(5%). Efficiency of line must be high as possible. Safe from consumer point of view. Layout should not effect the appearance of locality. Line should not be overloaded.
  • 6. Distribution system is further classified on the basis of voltage 1.primary distribution systems 2.secondary distribution systems Primary Distribution:-The part of the electrical-supply system existing between the distribution substations and the distribution transformers is called the primary system. Secondary Distribution:-The secondary distribution system receives power from the secondary side of distribution transformers at low voltage and supplies power to various connected loads via service lines.
  • 8. DC Distribution system 1.General Distribution system 2. D.C Three wire system 1.General Distribution system Feeder are used to feed the electrical power from the generating station to the substation. Distributors are used to distribute the supply further from the substation. Service mains are connected to the distributors so as to make the supply available at the consumers.(simplest two wire distribution system)
  • 9. 2.D.C Three wire system Voltage level can not be increased readily like a.c. Method:-two generators are connected in series -each is generating a voltage of V volts -common point is neutral from where neutral wire is run. (too expensive , use to double the transmission voltage) Demand :-consumers demanding higher voltage are connected to the two lines. -consumers demanding less voltage are connected between any one line and neutral.
  • 10. D.C Three wire system
  • 11. Balanced:-One line carries current I1 while the other current I2.when the load is balanced(loads connected on either sides of the neutral wire are equal) .neutral current is zero. Out of balance current:-I1 is greater than I2 then neutral wire carries current equal to I1-I2 -I2 is greater than I1 then neutral wire carries current equal to I2- I1. (Direction).neutral potential will not remain half of that between the 2 lines.
  • 12. Single generator having twice the line Two small d.c machines are connected across the line in series which are mechanically coupled to a common shaft . These are called balancers. load is balanced:-machines work as the d.c motors. Out of balance:-machine connected to lightly loaded side acts as motor , heavily loaded side acts as generator. Energy is transferred from lightly loaded side to heavily loaded side as machine as motor drives the machine as generator.
  • 13. AC Distribution system 1.Radial Distribution system 2.Ring main Distribution system 1.Radial Distribution system only one/single path is connected between each Distributor and substation is called radial Distribution system. Fault occurs either on feeder or a distributor, all the consumers connected to that distributor will get affected. In India, 99% of distribution of power is by radial distribution system only.
  • 14. Advantages: Its initial cost is minimum. Simple in planning, design and operation. Useful when the generation is at low voltage.. Station is located at the center of the load Disadvantages: Distributor nearer to the feeding end is heavily loaded. The consumers at the far end of the feeder would be subjected to series voltage fluctuations with the variations in load.
  • 15. 2.Ring main Distribution system Feeder covers the whole area of supply in the ring fashion and finally terminates at the substation from where it is started. Closed loop form and looks like a ring.
  • 16. Advantages: Less conductor material is required as each part of the ring carries less current than in the radial system. Less voltage fluctuations. Disadvantage: It is difficult to design when compared to the designing of a radial system.
  • 17. Types of D.C Distributors D.C Distributors Concentrated loads Fed at both the end Ends at Unequal voltages End at Equal voltages Fed at one end Distributed loads Fed at one end Fed at both the end End at Equal voltages Ends at Unequal voltages
  • 18. Concentrated loads:-load which are acting at particular points of the distributor are called concentrated loads. Distributed loads:-load which spread over the particular distance of the distributor are called distributed load.(no load condition practical) D.C Distributor with Concentrated loads Classified 1. Fed at one end 2.Fed at both the ends
  • 19. 1.Fed at one end(Concentrated loads)
  • 20. Fed at one end A-A. Applying KCL at various points we get, i1=I1+I2+I3,i2=I2+I3 and i3=I3 the wire AB is the return wire of the distributor r=resistance per unit length of conductor in 立 Voltage drop tabulated as, section Drop section Drop Aa i1l1r Aa i1l1r ab i2(l2-l1)r ab i2(l2-l1)r bc i3(l3-l2)r bc i3(l3-l2)r
  • 21. In practice , the resistance of go and return conductor per unit length is assumed to be r=2r. r1=2r1, r2=2r2, r3=2r3 The total drop in the distributor is =r1i1l1+r2i2(l2-l1)+r3i3(l3-l2)
  • 22. Current loading and voltage drop diagram
  • 23. 2.Fed at both the ends(Concentrated loads) 1.End at Equal voltages A and B maintained at equal voltage b be the point of minimum potential(the load point where the current are coming from both the side of distributor is the point of minimum potential. Let x be supplied by point A while y be supplied by point B, y=I2-x
  • 24. As both the point A and B are maintained at same voltage, drop in section Aa must be equal to drop in section Bb. i1r1+i2r2=i3r3+i4r4 (I1+x)r1+xr2=(I2-x)r3+(I2+I3-x)r4 All current known , x and voltage drop can be calculated Current loading and voltage drop diagram
  • 25. 2.Ends at Unequal voltages A and B maintained at different voltage b be the point of minimum potential. Let x be supplied by point A while y be supplied by point B, y=I2-x Voltage drop between A and B = Voltage drop over AB If voltage of A is V1 and is greater than voltage of B which is V2 then, V1-V2=drop in all the section of AB The same equation can be written as, V1-drops over Ab= V2-drops over Bb
  • 26. V1-i1r1-i2r2=V2-i3r3-i4r4 V1-(I1+x)r1-xr2=V2-(I2-x)r3-(I2+I3-x)r4 Here V1 and V2 are known ,obtain x Current loading and voltage drop diagram
  • 27. D.C Distributor with Uniformly Distributed load Classified 1. Fed at one end 2.Fed at both the ends 1.Fed at one end (Distributed load ) Uniformly distributed load on 2 wire distributor , fed at one end I amperes per meter Total voltage drop is to be obtained by considering a point C(distance x),feeding end A Current tapped at point C is =total current current up to point C=i =i(l )
  • 28. dx near point C , its resistance rdx dV=i(l-x)rdx Total voltage drop upto point C Upto B, x=l 基 = 0 = 0 = ( 2 2 )0 基=( 2 2 ) volts equation of parabola 基=( 2 )=ir 2 2 = 1 2 (il)(rl) 基 = 1 2 腫
  • 29. Power loss=I2R,elementary length dx At point C X=l = [ ]2 = 0 2 2 2 + 2 = 2(2 22 2 + 3 3 ) = 23 3
  • 30. 2.Fed at both the ends (Uniformly Distributed load) 1.End at Equal voltages fed at point A and B are maintained at equal voltage The total current to be supplied is il amperes. As two end voltage are equal ,each end will supply half the required current i.e 2 . Midpoint distance l/2,point C at a distance x , current feeding is il/2 (A) Current at C= 2 = 2 Voltage drop over length dx is, = 2
  • 31. Upto point C is, 基 = 0 2 = 2 2 2 = 2 [ 2] Maximum voltage drop at midpoint x=l/2 ヰ = ir 2 4 2 8 = 2 8 = 1 8 = 腫 8 村 drop of fed at one end Power loss ,point c = [ 2 ]2 = 2 0 2 4 + 2 = 2 3 12
  • 32. 2.Ends at Unequal voltages Let point C be the point of minimum potential which at a distance x from feeding point A The current supplied by the feeding point A is ix The current supplied by the feeding point B is i(l-x) V1-drops over AC= V2-drops over BC In case of distributed load the drop is given by 2 2 for a length of l 基 = 2 2 p$ 巨 = ( )2 2 p$ 1 2 2 = 2 ( )2 2 X?
  • 33. Ring main distributor with interconnection Cable is arranged in the Loop fashion,fed at only one point Use for large area hence voltage drop across the various section become larger(excessive voltage drop). Solution:-distant point of ring distributor are joined together by a conductor this is called interconnection. Thevenins theorem = 乞 + 倹
  • 34. AC Distribution Advantages of AC Cheaper transformation between voltages Easy to switch off Less equipment needed More economical in general Rotating field
  • 35. Methods of solving A.C Distribution problem 1.power factor referred to receiving end voltage Resistance R , reactance X Impedance of section PR is given by, = 1 + 1. Impedance of section RQ is given by, = 2 + 2. The load current at point R is 1, 1 = 1(cos 1 sin 1) The load current at point Q is 2, 2 = 2(cos 2 sin 2) Current in section RQ is nothing but 腫 = 2 = 2(cos 2 sin 2) Current in section PR is 腫 = 1 + 2=1(cos 1 sin 1)+2(cos 2 sin 2)
  • 36. 1.power factor referred to receiving end voltage
  • 37. Voltage drop in section RQ, = 腫 =[2(cos 2 sin 2)].[ 2 + 2] Voltage drop in section PR , = 腫 =[1(cos 1 sin 1) + 2(cos 2 sin 2)][1 + 1]. Sending end voltage = + + Sending end current 腫 = 1 + 2
  • 38. 2. power factor referred to respective load voltages
  • 39. 2. power factor referred to respective load voltages Voltage drop in section RQ is given, = 2 =[2(cos 2 sin 2)].[ 2 + 2] = +drop of voltage in section RQ= 留. 1 = 1(cos 1 sin 1) w.r.t voltage 1 = 1(cos(1留) sin(1 留)) w.r.t voltage 腫 = 1 + 2 =1(cos(1留) sin(1 留)) +2(cos 2 sin 2) =[1(cos(1留) sin(1 留)) +2(cos 2 sin 2)].[1 + 1] Sending end voltage , = + +